Protective plug PT with HF protective circuit for 4 signal wires. Nominal voltage: 5 V DC
The illustration shows variant PT
5-HF-12 DC-ST
Why buy this product
High transmission speed
High discharge capacity
Plugs can be checked with CHECKMASTER
Key commercial data
Packing unit
1
Minimum order quantity
10
Catalog page
Page 100 (TT-2011)
GTIN
Custom tariff number
85363010
Country of origin
GERMANY
Technical data
General
Housing material
PA
Inflammability class according to UL 94
V0
Color
black
Standards for air and creepage distances
DIN EN 61664-1
Standards for air and creepage distances
IEC 60664-1
Total surge current (8/20) µs
20 kA
Ambient temperature (operation)
-40 °C ... 85 °C
Mounting type
On base element
Design
DIN rail module, two-section, divisible
Number of positions
5
05.10.2012 Page 1 / 7
https://www.phoenixcontact.com/us/produkte/2838762
Surge protection connector - PT 5-HF-5DC-ST - 2838762
Technical data
General
Degree of protection
IP20
Direction of action
Line-Line & Line-Signal Ground/Shield & optional Signal Ground/
Shield-Earth Ground
Arrester can be tested with CHECKMASTER from software
version:
From SW rev. 1.00
Width
17.7 mm
Height
45 mm
Depth
52 mm
Pitch unit
1 Div.
Protective circuit
IEC category
C1
IEC category
C2
IEC category
C3
IEC category
D1
VDE requirement class
C1
VDE requirement class
C2
VDE requirement class
C3
VDE requirement class
D1
Nominal voltage UN
5 V DC
Maximum continuous operating voltage UC
5.2 V DC
Maximum continuous operating voltage UC
3.6 V AC
Maximum continuous voltage UC (wire-wire)
5.2 V DC
Maximum continuous voltage UC (wire-wire)
3.6 V AC
Maximum continuous voltage UC (wire-ground)
5.2 V DC (with PT 2x2-BE)
Nominal current IN
450 mA (45°C)
Operating effective current IC at UC
≤ 300 µA
Ground conductor current IPE
≤ 300 µA (with PT 2x2-BE)
Ground conductor current IPE
≤ 1 µA (with PT 2x2+F-BE)
Nominal discharge surge current In (8/20) µs (Core-Core)
10 kA
Nominal discharge surge current In (8/20) µs (Core-Earth)
10 kA
Total surge current (8/20) µs
20 kA
Max. discharge surge current Imax (8/20) µs maximum (CoreCore)
10 kA
Max. discharge surge current Imax (8/20) µs maximum (CoreEarth)
10 kA
Nominal pulse current Ian (10/1000) µs (Core-Core)
90 A
Lightning test current (10/350) µs, peak value limp
2.5 kA
Output voltage limitation at 1 kV/µs (Core-Core) spike
≤ 55 V
Output voltage limitation at 1 kV/µs (Core-Earth) spike
≤ 55 V (PT 2x2-BE)
Output voltage limitation at 1 kV/µs (Core-Earth) spike
≤ 700 V (with PT 2x2+F-BE)
Output voltage limitation at 1 kV/µs (Core-Core) static
≤ 15 V
Output voltage limitation at 1 kV/µs (Core-Earth) static
≤ 15 V
Output voltage limitation at 1 kV/µs (Core-Earth) static
≤ 30 V (PT 2x2+F-BE)
05.10.2012 Page 2 / 7
https://www.phoenixcontact.com/us/produkte/2838762
Surge protection connector - PT 5-HF-5DC-ST - 2838762
Technical data
Protective circuit
Residual voltage at In, (conductor-conductor)
≤ 15 V
Residual voltage at In, (conductor-ground)
≤ 30 V (with PT 2x2-BE)
Residual voltage at In, (conductor-GND)
≤ 15 V (with PT 2x2-BE)
Residual voltage with Ian (10/1000)µs (conductor-conductor)
≤ 15 V
Residual voltage with Ian (10/1000)µs (conductor-GND)
≤ 15 V
Protection level UP (Core-Core)
≤ 100 V (C2 (10 kV/5 kA))
Protection level UP (Core-Core)
≤ 34 V (C3 - 25 A)
Protection level UP (Core-Earth)
≤ 100 V (C2 (10 kV/5 kA) with BE 2839208)
Protection level UP (Core-Earth)
≤ 600 V (C2 (10 kV/5 kA) with BE 2839224)
Protection level UP (Core-Earth)
≤ 34 V (C3 - 25 A)
Protection level UP (Core-GND)
≤ 38 V (C3 - 25 A)
Response time tA (Core-Core)
≤ 500 ns
Response time tA (Core-Earth)
≤ 500 ns
Input attenuation aE, sym.
