IB IL 24 DI 16 ...
1 2
1 2
D
1 2
Inline Terminal With 16 Digital Inputs
1 2
3 4
3 4
3 4
3 4
DI16
4x
Data Sheet
5553_en_04
m
AUTOMATIONWORX
© PHOENIX CONTACT - 09/2007
Description
on
l
in
ec
om
po
ne
–
–
Connections for 16 digital sensors
Connection of sensors in 2 and 3-wire technology
Maximum permissible load current per sensor: 250 mA
Maximum permissible load current from the terminal:
4.0 A
Diagnostic and status indicators
IB IL 24 DI 16 and IB IL 24 DI 16-PAC:
Approved for use in potentially explosive areas
(observe the notes on page 6)
s.
–
–
–
–
nt
The terminal is designed for use within an Inline station. It is
used to acquire digital signals.
co
Features
This data sheet is only valid in association with the IL SYS INST UM E user manual or the Inline system manual
for your bus system.
Please note that the numbering of the terminal points differs for the various connector versions (see Figure 2
on page 5).
Make sure you always use the latest documentation.
It can be downloaded at www.download.phoenixcontact.com.
A conversion table is available on the Internet at
www.download.phoenixcontact.com/general/7000_en_00.pdf.
This data sheet is valid for all products listed on the following page:
IB IL 24 DI 16 ...
Ordering Data
Products
Description
Order No.
Pcs./Pck.
IB IL 24 DI 16-PAC
2861250
1
Terminal with 16 digital inputs; complete with accessories
(connectors not consecutively numbered and labeling fields);
transmission speed of 500 kbps
IB IL 24 DI 16-PAC/SN
2862958
1
Terminal with 16 digital inputs; without accessories;
transmission speed of 500 kbps
IB IL 24 DI 16
2726230
1
Terminal with 16 digital inputs; complete with accessories
(connectors not consecutively numbered and labeling fields);
transmission speed of 2 Mbps
IB IL 24 DI 16-2MBD-PAC
2861595
1
Terminal with 16 digital inputs; complete with accessories
(connectors not consecutively numbered and labeling fields);
transmission speed of 2 Mbps
IB IL 24 DI 16-2MBD-PAC/SN
Terminal with 16 digital inputs; without accessories;
transmission speed of 2 Mbps
IB IL 24 DI 16-2MBD
m
Type
Terminal with 16 digital inputs; complete with accessories
(connectors consecutively numbered and labeling fields);
transmission speed of 500 kbps
1
co
2878120
1
s.
2855114
ne
nt
Four of the listed connectors or one connector set are needed for the complete fitting of the IB IL 24 DI 16 and IB IL 24 DI 16-2MBD.
Accessories
Description
po
Type
Order No.
Pcs./Pck.
Connector with twelve spring-cage connections (green, without color print)
IB IL SCN-12
2726340
10
Connector with twelve spring-cage connections (green, with color print)
IB IL SCN-12-ICP
2727611
10
IB IL DI/DO 16-PLSET
2860976
1
IB IL DI 16-PLSET/ICP
2860989
1
Documentation
Description
om
Connector set with 48 spring-cage connections (green, without color print)
Connector set numbered consecutively with 48 spring-cage connections
(green, with color print)
Order No.
Pcs./Pck.
IL SYS INST UM E
2698737
1
"Configuring and Installing the INTERBUS Inline Product Range"
user manual
IB IL SYS PRO UM E
2743048
1
"INTERBUS Addressing"
data sheet
DB GB IBS SYS ADDRESS
9000990
1
"Inline Terminals for Use in Zone 2 Potentially Explosive Areas"
application note
AH EN IL EX ZONE 2
7217
1
"Addressing of 16-Channel Inline Terminals"
application note
AH IB IL 24 DI/DO 16 ADDRESS
9014124
1
on
l
in
ec
Type
"Automation Terminals of the Inline Product Range"
user manual
5553_en_04
PHOENIX CONTACT
2
IB IL 24 DI 16 ...
