Extract from the online
catalog
VAL-CP-3C-350
Order No.: 2859547
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2859547
Pluggable type 2 arrester (surge arrester) for 3-phase current supply
networks with N and PE in a common conductor (4-conductor system:
L1, L2, L3, PEN), with remote indication contact. Overall width: 36 mm.
Product notes
WEEE/RoHS-compliant since:
05/05/2006
Commercial data
GTIN (EAN)
4
017918
960827
sales group
J020
Pack
1 pcs.
Customs tariff
85363030
Catalog page information
Page 32 (TT-2011)
http://
www.download.phoenixcontact.com
Please note that the data given
here has been taken from the
online catalog. For comprehensive
information and data, please refer
to the user documentation. The
General Terms and Conditions of
Use apply to Internet downloads.
Technical data
Standards
Housing material
PBT
Inflammability class acc. to UL 94
V0
Color
gray
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 1 / 6
Jul 26, 2011
VAL-CP-3C-350 Order No.: 2859547
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2859547
Standards for air and creepage distances
DIN VDE 0110-1
IEC 60664-1: 1992-10
IEC 61643-1
Surge voltage category
III
Pollution degree
2
Degree of protection
IP20
Mounting type
DIN rail: 35 mm
Design
DIN rail module, two-section, divisible
Number of positions
3
Ambient temperature (operation)
-40 °C ... 80 °C
Message: Surge protection fault
Optical, remote indicator contact
Direction of action
3L-N/PE
Width
37.25 mm
Height
70.00 mm
Length
98.50 mm
Protective circuit
IEC category
II
T2
EN type
T2
Nominal voltage UN
240 V AC (230/400 V AC ... 240/415 V AC)
415 V AC (L-L)
Arrester rated voltage UC (L-PEN)
350 V AC
UT (TOV-proof)
415 V AC (5 s)
Nominal frequency fN
50 Hz
60 Hz
Nominal load current IL
40 A (40 A ... 63 A)
2
63 A (10 mm )
Ground conductor current IPE
≤ 250 µA (ground conductor current IPE)
Standby power consumption PC
≤ 3.5 mW
Power consumption without load Pc
≤ 3.5 mW
Max. discharge surge current Imax (8/20) µs
maximum (L-PEN)
120 kA (all channels)
Nominal discharge surge current In (8/20) µs (LPEN)
20 kA (per channel)
60 kA (all channels)
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 2 / 6
Jul 26, 2011
VAL-CP-3C-350 Order No.: 2859547
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2859547
Protection level UP (L-PEN)
≤ 1.4 kV
Residual voltage (L-PEN)
≤ 1.4 kV (at In)
≤ 1.2 kV (at 10 kA)
≤ 1.1 kV (at 5 kA)
≤ 1 kV (at 3 kA)
Clamping voltage SVR (L-PEN)
≤ 0.9 kV
Clamping voltage ringwave (L-PEN)
≤ 1.2 kV (category C3 20 kV/10 kA)
≤ 1.1 kV (category C2 10 kV/5 kA)
≤ 1 kV (category B3/C1 6 kV/3 kA)
Response time (L-N)
≤ 25 ns
Max. required backup fuse with branch wiring
125 A (gL/gG)
Max. required backup fuse with V-type through
wiring
40 A (gL/gG)
Short-circuit resistance IP with max. backup fuse
(effective)
25 kA
Connection, protective circuit
Connection method
Screw connection
Connection type IN
Biconnect screw terminal block
Connection type OUT
Biconnect screw terminal block
Connection method
Biconnect terminal block
Screw thread
M5
Tightening torque
4.5 Nm
Stripping length
16 mm
Conductor cross section stranded min.
2.5 mm²
Conductor cross section stranded max.
16 mm²
Conductor cross section solid min.
2.5 mm²
Conductor cross section solid max.
25 mm²
Conductor cross section AWG/kcmil min.
12
Conductor cross section AWG/kcmil max
4
Remote indicator contact
Connection name
Remote fault indicator contact
Switching function
PDT contact
Connection method
Pluggable screw connection
Screw thread
M2
Tightening torque
0.25 Nm
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 3 / 6
Jul 26, 2011
VAL-CP-3C-350 Order No.: 2859547
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2859547
Stripping length
7 mm
Conductor cross section stranded min.
0.14 mm²
Conductor cross section stranded max.
1.5 mm²
Conductor cross section solid min.
0.14 mm²
Conductor cross section solid max.
1.5 mm²
Conductor cross section AWG/kcmil min.
28
Conductor cross section AWG/kcmil max
16
Maximum operating voltage Umax. AC
250 V AC
Maximum operating voltage Umax DC
125 V DC
Max. operating current Imax
1 A AC (inductive)
1 A AC (ohmic)
30 mA DC (inductive)
200 mA DC (ohmic)
Min. permissible switching capacity
0.12 VA (12 V, 10 mA)
Standards
Standards/regulations
IEC 61643-1 1998
DIN EN 61643-11 2002
UL 1449
IEEE C62.1 / C62.34 / C62.45
Certificates / Approvals
Certification
CB, CUL, GL, GOST, KEMA, UL
Accessories
Item
Designation
Description
MPB SET VAL-CP-3S
Wiring bridge set, consisting of three flexible bridges 15 cm black,
1 bridge 27 cm blue.
Bridges
2880684
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 4 / 6
Jul 26, 2011
VAL-CP-3C-350 Order No.: 2859547
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2859547
Marking
0811228
X-PEN 0,35
Marker pen without ink cartridge, for manual labeling of markers,
labeling extremely wipe-proof, line thickness 0.35 mm
0809735
ZBF 12:UNBEDRUCKT
Zack strip, flat, unprinted, 5-section, divisible, for labeling by the
customer
0803595
ZBFM 5/WH:UNBEDRUCKT
Zack marker sheet, flat, unprinted: 120-section, 10 strips à 12
markers, sufficient for 120 terminal blocks, for all terminal blocks,
pitch 5.2 mm, labeling with M-PEN or CMS system, color: white
Diagrams/Drawings
Dimensioned drawing
Circuit diagram
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 5 / 6
Jul 26, 2011
VAL-CP-3C-350 Order No.: 2859547
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2859547
Address
PHOENIX CONTACT Inc., USA
586 Fulling Mill Road
Middletown, PA 17057,USA
Phone (800) 888-7388
Fax (717) 944-1625
http://www.phoenixcon.com
© 2011 Phoenix Contact
Technical modifications reserved;
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 6 / 6