https://www.phoenixcontact.com/us/products/2859482
Type 2 surge arrester - VAL-CP-2C-175 - 2859482
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Plug-in surge arrester for 2-phase power supply networks with N and PE in a common conductor (3-conductor
system: L1, L2, PEN), with remote indication contact.
Product Features
■
■
■
■
■
■
■
■
■
With or without floating remote indication contact
Plugs can be checked with CHECKMASTER
High continuous voltage of 175 V AC for 120/208 V AC networks with high voltage fluctuations
Mechanical coding of all slots
Optical, mechanical status indication for the individual arresters
Disconnect device on each individual plug
Type 2 consistent plug-in surge arresters
Modular arrester blocks with ultra-narrow design
Use of varistors that are free of leakage current
Key Commercial Data
Packing unit
1 pc
Weight per Piece (excluding packing)
210.7 g
Custom tariff number
85369010
Country of origin
Germany
Technical data
Dimensions
Height
98 mm
Width
25.3 mm
Depth
71.5 mm
04/19/2016 Page 1 / 6
https://www.phoenixcontact.com/us/products/2859482
Type 2 surge arrester - VAL-CP-2C-175 - 2859482
Technical data
Dimensions
Horizontal pitch
1.4 Div.
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-40 °C ... 80 °C
Ambient temperature (storage/transport)
-40 °C ... 80 °C
Altitude
≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)
5 % ... 95 %
Shock (operation)
30g (half sinus / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)
5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
General
Standards/specifications
IEC 61643-11 2011
EN 61643-11 2012
IEC test classification
II
T2
EN type
T2
IEC power supply system
TN-C
Number of ports
One
SPD design
Voltage-limiting type
Mode of protection
L-PEN
Mounting type
DIN rail: 35 mm
Color
gray/blue
black
Housing material
PBT-FR
Degree of pollution
2
Flammability rating according to UL 94
V-0
Type
DIN rail module, two-section, divisible
Number of positions
2
Surge protection fault message
Optical, remote indicator contact
Protective circuit
Nominal voltage UN
120/208 V AC (TN-C)
Nominal frequency fN
50 Hz (60 Hz)
Maximum continuous operating voltage UC (L-PEN)
175 V AC
Rated load current IL
40 A (Biconnect M4 fork-type cable lug 6 mm²)
63 A (TWIN ferrule 2 x 10 mm²)
Nominal discharge current In (8/20) µs (L-PEN)
20 kA
Maximum discharge current Imax (8/20) µs (L-PEN)
40 kA
04/19/2016 Page 2 / 6
https://www.phoenixcontact.com/us/products/2859482
Type 2 surge arrester - VAL-CP-2C-175 - 2859482
Technical data
Protective circuit
Short-circuit current rating ISCCR
25 kA
Voltage protection level Up (L-PEN)
≤ 0.85 kV
Residual voltage Ures (L-PEN)
≤ 0.85 kV (at In)
≤ 0.75 kV (at 10 kA)
≤ 0.65 kV (at 5 kA)
≤ 0.63 kV (at 4 kA)
≤ 0.57 kV (at 2 kA)
TOV behavior at UT (L-PEN)
240 V AC (5 s / withstand mode)
240 V AC (120 min / safe failure mode)
Response time tA (L-PEN)
≤ 25 ns
Max. backup fuse with branch wiring
315 A (gG)
Max. backup fuse with V-type through wiring
40 A (gG / Biconnect M4 fork-type cable lug, 6 mm²)
63 A (gG / TWIN ferrule 2x 10mm²)
Indicator/remote signaling
Connection name
Remote fault indicator contact
Switching function
PDT contact
Operating voltage
5 V AC ... 250 V AC
125 V DC (200 mA DC)
Operating current
5 mA AC ... 1 A AC
1 A DC (30 V DC)
Connection method
Pluggable screw connection
Screw thread
M2
Tightening torque
0.25 Nm
Stripping length
7 mm
Conductor cross section flexible
0.14 mm² ... 1.5 mm²
Conductor cross section solid
0.14 mm² ... 1.5 mm²
Conductor cross section AWG
28 ... 16
Connection data
Connection method
Screw connection
Conductor cross section flexible
2.5 mm² ... 16 mm²
Conductor cross section solid
2.5 mm² ... 25 mm²
Conductor cross section AWG
12 ... 4
Screw thread
M5
Tightening torque
4.5 Nm
Stripping length
16 mm
UL specifications
04/19/2016 Page 3 / 6
https://www.phoenixcontact.com/us/products/2859482
Type 2 surge arrester - VAL-CP-2C-175 - 2859482
Technical data
UL specifications
SPD Type
4CA
Maximum continuous operating voltage MCOV (L-L)
350 V AC
Maximum continuous operating voltage MCOV (L-N)
175 V AC
Nom. voltage
120/240 V AC
Mode of protection
L-L
L-N
Power distribution system
1S
Nominal frequency
50/60 Hz
Measured limiting voltage MLV (L-L)
2010 V
Measured limiting voltage MLV (L-N)
1510 V
Nominal discharge current In (L-L)
20 kA
Nominal discharge current In (L-N)
20 kA
Classifications
eCl@ss
eCl@ss 4.0
27140201
eCl@ss 4.1
27130801
eCl@ss 5.0
27130801
eCl@ss 5.1
27130801
eCl@ss 6.0
27130805
eCl@ss 7.0
27130805
eCl@ss 8.0
27130805
eCl@ss 9.0
27130805
ETIM
ETIM 2.0
EC000941
ETIM 3.0
EC000941
ETIM 4.0
EC000941
ETIM 5.0
EC000941
UNSPSC
UNSPSC 6.01
30212010
UNSPSC 7.0901
39121610
UNSPSC 11
39121610
UNSPSC 12.01
39121610
UNSPSC 13.2
39121620
04/19/2016 Page 4 / 6
https://www.phoenixcontact.com/us/products/2859482
Type 2 surge arrester - VAL-CP-2C-175 - 2859482
Approvals
Approvals
Approvals
UL Recognized / KEMA-KEUR / cUL Recognized / IECEE CB Scheme / CCA / EAC / cULus Recognized
Ex Approvals
Approvals submitted
Approval details
UL Recognized
KEMA-KEUR
cUL Recognized
IECEE CB Scheme
CCA
EAC
cULus Recognized
Drawings
04/19/2016 Page 5 / 6
https://www.phoenixcontact.com/us/products/2859482
Type 2 surge arrester - VAL-CP-2C-175 - 2859482
Dimensional drawing
Circuit diagram
PEN
98
22,5
11
14
FM
64
51,5
71,5
45
12
L1
L2
Phoenix Contact 2016 © - all rights reserved
http://www.phoenixcontact.com
04/19/2016 Page 6 / 6