Technical Data
General Data
Housing dimensions (width x height x depth)
48.8 mm x 120 mm x 71.5 mm
Weight
122 g (without connectors), 210 g (with connectors)
Operating mode
Process data mode with 1 word
Connection method for sensors
2 and 3-wire technology
Permissible temperature (operation)
-25°C to +55°C
Permissible temperature (storage/transport)
-25°C to +85°C
Permissible humidity (operation/storage/transport)
10% to 95% according to DIN EN 61131-2
Permissible air pressure (operation/storage/transport)
70 kPa to 106 kPa (up to 3000 m above sea level)
IP20 according to IEC 60529
Protection class
Class 3 according to EN 61131-2, IEC 61131-2
m
Degree of protection
Connection data for connectors
Spring-cage terminals
Conductor cross-section
0.2 mm2 to 1.5 mm2 (solid or stranded), 24 - 16 AWG
Interface
Through data routing
s.
Local bus
co
Connection method
nt
Transmission Speed
IB IL 24 DI 16-PAC
500 kbps
500 kbps
ne
IB IL 24 DI 16-PAC/SN
IB IL 24 DI 16
500 kbps
IB IL 24 DI 16-2MBD-PAC
2 Mbps
2 Mbps
po
IB IL 24 DI 16-2MBD-PAC/SN
IB IL 24 DI 16-2MBD
2 Mbps
om
Supply of the Module Electronics and I/O Through Bus Terminal/Power Terminal
Connection method
Communications power
in
ec
Power Consumption
Current consumption from the local bus
Through potential routing
500 kbps
2 Mbps
7.5 V
7.5 V
60 mA, maximum
80 mA, maximum
Power consumption from the local bus
0.45 W, maximum
0.6 W, maximum
Segment supply voltage US
24 V DC (nominal value)
24 V DC (nominal value)
4 A, maximum
4 A, maximum
on
l
Nominal current consumption at US
Digital Inputs
Number
Input design
16
According to EN 61131-2 Type 1
Definition of switching thresholds
Maximum low-level voltage
ULmax < 5 V
Minimum high-level voltage
UHmin > 15 V
Common potentials
Segment supply, ground
Nominal input voltage UIN
24 V DC
Permissible range
-30 V < UIN < +30 V DC
Nominal input current for UIN
3 mA, minimum
Delay time
None
Permissible cable length to the sensor
30 m (to ensure conformance with EMC directive 89/336/EEC)
Use of AC sensors
AC sensors in the voltage range < UIN are limited in application (according to
the input design)
5553_en_04
PHOENIX CONTACT
3
IB IL 24 DI 16 ...
Characteristic Curve: Current Depending on the Input Voltage and the Ambient Temperature TA
Supply Voltage
Input Current
Input Current for t >= 20 s
For TA = 25°C
For TA = 55°C
18 V
3.0 mA
2.9 mA
2.5 mA
24 V
3.9 mA
3.8 mA
3.5 mA
30 V
4.5 mA
4.2 mA
3.0 mA
The current is reduced depending on the ambient temperature TA and the number of inputs that are switched on (internal module temperature).
Power Dissipation
Formula to Calculate the Power Dissipation of the Electronics
500 kbps
2 Mbps
16
m
16
PEL = 0.6 W + S [ UINn x 0.003 A ]
PEL = 0.525 W + S [ UINn x 0.003 A ]
n=1
Where
PEL
n
UINn
co
n=1
Total power dissipation in the terminal
Index of the number of set inputs n = 1 to 16
Input voltage of input n
s.
Power Dissipation of the Housing PHOU
2.8 W, maximum (within the permissible operating temperature)
nt
Limitation of Simultaneity, Derating
No limitation of simultaneity, no derating
ne
Derating
Error Messages to the Higher-Level Control or Computer System
po
None
Safety Equipment
Overload in segment circuit
No
om
Surge voltage
Polarity reversal
Protective elements in the power terminal
Protective elements in the power terminal
in
ec
Electrical Isolation/Isolation of the Voltage Areas
To provide electrical isolation between the logic level and the I/O area it is necessary to supply the station bus coupler and the digital input
terminal described here via the bus coupler or a power terminal from separate power supply units. Interconnection of the power supply
units in the 24 V area is not permitted (see also user manual).
