IB IL 24 DO 8 ...
Inline Terminal With Eight Digital Outputs
AUTOMATIONWORX
Data Sheet
Description
–
–
–
–
–
–
–
Connections for eight digital actuators
Connection of actuators in 2, 3, and 4-wire technology
Nominal current of each output: 0.5 A
Total current of the terminal: 4 A
Short-circuit and overload protected outputs
Diagnostic and status indicators
Approved for use within a safety-related segment
circuit (not valid for IB IL 24 DO 8-PAC/SN)
on
l
in
ec
om
po
ne
The terminal is designed for use within an Inline station. It is
used to output digital signals.
nt
Features
s.
© PHOENIX CONTACT - 08/2005
co
m
4 x
This data sheet is only valid in association with the IB IL SYS PRO UM E user manual or the Inline system
manual for your bus system.
Please observe the notes on page 4 when using the terminal within a safety-related segment circuit.
Make sure you always use the latest documentation.
It can be downloaded at www.download.phoenixcontact.com.
A conversion table is available on the Internet at
www.download.phoenixcontact.com/general/7000_en_00.pdf.
This data sheet is valid for the terminals listed under "Ordering Data" on page 12.
5558_en_07
PHOENIX CONTACT GmbH & Co. KG • Flachsmarktstraße 8 • 32825 Blomberg • Germany
Phone: +49-(0) 5235-3-00 • Fax: +49-(0) 5235-3-4 12 00 • www.phoenixcontact.com
www.phoenixcontact.com/salesnetwork
1
IB IL 24 DO 8 ...
Distinguishing the Product Versions
The product versions with and without "PAC" only differ in
the scope of supply (see "Ordering Data" on page 12).
Their function and technical data are identical.
–
–
Without PAC:
With PAC:
Local Diagnostic/Status Indicators and
Terminal Point Assignment
Local Diagnostic and Status Indicators
Without accessories
Including connectors and labeling
fields
D
1
2
The product versions with and without "SN" only differ with
regard to the numbering of the terminal points on the
different connector versions (see Figure 2 on page 3). Their
function and technical data are identical.
nt
500 kbps
2 Mbps
Figure 1
Further differing technical data are particularly identified.
5 5 5 8 C 0 0 2
Local diagnostic and status indicators
Des.
Color
Meaning
D
Green
Diagnostics
1, 2
Yellow Status indicators of the outputs
Function Identification
Pink
2 Mbps: white stripe in the vicinity of the D LED
on
l
in
ec
om
po
For greater clarity, the designation IB IL 24 DO 8 is used
throughout this document.
ne
Without 2MDB:
With 2MBD:
2
8
m
PAC without SN: Connectors consecutively
numbered
With PAC/SN:
Connectors not consecutively
numbered
The terminal functions with and without "2MBD" are
identical. The essential difference between them is the
transmission speed.
–
–
1
2
co
–
1
2
s.
–
D O
1
5558_en_07
PHOENIX CONTACT
2
IB IL 24 DO 8 ...
Terminal Point Assignment for Each Connector
B
1
x
2
x
x
1 .1
1
1
2 .1
1 .1
1
1 .2
2
2
2 .2
1 .2
2
1 .3
3
3
2 .3
1 .3
1 .4
4
4
2 .4
1 .4
1
2
1
2
1
2
1
2
1 .1
2 .1
3 .1
4 .1
5 .1
6 .1
7 .1
8 .1
1 1
1 .2
2 .2
1 1
3 .2
1 .3
2 .3
3
3 .3
1 .4
4
2 .4
3 .4
2
8 .2
3
8 .3
4
8 .4
8 .2
8 .3
3 3
5 .4
4 .4
7 .3
6 .3
3 3
4 4
8 .1
2 2
5 .3
4 .3
7 .2
6 .2
2 2
3 3
1
1 1
5 .2
4 .2
2 2
x
4 4
7 .4
6 .4
4 4
8 .4
m
4 x
6 9 5 0 A 0 0 7
Terminal point numbering: individual connectors (A) and connector sets (B)
s.
Figure 2
co
A
–
–
Using the IB IL 24 DO 8-PAC/SN or IB IL 24 DO 8-2MBD-PAC/SN with the supplied connectors
Using individual connectors (IB IL SCN-8 or IB IL SCN-8-CP)
B
–
–
Using the IB IL 24 DO 8-PAC or IB IL 24 DO 8-2MBD-PAC with the original connector set
Using a connector set (IB IL DI/DO 8-PLSET or IB IL DI/DO 8-PLSET/CP)
Assignment
x.1
Signal output (OUT 1)
x.2
Segment voltage US
for 4-wire termination
om
Terminal
Point
po
ne
nt
A
in
ec
Measuring points for the supply voltage
Ground contact (GND)
for 2, 3, and 4-wire termination
x.4
FE connection
for 3 and 4-wire termination
on
l
x.3
5558_en_07
PHOENIX CONTACT
3
IB IL 24 DO 8 ...
