https://www.phoenixcontact.com/us/produkte/2859738
Type 1/2 surge protection device - FLT-CP-1S-350 - 2859738
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in
the user's documentation. Our General Terms of Use for Downloads are valid
(http://download.phoenixcontact.com)
Pluggable lightning current and surge arrester combination, in acc. with typ 1+2 / Class I+II / B+C
arresters. Arresters coordinated following the AEC principle, for 1-phase power supply networks with
separately installed PE and N (L1, PE, N).
Why buy this product
Plugs can be checked with CHECKMASTER
High continuous voltage of 350 V AC for 230/400 V AC networks with high voltage fluctuations
With floating remote indication contact
Thermal disconnect device for each individual plug
Optical, mechanical status indication for the individual arresters
Key commercial data
Packing unit
1
Minimum order quantity
1
Catalog page
Page 29 (TT-2011)
GTIN
Custom tariff number
85363030
Country of origin
GERMANY
Technical data
Standards
Housing material
PBT
Inflammability class according to UL 94
V0
Color
gray
Standards for air and creepage distances
DIN VDE 0110-1
Standards for air and creepage distances
IEC 60664-1
Standards for air and creepage distances
IEC 61643-1
Surge voltage category
III
Pollution degree
2
Degree of protection
IP20
Mounting type
DIN rail: 35 mm
Design
DIN rail module, two-section, divisible
05.10.2012 Page 1 / 7
https://www.phoenixcontact.com/us/produkte/2859738
Type 1/2 surge protection device - FLT-CP-1S-350 - 2859738
Technical data
Standards
Number of positions
2
Ambient temperature (operation)
-40 °C ... 80 °C
Arrester can be tested with CHECKMASTER from software
version:
From SW rev. 3.00
Message: Surge protection fault
Optical, remote indicator contact
Direction of action
1L-N & N-PE
Width
71.6 mm
Height
95.8 mm
Depth
70 mm
Pitch unit
4 Div.
Protective circuit
IEC category
I + II
IEC category
T1 + T2
EN type
T1 + T2
Lightning protection class
III-IV /50 kA (TT, TN-C-S)
Nominal voltage UN
240 V AC (230 V AC ... 240 V AC)
Arrester rated voltage UC (L-N)
350 V AC
Arrester rated voltage UC (N-PE)
350 V AC
UT (TOV-proof)
≤ 415 V AC (5 s / L-N)
UT (TOV-safe)
≤ 1200 V AC (200 ms / N-PE)
Nominal frequency fN
50 Hz (60 Hz)
Nominal load current IL
125 A (≤ 55°C)
Ground conductor current IPE
≤ 5 µA
Standby power consumption PC
≤ 3.5 mW
Nominal discharge surge current In (8/20) µs (L-N)
25 kA
Nominal discharge surge current In (8/20) µs (N-PE)
100 kA
Lightning test current (10/350) µs, charge
25 As
Lightning test current (10/350) µs, specific energy
625.00 kJ/Ω
Lightning test current (10/350) µs, peak value limp
50 kA
Lightning test current (10/350) µs, charge
50 As
Lightning test current (10/350) µs, specific energy
2.50 MJ/Ω
Lightning test current (10/350) µs, peak value limp
100 kA (N-PE)
Impulse operate voltage at 6 kV (1.2/50)µs (N-PE)
≤ 1.5 kV
Protection level UP (L-N)
≤ 1.5 kV
Protection level UP (N-PE)
≤ 1.5 kV
Residual voltage (L-N)
≤ 1.3 kV (at In)
Residual voltage (L-N)
≤ 1.1 kV (at 10 kA)
Residual voltage (L-N)
≤ 1 kV (at 5 kA)
Residual voltage (L-N)
≤ 1 kV (at 3 kA)
Residual voltage (L-PE)
≤ 2.2 kV (at In)
Residual voltage (L-PE)
≤ 2 kV (at 10 kA)
Residual voltage (L-PE)
≤ 1.8 kV (at 5 kA)
Residual voltage (L-PE)
≤ 1.6 kV (at 3 kA)
05.10.2012 Page 2 / 7
https://www.phoenixcontact.com/us/produkte/2859738
Type 1/2 surge protection device - FLT-CP-1S-350 - 2859738
Technical data
Protective circuit
Residual voltage (N-PE)
≤ 1.5 kV (at In)
Residual voltage (N-PE)
≤ 1 kV (at 10 kA)
Residual voltage (N-PE)
≤ 0.9 kV (at 5 kA)
Residual voltage (N-PE)
≤ 0.8 kV (at 3 kA)
Response time (L-N)
≤ 25 ns
Response time (L-PE)
≤ 100 ns
Response time (N-PE)
≤ 100 ns
Max. required backup fuse with branch wiring
315 A (gL/gG)
Max. required backup fuse with V-type through wiring
125 A (gL/gG)
Recommended backup fuse maximum
160 A (gL/gG, 125 A with serial through wiring)
Short-circuit resistance IP with max. backup fuse (effective)
25 kA
Short-circuit current self-quenching
100 A (effective (N-PE))
Follow current quenching capacity If
100 A (350 V AC (N-PE))
Follow current quenching capacity If (L-N)
25 kA (264 V AC)
Follow current quenching capacity If (L-N)
3 kA (350 V AC)
Follow current quenching capacity If (N-PE)
100 A
Connection, protective circuit
Connection method
Screw terminal blocks
Connection type IN
Biconnect screw terminal block
Connection type OUT
Biconnect screw terminal block
Connection method
Biconnect terminal block
Screw thread
M5
Tightening torque
4.5 Nm
Stripping length
18 mm
Conductor cross section stranded min.