Common Potentials
on
l
The 24 V main voltage, 24 V segment voltage, and GND have the same potential. FE is a separate potential area.
Separate Potentials in the System Consisting of Bus Terminal/Power Terminal and I/O Terminal
Test Distance
Test Voltage
5 V supply incoming remote bus/7.5 V supply (bus logic)
500 V AC, 50 Hz, 1 min.
5 V supply outgoing remote bus/7.5 V supply (bus logic)
500 V AC, 50 Hz, 1 min.
7.5 V supply (bus logic)/24 V supply (I/O)
500 V AC, 50 Hz, 1 min.
24 V supply (I/O)/functional earth ground
500 V AC, 50 Hz, 1 min.
Approvals
For the latest approvals, please visit www.download.phoenixcontact.com or eshop.phoenixcontact.com.
5553_en_04
PHOENIX CONTACT
4
IB IL 24 DI 16 ...
Local Diagnostic and Status Indicators and Terminal Point Assignment
Local Diagnostic and Status Indicators
Terminal Point Assignment for Each Connector
A
D
1
1
2
1
3
2
4
3
2
1 .1
3
4
B
1
x
2
3
4
4 x
1
4
2
x
x
1
2
2 .2
1
2 .1
1 .1
1
2
1
2
1
2
1
2
1 .1
2 .1
3 .1
4 .1
5 .1
6 .1
7 .1
8 .1
1 .2
2 .2
3 .2
4 .2
5 .2
6 .2
7 .2
8 .2
1 .3
2 .3
3 .3
4 .3
5 .3
6 .3
7 .3
8 .3
1
1 1
1 1
x
1
2
8 .2
3
8 .3
4
8 .4
5
8 .5
6
8 .6
1 1
8 .1
D I1 6
2
1 .3
3
3
1 .4
4
4
1 .2
2 .3
1 .3
2 .4
1 .4
2 .5
1 .5
2
2 2
3
3 3
1 .4
ne
A
om
po
Des.
Color Meaning
D
Green Diagnostics
For Each Connector
1, 2, 3, 4 Yellow Status indicators of the inputs
Light blue
–
–
B
–
on
l
in
ec
2 Mbps: White stripe in the vicinity of the D LED
–
co
2 .6
1 .6
5
1 .6
4 .5
3 .6
4 .6
5 5
2 .6
6
3 .5
6 6
5 .4
6 .4
4 4
5 .5
6 .5
5 .6
6 .6
5 5
6 6
7 .4
8 .4
4 4
7 .5
8 .5
7 .6
8 .6
5 5
6 6
6 9 9 0 A 0 0 3
Terminal point numbering:
individual connectors (A) and connector
sets (B)
Using the IB IL 24 DI 16-PAC/SN and
IB IL 24 DI 16-2MBD-PAC/SN with the
connectors provided
Using individual connectors
(IB IL SCN-12 or IB IL SCN-12-ICP)
Using the IB IL 24 DI 16-PAC and
IB IL 24 DI 16-2MBD-PAC with the original
connector set
Using the IB IL 24 DI 16-PLSET/ICP or
IB IL DI/DO 16-PLSET connector sets
Terminal
Point
x.1
x.2
x.3
x.4
x.5
x.6
5553_en_04
6
Figure 2
Local diagnostic and status indicators
Function Identification
6
4 .4
3 3
nt
5 5 5 3 D 0 0 3
Figure 1
5
3 .4
2 .5
2 2
3 3
4 4
s.
1 .6
5
2 .4
4
1 .5
1 .5
2 2
m
1 .2
Assignment
Signal input (IN)
Segment voltage US
for 2 and 3-wire termination
Ground contact (GND)
for 3-wire termination
Signal input (IN)
Segment voltage US
for 2 and 3-wire termination
Ground contact (GND)
for 3-wire termination
PHOENIX CONTACT
5
IB IL 24 DI 16 ...
