PLC-…24UC/1/S/H
PLC-…24UC/1/S/L
PLC INTERFACE With Switch and Integrated
Power Contact Relay
INTERFACE
Data Sheet
101460_en_04
1
© PHOENIX CONTACT - 03/2008
Description
The 6.2 mm PLC-…24UC/1/S… PLC INTERFACE module
supports "Manual", "Zero", and "Automatic" functions. The
load can be switched directly using the module.
1.1
1.3
–
Switching Function
Depending on the version, the switch can be operated either
by hand or using a screwdriver.
A floating contact provides confirmation for the "Automatic"
switching state.
1.2
inserted in the bridge shafts. They eliminate the need for
complicated and time-consuming loop bridges.
Optimum Use of Plug-In Bridges
–
–
–
–
–
Additional Advantages
Environmentally friendly, cadmium-free power contact
material for loads up to 250 V AC/6 A
Integrated input/protective circuit
Safe isolation according to DIN EN 50178
Spring-cage and screw connection types available
6 kVrms electrical isolation between coil and contact
Floating confirmation contact for "Automatic" switching
state
The PLC INTERFACE module achieves maximum
efficiency with the user-friendly FBST plug-in bridge system.
The PLC-…24UC/1/S… makes effective use of the bridging
options for the A1/A2 connection on the coil side, for the
supply at connection 13 on the contact side, and for the
manual input at connection M. Especially effective here are
the 500 mm long color-insulated continuous plug-in bridges
that can easily be cut to the required length and quickly
Make sure you always use the latest documentation.
It can be downloaded at www.download.phoenixcontact.com.
A conversion table is available on the Internet at
www.download.phoenixcontact.com/general/7000_en_00.pdf.
This data sheet is valid for all products listed on the following page:
PLC-…24UC/1/S…
2
Ordering Data
PLC INTERFACE With Switch (Operation by Hand)
Description
Type
Order No.
Pcs./Pck.
PLC INTERFACE with switch (operation by hand) and integrated power
contact relay for "Manual", "Zero", and "Automatic" functions, with screw
connection, for mounting on 3
PLC-RSC- 24UC/1/S/H
2982236
10
PLC INTERFACE with switch (operation by hand) and integrated power
contact relay for "Manual", "Zero", and "Automatic" functions, with spring-cage
connection, for mounting on 3
PLC-RSP- 24UC/1/S/H
2982249
10
PLC INTERFACE With Switch (Operation Using a Screwdriver)
Description
Type
Order No.
Pcs./Pck.
PLC INTERFACE with switch (operation using a screwdriver) and integrated
power contact relay for "Manual", "Zero", and "Automatic" functions, with
screw connection, for mounting on 3
PLC-RSC- 24UC/1/S/L
2834876
10
PLC INTERFACE with switch (operation using a screwdriver) and integrated
power contact relay for "Manual", "Zero", and "Automatic" functions, with
spring-cage connection, for mounting on 3
PLC-RSP- 24UC/1/S/L
2834889
10
For the protection of input and output, inductive loads must be dampened with an effective protective circuit.
Accessories
Description
Type
Order No.
Pcs./Pck.
Insulating plate
PLC-ATP BK
2966841
25
The PLC-ATP BK insulating plate should be used in the following cases: always fit at the start and end of a PLC terminal strip for voltages
greater than 250 V (L1, L2, L3) between the same terminal points on adjacent modules (FBST 8-PLC... or FBST 500... can be used for
potential bridging) and for safe isolation between adjacent modules.
For additional accessories such as power terminal blocks and plug-in bridges, please refer to the INTERFACE catalog or www.phoenixcontact.com.
101460_en_04
PHOENIX CONTACT
2
PLC-…24UC/1/S…
3
Technical Data
Input Data
Input voltage UN
24 V AC/DC, 50 Hz ... 60 Hz
Permissible range (with reference to UN)
See "Operating Voltage Range" on page 4
Typical input current at UN
11 mA
Input circuit
Yellow LED, bridge rectifier
Output Data
Contact type
Single contact, 1 N/O contact
Contact material
Silver tin oxide AgSnO
Maximum switching voltage
250 V AC/DC1
Minimum switching voltage
12 V AC/DC
Limiting continuous current
6A
Maximum inrush current
On request
Minimum switching current
10 mA
Maximum shutdown power
Ohmic load τ = 0 ms
24 V DC 140 W
48 V DC 20 W
60 V DC 18 W
110 V DC 23 W
220 V DC 40 W
250 V AC 1500 VA
Minimum switching power
1
120 mW
The PLC-ATP BK insulating plate must be installed for voltages greater than 250 V (L1, L2, L3) between the same terminal points on adjacent modules
(see "Accessories"). FBST 8-PLC... or FBST 500... is then used for potential bridging.
General Data
Rated insulation voltage
250 V AC
Impulse voltage withstand level
6 kV
Ambient temperature range
Operation
-25°C ... 60°C
Storage/transport
-20°C ... 85°C
Nominal operating mode
100% operating factor
Inflammability class according to UL 94 (housing)
V0
Air and creepage distances between the circuits
DIN EN 50178/VDE 0160 (safe isolation, reinforced insulation I/O)
Standards/specifications
IEC 60664, IEC 60664 A, DIN VDE 0110, DIN EN 50155/VDE 0115-200 (in
relevant parts), IEC 60255/DIN VDE 0435 (in relevant parts)
Pollution degree
2
Surge voltage category
III
Mounting position
Any
Mounting
Can be aligned without spacing
Conductor cross-section
Solid, with screw connection
0.14 mm2 ... 2.5 mm2 (26 - 14 AWG)
Stranded, with screw connection
0.14 mm2 ... 1.5 mm2 (26 - 14 AWG)
Solid, with spring-cage connection
0.2 mm2 ... 2.5 mm2 (24 - 14 AWG)
Stranded, with spring-cage connection
0.2 mm2 ... 1.5 mm2 (24 - 14 AWG)
Stripping length
Screw connection
10 mm
Spring-cage connection
8 mm
Dimensions (W x H x D)
6.2 mm x 94 mm x 80 mm
Housing material
Polybutylene terephthalate PBT, non-reinforced, green
101460_en_04
PHOENIX CONTACT
3
PLC-…24UC/1/S…
Confirmation
"Automatic" mode, floating
30 V AC/DC / 50 mA, maximum
2 V AC/DC / 1 mA, minimum
Approvals
CE
c
UL/CUL
Applied for
GL
Planned
4
Application Example
6
VCC
Operating Voltage Range
U
U N 1,4
+-
A
1,3
1,2
1,1
UN= 24 V DC / 24 V AC
A1
1
A2
CTL2
0,9
0,8
A
O
M
0,7
B
20
25
30
35
40
45
50
CTL1
55
60 65
TU [ ° C]
M
13
General Conditions
14
Direct alignment in the block, all devices 100% operating
factor, horizontal or vertical mounting.
Curve A
5
Maximum permissible continuous voltage Umax with limiting
continuous current on the contact side
Block Diagram
Curve B
A2
13
M
A1
1(CTL)
101460_en_04
0
Minimum permissible relay operate voltage Uop following
pre-excitation
14
2(CTL)