IBS IL 24 BK RB-T-2MBD
INTERBUS Inline Terminal
for Connecting a Remote Bus Branch
Data Sheet 6766A
6 0 3 6 B 0 0 1
01/2003
This data sheet is only valid in
association with the "Configuring and
Installing the INTERBUS Inline
Product Range" User Manual
IB IL SYS PRO UM E.
Function
This terminal can be used to create a remote bus
branch from an Inline station. It can also be used
to integrate remote devices (e.g., display fields,
keypads, motor starters with IP 65 protection or
sensor/actuator boxes) into INTERBUS via an
Inline station.
Features
5 0 3 6 B 0 0 3
–
Connections for a remote bus branch using
copper technology
–
Supply of the remote bus branch terminal via
the bus terminal or a pre-connected power
terminal (not a bus device)
Please note the "Configuration Notes"
on page 4 to avoid configuration
errors.
6766A
Figure 1
The IBS IL 24 RB-T-2MBD terminal
with connector
Please note that the connector is not
supplied as standard with the
terminal. Refer to the Ordering Data
on page 10 to order the appropriate
connector for your application.
1
IBS IL 24 RB-T-2MBD
Local Diagnostic Indicators
D
R C
R D
L D
R B -T
Des.
D
Color Meaning
Green Bus diagnostics
RC
Green Remote bus cable check
RD
Yellow Remote bus branch switched
off
LD
Yellow Local bus switched off
LD
Red
Isolated disconnection of local
bus after error
Function Identification
Gray
1
2
1 .1
1
1
2 .1
1 .2
2
2
2 .2
1 .3
3
3
2 .3
1 .4
4
4
2 .4
Terminal Assignment
Terminal Assignment
Point
6 0 3 6 B 0 0 2
Figure 2
IBS IL 24 RB-T-2MBD
with appropriate connector
1.1
2.1
1.2
2.2
1.3
2.3
1.4, 2.4
2
Remark/
Wire Color in
the INTERBUS
Standard
Cable
Receive
Green
DO
DO
Receive
Yellow
Send
Pink
DI
DI
Send
Gray
GND Reference Brown
potential
Not used
Shield
Shield potential
is directly
connected to
functional earth
ground (FE) of
the voltage
jumper.
6766A
IBS IL 24 RB-T-2MBD
Internal Circuit Diagram
Key:
IN T E R B U S
U
U
U
O P C
OPC
L +
A N A
L -
INTERBUS protocol chip (bus logic
including voltage conditioning)
LED
Optocoupler
2 4 V
5 V
1
5 V
5 V
R S -4 2 2
In te rfa c e
/
R S -4 2 2
In te rfa c e
/
R S -4 2 2
In te rfa c e
Interface component
Electrically isolated area
/
Other symbols are explained in the
IB IL SYS PRO UM E User Manual.
+ 2 4 V (U S )
+ 2 4 V (U M )
Power supply unit with electrical
isolation
Ground; electrically isolated from
ground of the voltage jumper (GND)
1
6 0 3 6 B 0 0 5
Figure 3
6766A
Internal wiring of the terminal points
3
IBS IL 24 RB-T-2MBD
Connection Example
IB S IL 2 4 B K -T /U
B A
R D
R C
L D
Configuration Notes
IB S IL 2 4 R B -T
D
R C
U S
U L
The terminal for connecting a remote bus branch
must be positioned directly after a bus terminal,
a control terminal, or a terminal with remote bus
branch. Directly means that there must be no
bus device between the bus terminal/control
terminal and the terminal with remote bus
branch.
R D
U M
Only one remote bus branch terminal may be
used within an Inline station with an
IBS IL 24 BK-T.
L D
B K -T /U
1
R B -T
2
1
2
1
2
1
2
1
2
1
1 1
1 1
1 1
1 1
1
2
2 2
2 2
2 2
2 2
2
3
3 3
3 3
3 3
3 3
3
4
4 4
4 4
4 4
4 4
4
Up to 15 terminals with remote bus branch may
be used after other bus terminals or after the
control terminal if no restrictions are made in the
according terminal-specific data sheets.