Notes on Using the Terminal in Potentially Explosive Areas
for the IB IL 24 DI 16 and IB IL 24 DI 16-PAC Terminals
Approval According to EC Directive 94/9 (ATEX)
II 3G Ex nAC IIC T4 X
UL
xx
LISTED
31ZN
Proc. Ctrl. Eqpt. For Haz. Locs.
Cl. I, Zn. 2, AEx nC IIC T5
Cl. I, Zn. 2, Ex nC IIC T5
Cl. I, Div. 2, Grp. A,B,C,D T5
5561C001
Typical labeling of terminals for use in
potentially explosive areas
on
l
Figure 3
GL
in
ec
INTERBUS
m
co
ne
5.
When working on the Inline terminal, always
disconnect the supply voltage.
The Inline terminal must only be installed, started up,
and maintained by qualified specialist personnel.
Install the Inline terminals in a control cabinet or metal
housing. The minimum requirement for both items is
IP54 protection according to EN 60529.
The Inline terminal must not be subject to mechanical
strain and thermal loads, which exceed the limits
specified in the product documentation.
The Inline terminal must not be repaired by the user.
Repairs may only be carried out by the manufacturer.
The Inline terminal is to be replaced by an approved
terminal of the same type.
Only category 3G equipment may be connected to
Inline terminals in zone 2.
Observe all applicable standards and national safety
and accident prevention regulations for installing and
operating equipment.
s.
4.
po
IBx IL xx xx x
Order-No.: xxxxxxx
Module-ID: xx HW/FW XX/-
om
II 3G Ex nAC IIC T4 X
Potential routing 4 A maximum
for use in Ex areas
1.
3.
Before using an Inline terminal in a zone 2
potentially explosive area, first check that the
terminal has been approved for installation in
this area.
Check the labeling on the Inline terminal and
the packaging (see Figure 3).
Before startup, ensure that the following
points and instructions are observed.
2.
WARNING: Explosion hazard
Only Inline terminals that are approved for
use in potentially explosive areas may be
snapped next to this Inline terminal.
For a list of terminals approved for zone 2
potentially explosive areas, please refer to the
AH EN IL EX ZONE 2 application note.
WARNING: Explosion hazard
nt
This Inline terminal conforms to the requirements of
protection type "n" and can be installed in a zone 2
potentially explosive area. This Inline terminal is a category
3G item of electrical equipment.
6.
7.
Restrictions
WARNING: Explosion hazard
When using terminals in potentially explosive
areas, observe the technical data and limit
values specified in the corresponding
documentation (user manual, data sheet,
package slip).
WARNING: Explosion hazard;
Restrictions regarding the Inline system
The maximum permissible current through
the potential jumpers UM and US (total current)
is limited to 4 A when using this Inline terminal
in potentially explosive areas.
5553_en_04
PHOENIX CONTACT
6
IB IL 24 DI 16 ...
Internal Basic Circuit Diagram
L o c a l b u s
O P C
U
L
8
2
2
2
2
2
2
8
2
8
8
2
2
2
2
2
2
2
2
)
S
M
)
Figure 4
Internal wiring of the terminal points
Key:
Protocol chip
(bus logic including voltage conditioning)
LED
in
ec
OPC
5 5 5 3 C 0 0 4
om
po
ne
+ 2 4 V (U
nt
+ 2 4 V (U
s.
co
m
2
on
l
Optocoupler
Digital input
Electrically isolated area
Other symbols used are explained in the
IL SYS INST UM E user manual or in the Inline
system manual for your bus system.
5553_en_04
PHOENIX CONTACT
7
IB IL 24 DI 16 ...
Connection Notes and Connection
Example
Programming Data/Configuration Data
Local Bus (INTERBUS)
When connecting the sensors observe the
assignment of the terminal points to the
process data (see page 9).
1
BEhex (190dec)
Length code
01hex
Process data channel
16 bits
Input address area
1 word
Output address area
0 words
Parameter channel (PCP)
0 words
Register length (bus)
1 word
4
3
2
ID code
D
2
1
1
2
3
4
1
2
3
2
3
4
For the programming data/configuration data
of other bus systems, please refer to the
corresponding electronic device data sheet
(e.g., GSD, EDS).
s.
