https://www.phoenixcontact.com/us/products/2859767
Lightning/surge arrester combination type 1+2 - FLT-CP-2S-350 - 2859767
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Pluggable lightning current and surge arrester combination, in acc. with typ 1+2 / Class I+II / B+C arresters.
Arresters coordinated following the AEC principle, for 2-phase power supply networks with separately installed
PE and N (L1, L2, PE, N).
Product Features
■
■
■
■
■
Plugs can be checked with CHECKMASTER
High continuous voltage of 350 V AC for 230/400 V AC networks with high voltage fluctuations
With floating remote indication contact
Thermal disconnect device for each individual plug
Optical, mechanical status indication for the individual arresters
Key Commercial Data
Packing unit
1 pc
Weight per Piece (excluding packing)
1185.92 g
Custom tariff number
85363030
Country of origin
Germany
Technical data
Dimensions
Height
95 mm
Width
106.8 mm
Depth
71.5 mm
Horizontal pitch
6 Div.
Ambient conditions
Degree of protection
IP20 (only when all terminal points are used)
Ambient temperature (operation)
-40 °C ... 80 °C
03/13/2016 Page 1 / 7
https://www.phoenixcontact.com/us/products/2859767
Lightning/surge arrester combination type 1+2 - FLT-CP-2S-350 - 2859767
Technical data
Ambient conditions
Ambient temperature (storage/transport)
-40 °C ... 80 °C
Altitude
≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)
5 % ... 95 %
Shock (operation)
25g (half sinus / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)
5g (5 - 500 Hz/2.5 h/X, Y, Z)
General
Standards/specifications
IEC 61643-11 2011
EN 61643-11 2012
IEC test classification
I + II
T1 + T2
EN type
T1 + T2
IEC power supply system
TN-S
TT
Number of ports
One
SPD design
Combination type
Mode of protection
L-N
L-PE
N-PE
Mounting type
DIN rail: 35 mm
Color
gray/blue
black
Housing material
PBT
Degree of pollution
2
Flammability rating according to UL 94
V-0
Type
DIN rail module, two-section, divisible
Number of positions
3
Arrester can be tested with CHECKMASTER from software version:
From SW rev. 3.00
Surge protection fault message
Optical, remote indicator contact
Protective circuit
Nominal voltage UN
240/415 V AC (TN-S)
240/415 V AC (TT)
Nominal frequency fN
50 Hz (60 Hz)
Maximum continuous operating voltage UC (L-N)
350 V AC
Maximum continuous voltage UC (N-PE)
350 V AC
Rated load current IL
125 A (< 55 °C)
Residual current IPE
≤ 0.01 mA
03/13/2016 Page 2 / 7
https://www.phoenixcontact.com/us/products/2859767
Lightning/surge arrester combination type 1+2 - FLT-CP-2S-350 - 2859767
Technical data
Protective circuit
Nominal discharge current In (8/20) µs (L-N)
25 kA
Nominal discharge current In (8/20) µs (L-PE)
25 kA
Nominal discharge current In (8/20) µs (N-PE)
100 kA
Impulse discharge current (10/350) µs (L-N), charge
12.5 As
Impulse discharge current (10/350) µs (L-N), specific energy
160 kJ/Ω
Impulse discharge current (10/350) µs (L-N), peak current value Iimp
25 kA
Impulse discharge current (10/350) µs (L-PE), charge
12.5 As
Impulse discharge current (10/350) µs (L-PE), specific energy
160 kJ/Ω
Impulse discharge current (10/350) µs (L-PE), peak current value Iimp
25 kA
Impulse discharge current (10/350) µs (N-PE), charge
50 As
Impulse discharge current (10/350) µs (N-PE), specific energy
2500 kJ/Ω
Impulse discharge current (10/350) µs (N-PE), peak current value Iimp
100 kA
Follow current interrupt rating Ifi (L-N)
25 kA (264 V AC)
3 kA (350 V AC)
Follow current interrupt rating Ifi (N-PE)
100 A (350 V AC)
Short-circuit current rating ISCCR
25 kA (264 V AC)
3 kA (350 V AC)
Voltage protection level Up (L-N)
≤ 1.5 kV
Voltage protection level Up (L-PE)
≤ 2.2 kV
Voltage protection level Up (N-PE)
≤ 1.5 kV
Residual voltage Ures (L-N)
≤ 1.5 kV (at In)
≤ 1.2 kV (at 10 kA)
≤ 1 kV (at 5 kA)
≤ 0.9 kV (at 3 kA)
Residual voltage Ures (L-PE)
≤ 2.2 kV (at In)
≤ 2 kV (at 10 kA)
≤ 1.8 kV (at 5 kA)
≤ 1.6 kV (at 3 kA)
Residual voltage Ures (N-PE)
≤ 1.5 kV (at In)
≤ 1 kV (at 10 kA)
≤ 0.9 kV (at 5 kA)
≤ 0.8 kV (at 3 kA)
Front of wave sparkover voltage at 6 kV (1.2/50) µs (L-N)
≤ 1.5 kV
Front of wave sparkover voltage at 6 kV (1.2/50) µs (L-PE)
≤ 2.2 kV
Front of wave sparkover voltage at 6 kV (1.2/50) µs (N-PE)
≤ 1.5 kV
TOV behavior at UT (L-N)
415 V AC (5 s / withstand mode)
03/13/2016 Page 3 / 7
https://www.phoenixcontact.com/us/products/2859767
Lightning/surge arrester combination type 1+2 - FLT-CP-2S-350 - 2859767
Technical data
Protective circuit
457 V AC (120 min / safe failure mode)
TOV behavior at UT (N-PE)
1200 V AC (200 ms / withstand mode)
Response time tA (L-N)
≤ 25 ns
Response time tA (N-PE)
≤ 100 ns
Max. backup fuse with branch wiring
315 A (gG)
Max. backup fuse with V-type through wiring
125 A (gG)
Indicator/remote signaling
Connection name
Remote fault indicator contact
Switching function
PDT contact
Operating voltage
12 V AC ... 250 V AC
125 V DC (200 mA DC)
Operating current
10 mA AC ... 1 A
1 A (30 V DC)
Connection method
Plug-in/screw connection via COMBICON
Screw thread
M2
Tightening torque
0.25 Nm
Stripping length
7 mm
Conductor cross section flexible min.