Programming Data
IN T E R B U S
IN
IN T E R B U S
O U T 1
Figure 4
IN T E R B U S
O U T 2
04hex (04dec)
Length code
00hex
Process data channel
0 bytes
Input address area
0 bytes
Output address area
0 bytes
Parameter channel
(PCP)
0 bytes
Register length (bus)
0 bytes
6 0 3 6 B 0 0 4
Example of connecting the
INTERBUS cables to the bus
terminal and to the remote bus
branch terminal
INTERBUS IN
Incoming Remote Bus
INTERBUS OUT 1
Outgoing Remote Bus
INTERBUS OUT 2
Remote bus branch
4
ID code
6766A
IBS IL 24 RB-T-2MBD
Technical Data
General Data
Housing dimensions (width x height x depth)
12.2 mm x 120 mm x 71.5 mm
(0.480 in. x 4.724 in. x 2.815 in.)
Weight
46 g (without connectors)
Permissible temperature (operation)
-25°C to +55°C (-13°F to +131°F)
Permissible temperature (storage/transport)
-25°C to +85°C (-13°F to +185°F)
Permissible humidity (operation)
75% on average, 85% occasionally
In the range from -25°C to +55°C (-13°F to +131°F) appropriate measures against
increased humidity (> 85%) must be taken.
Permissible humidity (storage/transport)
75% on average, 85% occasionally
For a short period, slight condensation may appear on the housing if, for example, the
terminal is brought into a closed room from a vehicle.
Permissible air pressure (operation)
80 kPa to 106 kPa (up to 2000 m [6562 ft.] above
sea level)
Permissible air pressure (storage/transport)
70 kPa to 106 kPa (up to 3000 m [9843 ft.] above
sea level)
Degree of protection
IP 20 according to IEC 60529
Class of protection
Class 3 according to VDE 0106, IEC 60536
Interfaces (INTERBUS)
Remote bus
Incoming remote bus
Through data routing
Outgoing remote bus
Through data routing
Remote bus branch
Copper cable (RS-422), connected via Inline
shield connector; electrically isolated supply,
shielding directly connected to functional earth
ground
Recommended cable lengths
See INTERBUS system data
6766A
5
IBS IL 24 RB-T-2MBD
Interfaces (INTERBUS) (Continued)
Local Bus
Connection
Through data routing
Level
5 V CMOS signal level
Number of Inline terminals that can be connected
Limitation through software
63, maximum
Limitation through power supply unit
Maximum logic current consumption of the
connected local bus terminals: Imax ≤ 2 A DC
Observe the current consumption of the terminals
Observe the logic current consumption of each device when configuring an Inline station.
This information is given in every terminal-specific data sheet. The current consumption
can differ depending on the individual terminal. The permissible number of devices that
can be connected depends on the specific station structure.
The remote bus branch devices do not count as Inline station devices.
Power Consumption
Communications voltage UL
–
Current consumption from UL
–
Power consumption from UL
–
Analog supply voltage UANA
24 V DC (nominal value)
Nominal current consumption at UANA
0.029 A (nominal value)
Power consumption from UANA
0.696 W, maximum
Supply of the Module Electronics Through the Bus Terminal (UANA)
Connection method
6
Through potential routing
6766A
IBS IL 24 RB-T-2MBD
Power Dissipation
Formula to Calculate the Power Dissipation of the Electronics
PEL = UANA x ITOT
Where
PEL
UANA
ITOT
Total power dissipation of the terminal
Analog voltage
Total current consumption in the remote bus branch terminal at UANA
Example:
PEL = 24 V x 29 mA
PEL = 696 mW
Power Dissipation of the Housing
PHOU = 0.7 W in the total permissible ambient temperature range
Where
PHOU
Permissible power dissipation of the housing
Derating
No derating
Error Messages to the Higher-Level Control or Computer System
None
Safety Devices
None
6766A
7
IBS IL 24 RB-T-2MBD
Electrical Isolation/Isolation of the Voltage Areas
Common Potentials
The 7.5 V communications power, 24 V analog supply, 24 V bus terminal supply and the 5 V
communications power of the remote bus branch terminal share a common potential.
