https://www.phoenixcontact.com/us/products/2859602
Type 2 surge protection plug - VAL-CP-350-ST - 2859602
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Replacement plug for VAL-CP surge protective device with high-capacity varistor with a low leakage current.
Key Commercial Data
Packing unit
1 pc
GTIN
GTIN
4017918956509
Weight per Piece (excluding packing)
51.540 g
Custom tariff number
85363030
Country of origin
Germany
Technical data
Dimensions
Height
46.4 mm
Width
11.7 mm
Depth
56.4 mm
Horizontal pitch
0.6 Div.
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-40 °C ... 80 °C
Ambient temperature (storage/transport)
-40 °C ... 80 °C
Altitude
≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)
5 % ... 95 %
09/06/2019 Page 1 / 8
https://www.phoenixcontact.com/us/products/2859602
Type 2 surge protection plug - VAL-CP-350-ST - 2859602
Technical data
Ambient conditions
Shock (operation)
30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)
5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
General
IEC test classification
II
T2
EN type
T2
IEC power supply system
TN
TT
Mode of protection
L-N
L-PEN
Mounting type
on base element
Color
gray/blue
Housing material
PBT-FR
Degree of pollution
2
Flammability rating according to UL 94
V-0
Type
DIN rail module, two-section, divisible
Number of positions
1
Surge protection fault message
optical
Protective circuit
Nominal voltage UN
240 V AC (TN)
240 V AC (TT)
Nominal frequency fN
50 Hz (60 Hz)
Maximum continuous voltage UC
350 V AC
Nominal discharge current In (8/20) µs
20 kA
Maximum discharge current Imax (8/20) µs
40 kA
Short-circuit current rating ISCCR
25 kA
Voltage protection level Up
≤ 1.5 kV
Residual voltage Ures
≤ 1.5 kV (at In)
≤ 1.3 kV (at 10 kA)
≤ 1.2 kV (at 5 kA)
≤ 1.1 kV (at 4 kA)
≤ 1 kV (at 2 kA)
TOV behavior at UT
415 V AC (5 s / withstand mode)
440 V AC (120 min / safe failure mode)
Response time tA
≤ 25 ns
Max. backup fuse with branch wiring
315 A (gG)
09/06/2019 Page 2 / 8
https://www.phoenixcontact.com/us/products/2859602
Type 2 surge protection plug - VAL-CP-350-ST - 2859602
Technical data
Connection data
Connection method
pluggable
UL specifications
SPD Type
4CA
Maximum continuous operating voltage MCOV (L-N)
350 V AC
Nom. voltage
277 V AC
Mode of protection
L-N
Power distribution system
Single phase
Nominal frequency
50/60 Hz
Measured limiting voltage MLV (L-N)
2000 V
Nominal discharge current In (L-N)
20 kA
Environmental Product Compliance
China RoHS
Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values
Drawings
09/06/2019 Page 3 / 8
https://www.phoenixcontact.com/us/products/2859602
Type 2 surge protection plug - VAL-CP-350-ST - 2859602
Circuit diagram
09/06/2019 Page 4 / 8
https://www.phoenixcontact.com/us/products/2859602
Type 2 surge protection plug - VAL-CP-350-ST - 2859602
Dimensional drawing
Classifications
eCl@ss
eCl@ss 10.0.1
27130890
eCl@ss 4.0
27130800
eCl@ss 4.1
27130800
eCl@ss 5.0
27130800
eCl@ss 5.1
27130800
eCl@ss 6.0
27130800
eCl@ss 7.0
27130805
eCl@ss 8.0
27130890
eCl@ss 9.0
27130890
ETIM
ETIM 2.0
EC000941
ETIM 3.0
EC000941
ETIM 4.0
EC000941
ETIM 5.0
EC002496
ETIM 6.0
EC000941
ETIM 7.0
EC000941
09/06/2019 Page 5 / 8
https://www.phoenixcontact.com/us/products/2859602
Type 2 surge protection plug - VAL-CP-350-ST - 2859602
Classifications
UNSPSC
UNSPSC 6.01
30212010
UNSPSC 7.0901
39121610
UNSPSC 11
39121610
UNSPSC 12.01
39121610
UNSPSC 13.2
39121620
Approvals
Approvals
Approvals
CCA / UL Recognized / KEMA-KEUR / cUL Recognized / IECEE CB Scheme / EAC / EAC / cULus Recognized
Ex Approvals
Approval details
CCA
NTR-NL 7221
UL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 330181
KEMA-KEUR
http://www.dekra-certification.com
2161502.01
cUL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 330181
IECEE CB Scheme
http://www.iecee.org/
NL-29957
09/06/2019 Page 6 / 8
https://www.phoenixcontact.com/us/products/2859602
Type 2 surge protection plug - VAL-CP-350-ST - 2859602
Approvals
EAC
EAC-Zulassung
EAC
RU CDE.A*30.B01561
cULus Recognized
Accessories
Accessories
Device marking
Zack marker strip - ZBN 18:UNBEDRUCKT - 2809128
Zack marker strip, Strip, white, unlabeled, can be labeled with: CMS-P1-PLOTTER, PLOTMARK, mounting type: snap
into tall marker groove, for terminal block width: 18 mm, lettering field size: 18 x 5 mm
Labeled device marker
Marker for terminal blocks - ZBN 18,LGS:ERDE - 2749589
Marker for terminal blocks, Strip, white, labeled, Horizontal: Grounding symbol, mounting type: snap into tall marker
groove, for terminal block width: 18 mm, lettering field size: 18 x 5 mm
Marker for terminal blocks - ZBN 18,LGS:L1-N,ERDE - 2749576
Marker for terminal blocks, Strip, white, labeled, Horizontal: L1, L2, L3, N, GND, mounting type: snap into tall marker
groove, for terminal block width: 18 mm, lettering field size: 18 x 5 mm
09/06/2019 Page 7 / 8
https://www.phoenixcontact.com/us/products/2859602
Type 2 surge protection plug - VAL-CP-350-ST - 2859602
Accessories
Marker pen
Marker pen - B-STIFT - 1051993
Marker pen, for manual labeling of unprinted Zack strips, smear-proof and waterproof, line thickness 0.5 mm
Phoenix Contact 2019 © - all rights reserved
http://www.phoenixcontact.com
09/06/2019 Page 8 / 8
很抱歉,暂时无法提供与“2859602”相匹配的价格&库存,您可以联系我们找货
免费人工找货