https://www.phoenixcontact.com/us/products/2856074
Surge protection plug - PT 2X1-12DC-ST - 2856074
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Surge protection plug for the base element, coarse and fine protection for two signal wires with common
reference potential, common mode voltage coarse protection to ground. Design: 12 V DC
Why buy this product
Plugs can be checked with CHECKMASTER
Installed in conjunction with the PT 2x1...-BE base element
Maximum ease of maintenance thanks to the two-piece design
Base element remains an integral part of the installation
Consistent plug-in signal circuit protection
Protection for two conductors with common reference potential
Impedance-neutral disconnection of plug for test and maintenance purposes
Key Commercial Data
Packing unit
1 STK
GTIN
GTIN
4017918599171
Weight per Piece (excluding packing)
20.090 g
Custom tariff number
85363010
Country of origin
Germany
Technical data
Dimensions
Height
44.8 mm
Width
17.5 mm
04/15/2018 Page 1 / 8
https://www.phoenixcontact.com/us/products/2856074
Surge protection plug - PT 2X1-12DC-ST - 2856074
Technical data
Dimensions
Depth
51.7 mm
Horizontal pitch
1 Div.
Complete module height
90 mm
Complete module width
17.7 mm
Complete module depth
65.5 mm
Ambient conditions
Ambient temperature (operation)
-40 °C ... 85 °C
Degree of protection
IP20
General
Housing material
PA 6.6
Flammability rating according to UL 94
V-0
Color
black
Standards for cearances and creepage distances
VDE 0110-1
IEC 60664-1
Mounting type
on base element
Type
Male
Direction of action
Line-Line & Line-Signal Ground/Shield & optional Signal Ground/ShieldEarth Ground
Arrester can be tested with CHECKMASTER from software version:
From SW rev. 1.00
Protective circuit
IEC test classification
C1
C2
C3
D1
VDE requirement class
C1
C2
C3
D1
Nominal voltage UN
12 V DC
Maximum continuous voltage UC
13 V DC
9 V AC
Rated current
300 mA (45°C)
Operating effective current IC at UC
≤ 5 µA
Residual current IPE
≤ 1 µA (with PT 2X1+F-BE)
≤ 10 µA (Directly grounded)
Nominal discharge current In (8/20) µs (core-earth)
10 kA
04/15/2018 Page 2 / 8
https://www.phoenixcontact.com/us/products/2856074
Surge protection plug - PT 2X1-12DC-ST - 2856074
Technical data
Protective circuit
Pulse discharge current Iimp (10/350) µs
2.5 kA (per path)
Total discharge current Itotal (8/20) µs
20 kA
Max. discharge current Imax (8/20) µs maximum (Core-Earth)
10 kA
Nominal pulse current Ian (10/1000) µs (Core-Earth)
67 A
Output voltage limitation at 1 kV/µs (core-earth) spike
≤ 23 V
≤ 600 V (with PT 2X1+F-BE)
Output voltage limitation at 1 kV/µs (core-earth) static
≤ 18 V
Residual voltage at In (conductor-ground)
≤ 18 V
Residual voltage with Ian (10/1000)µs (conductor-ground)
≤ 23 V
Voltage protection level Up (core-ground)
≤ 65 V (C2 - 10 kV / 5 kA)
Response time tA (core-earth)
≤ 1 ns
Input attenuation aE, asym.
0.5 dB (≤ 600 kHz)
Cut-off frequency fg (3 dB), asym. (PE) in 50 Ohm system
typ. 3 MHz
Capacity (core-earth)
1.5 nF
Resistance in series
4.7 Ω (1-2/5-6/7-8/11-12)
Surge protection fault message
none
Max. required back-up fuse
315 mA (T)
Impulse durability (conductor-ground)
C2 - 10 kV/5 kA
D1 - 2.5 kA
Connection data
Screw thread
M3
Tightening torque
0.8 Nm
Stripping length
8 mm
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section solid
0.2 mm² ... 4 mm²
Conductor cross section AWG
24 ... 12
Standards and Regulations
Standards/regulations
IEC 61643-21
DIN EN 61643-21
UL 497B
Standards/specifications
IEC 61643-21 2000
Drawings
04/15/2018 Page 3 / 8
https://www.phoenixcontact.com/us/products/2856074
Surge protection plug - PT 2X1-12DC-ST - 2856074
Pictogram
Dimensional drawing
17,7
90
65,5
51,5
U
≃
The figure shows the complete module consisting of a base element and connector
Circuit diagram
7
8
11
12
OUT
IN
9
3
*
10
4
Classifications
eCl@ss
eCl@ss 4.0
27140201
eCl@ss 4.1
27130801
eCl@ss 5.0
27130801
eCl@ss 5.1
27130801
eCl@ss 6.0
27130807
eCl@ss 7.0
27130807
eCl@ss 8.0
27130807
eCl@ss 9.0
27130807
ETIM
ETIM 2.0
EC000943
ETIM 3.0
EC000943
ETIM 4.0
EC000943
ETIM 5.0
EC000943
ETIM 6.0
EC000943
UNSPSC
UNSPSC 6.01
30212010
04/15/2018 Page 4 / 8