Notes on Using the Terminals Within a Safety-Related Segment Circuit
The terminals of the following hardware version and later
(listed below) are approved for use within a safety-related
segment circuit.
1
The IB IL 24 DO 8-PAC/SN terminal is not approved for
use within a safety-related segment circuit.
IB IL 2 4 D O 8
O rd e r-N o .: 2 7 2 6 2 6 9
M o d u le - ID : X X
Hardware
Version
05
05
IB IL DO 8-2MBD
IB IL 24 DO 8-2MBD-PAC
IB IL 24 DO 8-2MBD-PAC/SN
04
04
04
0 5 /-
5 5 5 8 A 0 0 8
Figure 3
Imprinting on an Inline terminal
m
IB IL 24 DO 8
IB IL 24 DO 8-PAC
H W /S W
IN T E R B U S
co
500 kbps
27 26 26 9
28 61 28 9
2 Mbps
28 19 03 7
28 61 68 7
28 78 22 7
Order Designation
The instructions of the current data sheet of the
safety terminal that opens the safety-related
segment circuit must be followed to ensure that
the function of the safety-related segment
circuit is not affected!
s.
Order No.
Up-to-date documentation can be downloaded
at www.download.phoenixcontact.com.
on
l
in
ec
om
po
ne
nt
The hardware version is imprinted on the side
of the housing of every terminal (1 in Figure 3).
5558_en_07
PHOENIX CONTACT
4
IB IL 24 DO 8 ...
Internal Circuit Diagram
L o c a l b u s
O P C
U
L
4
2
4
2
2
4
4
2
2
2
2
M
)
Internal wiring of the terminal points
om
Figure 4
Key:
Protocol chip (bus logic including
voltage conditioning)
LED
in
ec
OPC
po
ne
+ 2 4 V (U
)
S
nt
+ 2 4 V (U
s.
co
m
2
5 5 5 8 C 0 0 3
Other symbols used are explained in the
IB IL SYS PRO UM E user manual or in the
Inline system manual for your bus system.
on
l
Optocoupler
Transistor
Digital output
Electrically isolated area
5558_en_07
PHOENIX CONTACT
5
IB IL 24 DO 8 ...
Connection Example
Programming Data/Configuration Data
INTERBUS
2
D
1
1
2
0 bytes
Output address area
1 byte
Parameter channel (PCP)
0 bytes
Register length (bus)
1 byte
For the programming data/configuration data
of other bus systems, please refer to the
corresponding electronic device data sheet
(GSD, EDS).
1
2
1
2
1
2
1 1
1 1
1
2
2 2
2 2
2 2
2
3
3 3
3 3
3 3
3
4
4 4
4 4
4 4
4
ne
nt
1 1
s.
2
om
in
ec
O U T
+ 2 4 V
O U T
8 bits
Input address area
Other Bus Systems
2
1
A
Figure 5
1
2
Process data channel
8
1
B
5 5 5 8 2 0 0 4
Typical actuator connection
4-wire termination
3-wire termination
on
l
A
B
1
2
81hex
po
D O
4
3
BDhex (189dec)
Length code
co
1
ID code
m
When connecting the actuators observe the
assignment of the terminal points to the
process data (see page 7).
The numbers above the module illustration identify the
connector slots.
5558_en_07
PHOENIX CONTACT
6
IB IL 24 DO 8 ...
Process Data
For the assignment of the illustrated (byte.bit) view to your INTERBUS control or computer system, please refer
to data sheet DB EN IBS SYS ADDRESS, Order No. 90 00 99 0.
Assignment of the Terminal Points to the OUT Process Data
Byte 0
7
Bit
4
4
3
2
3
1
2
0
1
8.1 7.1 6.1 5.1 4.1 3.1 2.1 1.1
Terminal point (+24 V)
8.2 7.2 6.2 5.2 4.2 3.2 2.2 1.2
Terminal point (GND)
8.3 7.3 6.3 5.3 4.3 3.3 2.3 1.3
Terminal point (FE)
8.4 7.4 6.4 5.4 4.4 3.4 2.4 1.4
s.