Typ. 0.2 dB (≤ 5 MHz / 100 Ω)
Cut-off frequency fg (3 dB), sym. in 100 Ohm system
Typ. 70 MHz
Capacity (Core-Core)
Typ. 30 pF
Resistance in series
2.2 Ω ±10 %
Max. required back-up fuse
500 mA (e.g. T in acc. with IEC 127-2/III)
Surge carrying capacity in acc. with IEC 61643-21 (Core-Core)
C2 (10 kV/5 kA)
Surge carrying capacity in acc. with IEC 61643-21 (Core-Core)
C3 (90 A)
Surge carrying capacity in acc. with IEC 61643-21 (Core-Earth)
C2 (10 kV/5 kA)
Surge carrying capacity in acc. with IEC 61643-21 (Core-Earth)
C3 (90 A)
Surge carrying capacity in acc. with IEC 61643-21 (Core-Earth)
D1 (2.5 kA)
Connection data
Connection method
Screw connection (in connection with the base element)
Connection type IN
PLUGTRAB plug-in system
Connection type OUT
PLUGTRAB plug-in system
Classifications
eclass
eCl@ss 4.0
27140201
eCl@ss 4.1
27130801
eCl@ss 5.0
27130801
eCl@ss 5.1
27130801
eCl@ss 6.0
27130807
eCl@ss 7.0
27130807
etim
ETIM 2.0
EC000943
ETIM 3.0
EC000943
ETIM 4.0
EC000943
05.10.2012 Page 3 / 7
https://www.phoenixcontact.com/us/produkte/2838762
Surge protection connector - PT 5-HF-5DC-ST - 2838762
Classifications
unspsc
UNSPSC 6.01
30212010
UNSPSC 7.0901
39121610
UNSPSC 11
39121610
UNSPSC 12.01
39121610
UNSPSC 13.2
39121620
Approvals
Approvals
Approvals
UL Listed / GOST
Ex Approvals
UL Listed / cUL Listed / cULus Recognized
Approvals submitted
Approval details
UL Listed
Nominal current IN
0.45 A
Nominal voltage UN
5V
GOST
Accessories
Accessories
Marking
05.10.2012 Page 4 / 7
https://www.phoenixcontact.com/us/produkte/2838762
Surge protection connector - PT 5-HF-5DC-ST - 2838762
Accessories
Marker pen - X-PEN 0,35 - 0811228
Marker pen without ink cartridge, for manual labeling of markers, labeling extremely wipe-proof, line
thickness 0.35 mm
Zack Marker strip, flat - ZBF 5:UNBEDRUCKT - 0808642
Zack Marker strip, flat, Strip, white, Unlabeled, Can be labeled with: Plotter, Mounting type: Snap into flat
marker groove, For terminal block width: 5 mm, Lettering field: 5.1 x 5.2 mm
Zack Marker strip, flat - ZBF 5/WH-100:UNBEDRUCKT - 0808668
Zack Marker strip, flat, Strip, white, Unlabeled, Can be labeled with: Plotter, Mounting type: Snap into flat
marker groove, For terminal block width: 5 mm, Lettering field: 5.15 x 5.15 mm
Zack Marker strip, flat - ZBF 5,LGS:FORTL.ZAHLEN - 0808671
Zack Marker strip, flat, Strip, white, Labeled, Printed horizontally: Consecutive numbers 1 - 10, 11 - 20, etc.
up to 491 - 500, Mounting type: Snap into flat marker groove, For terminal block width: 5 mm, Lettering field:
5.15 x 5.15 mm
Zack Marker strip, flat - ZBF 5,LGS:GERADE ZAHLEN - 0810821
Zack Marker strip, flat, Strip, white, Labeled, Printed horizontally: Consecutive numbers 2 - 20, 22 - 40, etc.
up to 82 - 100, Mounting type: Snap into flat marker groove, For terminal block width: 5 mm, Lettering field:
5.15 x 5.15 mm
Zack Marker strip, flat - ZBF 5,LGS:UNGERADE ZAHLEN - 0810863
Zack Marker strip, flat, Strip, white, Labeled, Printed horizontally: Odd numbers 1 - 19, 21 - 39, etc. up to
81 - 99, Mounting type: Snap into flat marker groove, For terminal block width: 5 mm, Lettering field: 5.15 x
5.15 mm
05.10.2012 Page 5 / 7
https://www.phoenixcontact.com/us/produkte/2838762
Surge protection connector - PT 5-HF-5DC-ST - 2838762
Accessories
Zack Marker strip, flat - ZBF 5,QR:FORTL.ZAHLEN - 0808697
Zack Marker strip, flat, Strip, white, Labeled, Printed vertically: Consecutive numbers 1 - 10, 11 - 20, etc.
up to 91 - 100, Mounting type: Snap into flat marker groove, For terminal block width: 5 mm, Lettering field:
5.15 x 5.15 mm
Zack marker strip - ZBN 18:UNBEDRUCKT - 2809128
Zack marker strip, Strip, white, Unlabeled, Can be labeled with: Plotter, Mounting type: Snap into tall marker
groove, For terminal block width: 18 mm, Lettering field: 18 x 5 mm
Necessary add-on products
Surge protection base element - PT 2X2-BE - 2839208
Base element for protective plug PT with protective circuit for two 2-wire floating signal circuit, bridge
between the connections 3-4 (GND) and 9-10, for mounting on NS 35/7.5 and NS 35/15, housing width:
17.5 mm
Additional products
Shield connection - SSA 3-6 - 2839295
shield fast connections for conductor diameter 3 - 6 mm. Potential connection cable: 200 mm, black
Shield connection - SSA 5-10 - 2839512
Shield fast connection for conductor diameters 5 - 10 mm. Potential connection cable: 200 mm, black
Drawings
05.10.2012 Page 6 / 7
https://www.phoenixcontact.com/us/produkte/2838762
Surge protection connector - PT 5-HF-5DC-ST - 2838762
Dimensioned drawing
Circuit diagram
90
1
2
5
6
7
8
11
12
44,8
OUT
65,5
IN
51,5
9
3
*
10
4
The figure shows the complete module consisting of a base element
and connector
Diagram
© Phoenix Contact 2012 - all rights reserved
http://www.phoenixcontact.com
05.10.2012 Page 7 / 7