2.5 mm²
Conductor cross section stranded max.
25 mm²
Conductor cross section solid min.
2.5 mm²
Conductor cross section solid max.
35 mm²
Conductor cross section AWG/kcmil min.
13
Conductor cross section AWG/kcmil max
2
Remote indicator contact
Connection name
Remote fault indicator contact
Switching function
PDT contact
Connection method
Plug-in/screw connection via COMBICON
Screw thread
M2
Tightening torque
0.25 Nm
Stripping length
7 mm
Conductor cross section stranded min.
0.14 mm²
Conductor cross section stranded max.
1.5 mm²
Conductor cross section solid min.
0.14 mm²
Conductor cross section solid max.
1.5 mm²
Conductor cross section AWG/kcmil min.
28
05.10.2012 Page 3 / 7
https://www.phoenixcontact.com/us/produkte/2859738
Type 1/2 surge protection device - FLT-CP-1S-350 - 2859738
Technical data
Remote indicator contact
Conductor cross section AWG/kcmil max
16
Maximum operating voltage Umax. AC
250 V AC
Maximum operating voltage Umax DC
125 V DC
Max. operating current Imax
1 A AC (inductive)
Max. operating current Imax
1 A AC (ohmic)
Max. operating current Imax
30 mA DC (inductive)
Max. operating current Imax
200 mA DC (ohmic)
Standards
Standards/regulations
IEC 61643-1 2002
Standards/regulations
EN 61643-11 2005
Standards/regulations
UL 1449
Classifications
eclass
eCl@ss 4.0
27140201
eCl@ss 4.1
27140201
eCl@ss 5.0
27140201
eCl@ss 5.1
27140201
eCl@ss 6.0
27140201
eCl@ss 7.0
27140201
etim
ETIM 2.0
EC001457
ETIM 3.0
EC001457
ETIM 4.0
EC001457
ETIM 5.0
EC001457
unspsc
UNSPSC 6.01
30212010
UNSPSC 7.0901
39121610
UNSPSC 11
39121610
UNSPSC 12.01
39121610
UNSPSC 13.2
39121620
Approvals
Approvals
Approvals
UL Recognized / KEMA-KEUR / cUL Recognized / GOST / CCA / IECEE CB Scheme / GL / cULus Recognized
05.10.2012 Page 4 / 7
https://www.phoenixcontact.com/us/produkte/2859738
Type 1/2 surge protection device - FLT-CP-1S-350 - 2859738
Approvals
Ex Approvals
Approvals submitted
Approval details
UL Recognized
KEMA-KEUR
cUL Recognized
GOST
CCA
IECEE CB Scheme
GL
cULus Recognized
Accessories
Accessories
Marking
Zack marker strip - ZBN 18:UNBEDRUCKT - 2809128
Zack marker strip, Strip, white, Unlabeled, Can be labeled with: Plotter, Mounting type: Snap into tall marker
groove, For terminal block width: 18 mm, Lettering field: 18 x 5 mm
05.10.2012 Page 5 / 7
https://www.phoenixcontact.com/us/produkte/2859738
Type 1/2 surge protection device - FLT-CP-1S-350 - 2859738
Accessories
Zack marker strip - ZBN 18,LGS:L1-N,ERDE - 2749576
Zack marker strip, Strip, white, Labeled, Horizontal: L1, L2, L3, N, GND, Mounting type: Snap into tall
marker groove, For terminal block width: 18 mm, Lettering field: 18 x 5 mm
Zack marker strip - ZBN 18,LGS:ERDE - 2749589
Zack marker strip, Strip, white, Labeled, Horizontal: Grounding symbol, Mounting type: Snap into tall marker
groove, For terminal block width: 18 mm, Lettering field: 18 x 5 mm
Marker pen - B-STIFT - 1051993
Marker pen, for manual labeling of unprinted Zack strips, smear-proof and waterproof, line thickness 0.5 mm
Flat zack marker sheet - ZBFM 5/WH:UNBEDRUCKT - 0803595
Flat zack marker sheet, Sheet, white, Unlabeled, Can be labeled with: Plotter, Mounting type: Snap into flat
marker groove, For terminal block width: 5.2 mm, Lettering field: 5 x 4.5 mm
Type 1 surge protection connector - FLT-CP-N/PE-350-ST - 2859686
Type 1 / Class I / B arrester (lightning arrester) replacement plug for path N-PE, can be combined with
FLASHTRAB compact series of products.
05.10.2012 Page 6 / 7
https://www.phoenixcontact.com/us/produkte/2859738
Type 1/2 surge protection device - FLT-CP-1S-350 - 2859738
Accessories
Type 2 surge protection connector - VAL-CP-350-ST - 2859602
Type 2 arrester replacement plug (surge arrester) with high-capacity varistor with low leakage current.
Drawings
Dimensioned drawing
Circuit diagram
11
14
FM
64
22,5
51,5
71,5
45
12
N
95
PE
L1
© Phoenix Contact 2012 - all rights reserved
http://www.phoenixcontact.com