Separate Potentials
The communications power ground is jumpered with the ground of the 7.5 V communications power
for the bus terminal power supply unit.
The interface supply for the remote bus branch is electrically isolated from all other potentials.
The I/O supply is always electrically isolated from the interface supplies.
Electrical Isolation/Isolation of the Voltage Areas With a Combination of the IBS IL 24 BK-T
Bus Terminal and the IBS IL 24 RB-T-2MBD Remote Bus Branch Terminal
Test Distance
Test Voltage
5 V supply of incoming remote bus electrically isolated from
–
5 V supply of outgoing remote bus
–
5 V supply of remote bus branch
–
7.5 V communications power, 24 V analog supply, 24 V bus terminal
supply, 5 V communications power of remote bus branch terminal
–
24 V main supply, 24 V segment supply
–
Functional earth ground
500 V AC,
50 Hz,
1 min
5 V supply of outgoing remote bus electrically isolated from
–
5 V supply of incoming remote bus
–
5 V supply of remote bus branch
–
7.5 V communications power, 24 V analog supply, 24 V bus terminal
supply, 5 V communications power of remote bus branch terminal
–
24 V main supply, 24 V segment supply
–
Functional earth ground
8
500 V AC,
50 Hz,
1 min
6766A
IBS IL 24 RB-T-2MBD
Electrical Isolation/Isolation of the Voltage Areas With a Combination of the IBS IL 24 BK-T
Bus Terminal and the IBS IL 24 RB-T-2MBD Remote Bus Branch Terminal
7.5 V communications power, 24 V analog supply, 24 V bus terminal
supply, 5 V communications power of remote bus branch terminal
electrically isolated from
–
5 V supply of incoming remote bus
–
5 V supply of outgoing remote bus
–
5 V supply of remote bus branch
–
24 V main supply, 24 V segment supply
–
Functional earth ground
500 V AC,
50 Hz,
1 min
24 V main supply, 24 V segment supply electrically isolated from
–
5 V supply of incoming remote bus
–
5 V supply of outgoing remote bus
–
5 V supply of remote bus branch
–
7.5 V communications power, 24 V analog supply, 24 V bus terminal
supply, 5 V communications power of remote bus branch terminal
–
Functional earth ground
500 V AC,
50 Hz,
1 min
5 V supply of remote bus electrically isolated from
–
5 V supply of incoming remote bus
–
5 V supply of outgoing remote bus
–
7.5 V communications power, 24 V analog supply, 24 V bus terminal
supply, 5 V communications power of remote bus branch terminal
–
24 V main supply, 24 V segment supply
–
Functional earth ground
6766A
500 V AC,
50 Hz,
1 min
9
IBS IL 24 RB-T-2MBD
Description
Order Designation
Order No.
INTERBUS Inline terminal for connecting a
remote bus branch
IBS IL 24 RB-T-2MBD
28 55 12 7
Shield connector;
pack of 5
IB IL SCN-6 SHIELD
27 26 35 3
"Configuring and Installing the INTERBUS
Inline Product Range" User Manual
IB IL SYS PRO UM E
27 43 04 8
© Phoenix Contact 01/2003 Technical modifications reserved TNR 90 12 64 1
Ordering Data
Phoenix Contact GmbH & Co. KG
Flachsmarktstr. 8
32825 Blomberg
Germany
+ 49 - (0) 52 35 - 3-00
+ 49 - (0) 52 35 - 3-4 12 00
www.phoenixcontact.com
Worldwide Locations:
www.phoenixcontact.com/salesnetwork
10