https://www.phoenixcontact.com/us/products/2835613
Signal isolator - PI-EX-IDS-I/I - 2835613
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://download.phoenixcontact.com)
Ex-i output signal conditioner, HART-capable. Isolates and sends intrinsically safe 0/4-20 mA signals to a load
(I/P converters, control valves, displays) in Ex areas. Galvanic 3-way isolation (input / output / supply). Line fault
detection.
Key commercial data
Packing unit
1 PCE
Weight per Piece (excluding packing)
106.8 GRM
Custom tariff number
85437090
Country of origin
Germany
Technical data
Note:
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
12.4 mm
Height
145 mm
Depth
147 mm
Ambient conditions
Ambient temperature (operation)
-20 °C ... 55 °C (see data sheet)
Ambient temperature (storage/transport)
-40 °C ... 80 °C
Permissible humidity (operation)
5 % ... 95 % (no condensation)
Degree of protection
IP20
Input data
Signal input
Current input
12/4/13 Page 1 / 5
https://www.phoenixcontact.com/us/products/2835613
Signal isolator - PI-EX-IDS-I/I - 2835613
Technical data
Input data
Current input signal
4 mA ... 20 mA
0 mA ... 20 mA
Input resistance current input
5.4 V (at 20 mA)
Input current range
0 mA ... 22 mA
Output data
Signal output
Intrinsically safe
Current output signal
4 mA ... 20 mA
0 mA ... 20 mA
Load/output load current output
≤ 800 Ω
Output ripple (current)
< 50 µAPP (For 800 Ω)
Power supply
Supply voltage range
20 V DC ... 35 V DC
Max. current consumption
< 15 mA (At 24 V DC / 0 mA)
Power consumption
max. 1.2 W (At 24 V DC / 20 mA)
General
No. of channels
1
Maximum transmission error
≤ 0.1 % (Of end value (at 20°C))
Maximum temperature coefficient
< 0.01 %/K
Step response (10-90%)
< 140 µs
Status display
Green LED (supply voltage, PWR)
Inflammability class according to UL 94
V0
Standards/regulations
NAMUR recommendation NE 21
Housing material
PBT and polyamide PA non-reinforced
Color
green
Name
Input/output
Electrical isolation
375 V (Peak value in accordance with EN 60079-11)
Name
Input/power supply
Electrical isolation
1.5 kV (50 Hz, 1 min., test voltage)
Name
Output/supply
Electrical isolation
375 V (Peak value in accordance with EN 60079-11)
Conformance
CE-compliant
ATEX
II (1) GD [EEx ia] IIC
II 3 G Ex nA II T4 X
UL, USA / Canada
UL applied for
Data communication (bypass)
12/4/13 Page 2 / 5
https://www.phoenixcontact.com/us/products/2835613
Signal isolator - PI-EX-IDS-I/I - 2835613
Technical data
Data communication (bypass)
HART function
Yes
Protocols supported
HART
Safety data
Max. inductance Li
0.1 mH
Max. capacitance Ci
5 nF
Max. output voltage Uo
27.7 V
Max. output current Io
92 mA
Max. output power Po
638 mW
Gas group
IIB
Max. external inductivity Lo
15 mH
Max. external capacity Co
658 nF
Additional text
The maximum values should be used either solely as concentrated
capacitance values or solely as concentrated inductance values, or as
cable reactance values
Gas group
IIB
Max. external inductivity Lo
1.9 mH
Max. external capacity Co
295 nF
Additional text
The maximum values should also be used as concentrated capacitance
values and concentrated inductance values.
Safety-related maximum voltage Um
250 V AC
Gas group
IIC
Max. external inductivity Lo
1.2 mH
Max. external capacity Co
80 nF
Additional text
The maximum values should be used either solely as concentrated
capacitance values or solely as concentrated inductance values, or as
cable reactance values
Gas group
IIC
Max. external inductivity Lo
0.4 mH
Max. external capacity Co
64 nF
Additional text
The maximum values should also be used as concentrated capacitance
values and concentrated inductance values.
Classifications
eCl@ss
eCl@ss 4.0
27210121
eCl@ss 4.1
27210121
eCl@ss 5.0
27210121
12/4/13 Page 3 / 5
https://www.phoenixcontact.com/us/products/2835613
Signal isolator - PI-EX-IDS-I/I - 2835613
Classifications
eCl@ss
eCl@ss 5.1
27210121
eCl@ss 6.0
27210121
eCl@ss 7.0
27210121
eCl@ss 8.0
27210121
ETIM
ETIM 2.0
EC001431
ETIM 3.0
EC001596
ETIM 4.0
EC001596
ETIM 5.0
EC001596
UNSPSC
UNSPSC 6.01
30211506
UNSPSC 7.0901
39121008
UNSPSC 11
39121008
UNSPSC 12.01
39121008
UNSPSC 13.2
39121008
Accessories
Additional products
Basic terminal block - PI-EX-TB - 2835901
Ex base terminal block for intrinsically safe signals with knife disconnection and test connections
Surge protection device - TT-PI-EX-TB - 2858386
Intrinsically safe basic terminal block with isolating connector, test connections and surge protection, for mounting on NS
35/7.5
12/4/13 Page 4 / 5
https://www.phoenixcontact.com/us/products/2835613
Signal isolator - PI-EX-IDS-I/I - 2835613
Accessories
Basic terminal block - PI-EX-ES-1/3 - 2835325
Ex basic terminal block, with three terminal points to the field level (Ex area)
Drawings
Block diagram
Dimensioned drawing
145
OUT
12,4
IN
0/4...20mA
4...20mA
+
0/4...20mA
+-
UB+
UB-
- +- +
UB+
UB+
UB-
PWR
UB-
147
P
-
PI-EX-IDS-I/I
© Phoenix Contact 2013 - all rights reserved
http://www.phoenixcontact.com
12/4/13 Page 5 / 5
很抱歉,暂时无法提供与“2835613”相匹配的价格&库存,您可以联系我们找货