Extract from the online
catalog
IB IL CNT
Order No.: 2836337
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2836337
Inline counter terminal block, without accessories, 1 counter input, 1
control input, 1 output, 24 V DC, 500 mA, 3-wire connection method
Product notes
WEEE/RoHS-compliant since:
03/03/2008
Commercial data
GTIN (EAN)
4
017918
160838
sales group
K413
Pack
1 pcs.
Customs tariff
85389091
Catalog page information
Page 90 (AX-2007)
http://
www.download.phoenixcontact.com
Please note that the data given
here has been taken from the
online catalog. For comprehensive
information and data, please refer
to the user documentation. The
General Terms and Conditions of
Use apply to Internet downloads.
Product description
The Inline IB IL CNT counter terminal registers and processes quick pulse trains from sensors. It has a counter input, a
control input, and a switching output that can be parameterized by the module itself. This way, quick response times can
be achieved independent of the bus and the control system.
The module can be operated in different operating modes:
- Event counting
- Time measurement and
- Pulse generation
PHOENIX CONTACT Deutschland GmbH
http://www.phoenixcontact.de
Page 1 / 6
Feb 8, 2011
IB IL CNT Order No.: 2836337
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2836337
The inputs can be used to connect initiators with 24 V DC supply and 5 V DC supply. The switching output supplies a
maximum current of 500 mA.
The Inline counter terminals can be labeled using hinged labeling fields. The fields have insert cards that can be labeled
individually to suit the application. Additionally, there is the ZB-FM-6... Zack strip for labeling the terminal points.
Technical data
Interfaces
Interface
Inline local bus
Type of connection
Inline data jumper
Transmission speed
500 kBit/s
Transmission physics
Copper
Power supply
Max. current consumption
50 mA
Typical current consumption
40 mA
I/O voltage
24 V DC (via voltage jumper)
Ripple
5%
Peripherals voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Initiator power supply
Segment circuit (500 mA)
Comments
The following are connected to the segment circuit US: Switching
output, sensor supplies with their own short-circuit protection
Electrical isolation
Test section
5 V supply, incoming remote bus/7.5 V supply (bus logics) 500 V
AC 50 Hz 1 min
5 V supply, outgoing remote bus/7.5 V supply (bus logics) 500 V
AC 50 Hz 1 min
7.5 V supply (bus logics)/24 V supply (I/O) 500 V AC 50 Hz 1 min
24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min
Counter input
Number of inputs
2
Operating mode
Event counting, frequency/time measurement, pulse generator
Input frequency
100 kHz
Input voltage
24 V DC
5 V DC
Input current
PHOENIX CONTACT Deutschland GmbH
http://www.phoenixcontact.de
5 mA (typical)
Page 2 / 6
Feb 8, 2011
IB IL CNT Order No.: 2836337
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2836337
Control input
Number of inputs
2
Connection method
2, 3-conductor
Input voltage
24 V DC
5 V DC
Input current
5 mA (typical)
Outputs
Number of outputs
1
Connection method
2-wire (shielded)
Output voltage
24 V DC
Output current
500 mA
General data
Weight
94 g
Number of connectors
2
Degree of protection
IP20
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
Connection data
Inline connectors Spring-cage connection 0.08 mm² 1.5 mm² 0.08
mm² 1.5 mm² 28 16
Width
24.4 mm
Height
119.8 mm
Depth
71.5 mm
Inline potential routing
Communications power UL
7.5 V DC (via voltage jumper)
Current consumption from UL
max. 50 mA
max. 50 mA
Segment supply voltage US
24 V DC
Current consumption from US
max. 1 A
Certificates / Approvals
Certification
ABS, CUL, DNV, GL, GOST, UL
Certifications applied for:
LR / BV
PHOENIX CONTACT Deutschland GmbH
http://www.phoenixcontact.de
Page 3 / 6
Feb 8, 2011
IB IL CNT Order No.: 2836337
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2836337
Accessories
Item
Designation
Description
0809492
ESL 62X10
Insert strip for laser printer, lettering field: 62 x 10 mm
2727501
IB IL FIELD 2
Labeling field, width: 12.2 mm
2732664
IB IL AO/CNT-PLSET
Connector set
2726353
IB IL SCN-6 SHIELD
Inline shield connector
2726337
IB IL SCN-8
Connector, for digital 1, 2 or 8-channel Inline terminals
Marking
Plug/Adapter
Diagrams/Drawings
Connection diagram
PHOENIX CONTACT Deutschland GmbH
http://www.phoenixcontact.de
Page 4 / 6
Feb 8, 2011
IB IL CNT Order No.: 2836337
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2836337
Block diagram
Dimensioned drawing
FAQs
•
Apparent measurement error in the operating mode "Time-controlled frequency measurement"
Due to predefined structures in the microcontroller used, the conversion time for the operating mode "Timecontrolled frequency measurement" can only be set in steps. It is therefore not possible to set the conversion times
to exactly the nominal values, such as 1 s or 10 ms. The actual conversion times are approx. 0.16% shorter than the
nominal values. There is therefore an apparent measurement error of -0.16% in this operating mode.
•
How high is the rated current consumption from the various voltage areas?
For 7.5 V supply of the bus logic (UL), the nominal current consumption of the module is typ. 40 mA and max. 50
mA. The 24 V supply of the switching output and the sensor supply is provided via the segment circuit (US). The
nominal current consumption here is 1 A. There is thus a maximum current consumption of a total of 1.05 A from the
voltage areas of UL and US.
PHOENIX CONTACT Deutschland GmbH
http://www.phoenixcontact.de
Page 5 / 6
Feb 8, 2011
IB IL CNT Order No.: 2836337
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2836337
Address
PHOENIX CONTACT Deutschland GmbH
Flachsmarktstr. 8
32825 Blomberg,Germany
Phone +49 5235 3 12000
Fax +49 5235 3 41200
http://www.phoenixcontact.de
© 2011 Phoenix Contact
Technical modifications reserved;
PHOENIX CONTACT Deutschland GmbH
http://www.phoenixcontact.de
Page 6 / 6
Feb 8, 2011
很抱歉,暂时无法提供与“2836337”相匹配的价格&库存,您可以联系我们找货
免费人工找货