1
co
Other Bus Systems
3
4
4
A
B
33
33
3
44
B
4
5
55
55
55
5
6
66
66
66
6
+24 V
44
IN15
IN16
44
in
ec
4
IN14
33
A
IN16
3
om
2
IN11
IN12
22
IN7
IN8
22
IN3
IN4
22
po
1
+24 V
11
2
ne
1
IN13
IN14
11
2
IN9
IN10
IN5
IN6
1
on
l
+24 V
IN1
IN3
+24 V
Figure 5
11
2
2
A
A
1
IN1
IN2
1
2
nt
DI16
1
m
Please note that the terminal must be provided
with supply voltage US, as it is used internally
as the auxiliary supply.
5553D005
Typical connection of sensors
3-wire termination
2-wire termination
The numbers above the module illustration indicate the
connector slots.
5553_en_04
PHOENIX CONTACT
8
IB IL 24 DI 16 ...
Process Data
For the assignment of the illustrated (byte.bit) view to your INTERBUS control or computer system, please refer
to the DB GB IBS SYS ADDRESS data sheet.
For the assignment of the illustrated (byte.bit) view to control systems of other bus systems, please refer to
the AH IB IL 24 DI/DO ADDRESS document.
Assignment of the Terminal Points to the IN Process Data
Word 0
Bit
13
7
6
5
12
11
10
9
2
1
Byte 0
Byte
Bit
3
4
8
7
0
7
6
5
6
5
3
4
3
2
1
0
2
1
0
Byte 1
4
3
2
1
nt
Slot
4
Terminal point
(signal)
8.4 7.4 8.1 7.1 6.4 5.4 6.1 5.1 4.4 3.4 4.1 3.1 2.4 1.4 2.1 1.1
Terminal point (+24 V)
8.5 7.5 8.2 7.2 6.5 5.5 6.2 5.2 4.5 3.5 4.2 3.2 2.5 1.5 2.2 1.2
Terminal point (GND)
8.6 7.6 8.3 7.3 6.6 5.6 6.3 5.3 4.6 3.6 4.3 3.3 2.6 1.6 2.3 1.3
Status indication Slot
4
4
3
2
1
4
3
3
2
2
1
4
3
1
2
1
4
3
2
1
om
LED
po
Module
14
s.
(Byte.bit) view
15
co
Word
ne
(Word.bit) view
m
The following table applies to the IB IL 24 DI 16-PAC and IB IL 24 DI 16-2MBD-PAC with the original
connector set and when using the IB IL DI/DO 16-PLSET or IB IL DI 16-PLSET/ICP connector sets (see also
Figure 2 on page 5, detail B).
(Word.bit) view
Word
Bit
(Byte.bit) view
Byte
Module
on
l
Bit
in
ec
The following table applies to the IB IL 24 DI 16-PAC/SN and IB IL 24 DI 16-2MBD-PAC/SN with the original
connector set and when using the B IL SCN-12 or IB IL SCN-12-ICP connectors (see also Figure 2 on page 5,
detail A).
Word 0
15
14
13
12
11
10
9
8
7
6
5
Byte 0
7
6
Slot
5
4
3
4
3
2
1
0
2
1
0
Byte 1
2
4
1
0
7
6
3
5
4
3
2
1
Terminal point
(signal)
2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1
Terminal point (+24 V)
2.5 1.5 2.2 1.2 2.5 1.5 2.2 1.2 2.5 1.5 2.2 1.2 2.5 1.5 2.2 1.2
Terminal point (GND)
2.6 1.6 2.3 1.3 2.6 1.6 2.3 1.3 2.6 1.6 2.3 1.3 2.6 1.6 2.3 1.3
Status indication Slot
LED
4
4
3
3
2
1
4
3
2
2
1
4
3
1
2
1
4
3
2
1
© PHOENIX CONTACT 09/2007
5553_en_04
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
Phone: +49 - 52 35 - 30 0 • Fax: +49 - 52 35 - 34 18 08
www.phoenixcontact.com
9