https://www.phoenixcontact.com/us/products/2856074
Surge protection plug - PT 2X1-12DC-ST - 2856074
Classifications
UNSPSC
UNSPSC 7.0901
39121610
UNSPSC 11
39121610
UNSPSC 12.01
39121610
UNSPSC 13.2
39121620
Approvals
Approvals
Approvals
UL Listed / EAC / EAC / DNV GL
Ex Approvals
UL Listed / cUL Listed / cULus Listed
Approval details
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
Nominal current IN
0.3 A
Nominal voltage UN
12 V
FILE E 138168
EAC
EAC-Zulassung
EAC
RU CDE.A*30.B01561
http://exchange.dnv.com/tari/
TAE00001N6
DNV GL
Accessories
Accessories
Device marking
04/15/2018 Page 5 / 8
https://www.phoenixcontact.com/us/products/2856074
Surge protection plug - PT 2X1-12DC-ST - 2856074
Accessories
Zack marker strip - ZBN 18:UNBEDRUCKT - 2809128
Zack marker strip, Strip, white, unlabeled, can be labeled with: CMS-P1-PLOTTER, PLOTMARK, mounting type: snap
into tall marker groove, for terminal block width: 18 mm, lettering field size: 18 x 5 mm
Labeled terminal marker
Zack Marker strip, flat - ZBF 5,LGS:FORTL.ZAHLEN - 0808671
Zack Marker strip, flat, Strip, white, labeled, printed horizontally: consecutive numbers 1 - 10, 11 - 20, etc. up to 491 500, mounting type: snap into flat marker groove, for terminal block width: 5 mm, lettering field size: 5.15 x 5.15 mm
Zack Marker strip, flat - ZBF 5,LGS:GERADE ZAHLEN - 0810821
Zack Marker strip, flat, Strip, white, labeled, printed horizontally: consecutive numbers 2 - 20, 22 - 40, etc. up to 82 - 100,
mounting type: snap into flat marker groove, for terminal block width: 5 mm, lettering field size: 5.15 x 5.15 mm
Zack Marker strip, flat - ZBF 5,LGS:UNGERADE ZAHLEN - 0810863
Zack Marker strip, flat, Strip, white, labeled, printed horizontally: Odd numbers 1 - 19, 21 - 39, etc. up to 81 - 99,
mounting type: snap into flat marker groove, for terminal block width: 5 mm, lettering field size: 5.15 x 5.15 mm
Zack Marker strip, flat - ZBF 5,QR:FORTL.ZAHLEN - 0808697
Zack Marker strip, flat, Strip, white, labeled, Printed vertically: consecutive numbers 1 - 10, 11 - 20, etc. up to 91 - 100,
mounting type: snap into flat marker groove, for terminal block width: 5 mm, lettering field size: 5.15 x 5.15 mm
04/15/2018 Page 6 / 8
https://www.phoenixcontact.com/us/products/2856074
Surge protection plug - PT 2X1-12DC-ST - 2856074
Accessories
Marker pen
Marker pen - X-PEN 0,35 - 0811228
Marker pen without ink cartridge, for manual labeling of markers, labeling extremely wipe-proof, line thickness 0.35 mm
Terminal marking
Zack Marker strip, flat - ZBF 5:UNBEDRUCKT - 0808642
Zack Marker strip, flat, Strip, white, unlabeled, can be labeled with: CMS-P1-PLOTTER, PLOTMARK, mounting type:
snap into flat marker groove, for terminal block width: 5 mm, lettering field size: 5.1 x 5.2 mm
Zack Marker strip, flat - ZBF 5/WH-100:UNBEDRUCKT - 0808668
Zack Marker strip, flat, Strip, white, unlabeled, can be labeled with: CMS-P1-PLOTTER, PLOTMARK, mounting type:
snap into flat marker groove, for terminal block width: 5 mm, lettering field size: 5.15 x 5.15 mm
Necessary add-on products
Surge protection base element - PT 2X1-BE - 2856139
Base element for protective plug PT with protective circuit for 2 conductors of signal circuits grounded on one side.
Mounting on NS 35/7.5 und NS 35/15, housing width: 17.5 mm.
04/15/2018 Page 7 / 8
https://www.phoenixcontact.com/us/products/2856074
Surge protection plug - PT 2X1-12DC-ST - 2856074
Accessories
Surge protection base element - PT 2X1+F-BE - 2856142
Base element for protective plug PT with protective circuit for 2 conductors of signal circuits grounded on one side.
Integrated gas arrester as coarse protection between GND and PE. Mounting on NS 35/7.5 und NS 35/15, housing width:
17.5 mm.
Additional products
Shield connection - SSA 3-6 - 2839295
Shield fast connection for 3 ... 6 mm cable diameter. Potential connecting cable: 200 mm, 1 mm², color: black
Shield connection - SSA 5-10 - 2839512
Shield fast connection for 5 ... 10 mm cable diameter. Potential connecting cable: 200 mm, 1 mm², color: black
Phoenix Contact 2018 © - all rights reserved
http://www.phoenixcontact.com
04/15/2018 Page 8 / 8