0.14 mm²
Conductor cross section flexible max.
1.5 mm²
Conductor cross section solid min.
0.14 mm²
Conductor cross section solid max.
1.5 mm²
Conductor cross section AWG
28 ... 16
Connection data
Connection method
Screw terminal blocks
Conductor cross section flexible min.
2.5 mm²
Conductor cross section flexible max.
25 mm²
Conductor cross section solid min.
2.5 mm²
Conductor cross section solid max.
35 mm²
Conductor cross section AWG
13 ... 2
Screw thread
M5
Tightening torque
4.5 Nm
Stripping length
18 mm
UL specifications
SPD Type
4CA
Maximum continuous operating voltage MCOV (L-L)
528 V AC
Maximum continuous operating voltage MCOV (L-N)
264 V AC
03/13/2016 Page 4 / 7
https://www.phoenixcontact.com/us/products/2859767
Lightning/surge arrester combination type 1+2 - FLT-CP-2S-350 - 2859767
Technical data
UL specifications
Maximum continuous operating voltage MCOV (L-G)
528 V AC
Maximum continuous operating voltage MCOV (N-G)
264 V AC
Nom. voltage
240/415 V AC
Mode of protection
L-L
L-N
L-G
N-G
Power distribution system
3Y
Nominal frequency
50/60 Hz
Measured limiting voltage MLV (L-L)
2470 V
Measured limiting voltage MLV (L-N)
1340 V
Measured limiting voltage MLV (L-G)
1550 V
Measured limiting voltage MLV (N-G)
1080 V
Nominal discharge current In (L-L)
20 kA
Nominal discharge current In (L-N)
20 kA
Nominal discharge current In (L-G)
20 kA
Nominal discharge current In (N-G)
20 kA
Follow current (L-N)
10 kA (264 V AC)
Follow current (N-G)
200 A (264 V AC)
Classifications
eCl@ss
eCl@ss 4.0
27140201
eCl@ss 4.1
27130801
eCl@ss 5.0
27130801
eCl@ss 5.1
27130801
eCl@ss 6.0
27130808
eCl@ss 7.0
27130808
eCl@ss 8.0
27130808
ETIM
ETIM 2.0
EC001457
ETIM 3.0
EC001457
ETIM 4.0
EC001457
ETIM 5.0
EC001457
03/13/2016 Page 5 / 7
https://www.phoenixcontact.com/us/products/2859767
Lightning/surge arrester combination type 1+2 - FLT-CP-2S-350 - 2859767
Classifications
UNSPSC
UNSPSC 6.01
30212010
UNSPSC 7.0901
39121610
UNSPSC 11
39121610
UNSPSC 12.01
39121610
UNSPSC 13.2
39121620
Approvals
Approvals
Approvals
UL Recognized / KEMA-KEUR / cUL Recognized / CCA / IECEE CB Scheme / EAC / EAC / cULus Recognized
Ex Approvals
Approvals submitted
Approval details
UL Recognized
KEMA-KEUR
cUL Recognized
CCA
03/13/2016 Page 6 / 7
https://www.phoenixcontact.com/us/products/2859767
Lightning/surge arrester combination type 1+2 - FLT-CP-2S-350 - 2859767
Approvals
IECEE CB Scheme
EAC
EAC
cULus Recognized
Drawings
Dimensional drawing
106,8
12
N
14
11 FM
64
71,5
95
Circuit diagram
PE
L1
L2
Phoenix Contact 2016 © - all rights reserved
http://www.phoenixcontact.com
03/13/2016 Page 7 / 7
很抱歉,暂时无法提供与“2859767”相匹配的价格&库存,您可以联系我们找货