Terminal point (signal)
Slot
4
2
3
1
2
2
1
2
1
1
2
1
po
LED
nt
Status
indicator
Slot
5
ne
Assignment
6
co
(Byte.bit) view Byte
m
The following table applies to the IB IL 24 DO 8-PAC and IB IL 24 DO 8-2MBD-PAC terminals with the original
connector set and when using the IB IL DI/DO 8-PLSET and IB IL DI/DO 8-PLSET/CP connector sets (see also
Figure 2 on page 3, detail B).
om
The following table applies to the IB IL 24 DO 8-PAC/SN and IB IL 24 DO 8-2MBD-PAC/SN terminals with the
original connector set and when using the IB IL SCN-8 or IB IL SCN-8-CP connectors (see also Figure 2 on
page 3, detail A).
Bit
Status
indicator
5558_en_07
Slot
7
6
Byte 0
5
4
4
3
3
2
1
2
0
1
Terminal point (signal)
2.1 1.1 2.1 1.1 2.1 1.1 2.1 1.1
Terminal point (+24 V)
2.2 1.2 2.2 1.2 2.2 1.2 2.2 1.2
Terminal point (GND)
2.3 1.3 2.3 1.3 2.3 1.3 2.3 1.3
Terminal point (FE)
2.4 1.4 2.4 1.4 2.4 1.4 2.4 1.4
on
l
Assignment
in
ec
(Byte.bit) view Byte
Slot
LED
4
2
3
1
2
2
1
2
1
1
2
1
PHOENIX CONTACT
7
IB IL 24 DO 8 ...
Technical Data
General Data
Housing dimensions (width x height x depth)
Weight
Operating mode
Connection method for actuators
Permissible temperature (operation)
Permissible temperature (storage/transport)
Permissible humidity (operation)
48.8 mm x 120 mm x 71.5 mm
130 g (without connectors)
Process data mode with 1 byte
2, 3, and 4-wire technology
-25°C to +55°C
-25°C to +85°C
75% on average, 85% occasionally
co
m
In the range from - 25°C to + 55°C appropriate measures against increased humidity (> 85%) must be
taken.
Permissible humidity (storage/transport)
75% on average, 85% occasionally
s.
For a short period, slight condensation may appear on the outside of the housing if, for example, the
terminal is brought into a closed room from a vehicle.
ne
po
Interface
Local bus
80 kPa to 106 kPa (up to 2000 m above sea level)
70 kPa to 106 kPa (up to 3000 m above sea level)
IP20 according to IEC 60529
Class 3 according to VDE 0106, IEC 60536
nt
Permissible air pressure (operation)
Permissible air pressure (storage/transport)
Degree of protection
Class of protection
in
ec
Transmission Speed
IB IL 24 DO 8
IB IL 24 DO 8-PAC
IB IL 24 DO 8-PAC/SN
IB IL DO 8-2MBD
IB IL 24 DO 8-2MBD-PAC
IB IL 24 DO 8-2MBD-PAC/SN
om
Through data routing
500 kbps
500 kbps
500 kbps
2 Mbps
2 Mbps
2 Mbps
7.5 V DC
60 mA, maximum
0.45 W, maximum
24 V DC (nominal value)
4 A (8 x 0.5 A), maximum
Power Consumption (2 Mbps)
Communications power
Current consumption from the local bus
Power consumption from the local bus
Segment supply voltage US
Nominal current consumption at US
7.5 V DC
85 mA, maximum
0.64 W, maximum
24 V DC (nominal value)
4 A (8 x 0.5 A), maximum
on
l
Power Consumption (500 kbps)
Communications power
Current consumption from the local bus
Power consumption from the local bus
Segment supply voltage US
Nominal current consumption at US
5558_en_07
PHOENIX CONTACT
8
IB IL 24 DO 8 ...
Digital Outputs
Number
Nominal output voltage UOUT
Differential voltage for Inom
Nominal current Inom per channel
Tolerance of the nominal current
Total current
Protection
8
24 V DC
≤1V
0.5 A
+10%
4A
Short-circuit; overload
m
Supply of the Module Electronics and I/O Through Bus Terminal/Power Terminal
Connection method
Through potential routing
co
Always 4 channels are thermally coupled, i.e. an error case in one channel can affect the other channels.
Nominal load
Ohmic
Lamp
Inductive
Signal delay upon power up of
Nominal ohmic load
Nominal lamp load
s.
nt
ne
om
po
100 µs, typical
100 ms, typical (with switching frequencies up to 8 Hz;
above this frequency the lamp load responds like an ohmic
load)
100 ms (1.2 H, 50 Ω), typical
in
ec
Nominal inductive load
Signal delay upon power down of
Nominal ohmic load
Nominal lamp load
Nominal inductive load
Switching frequency with
Nominal ohmic load
48 Ω / 12 W
12 W
12 VA (1.2 H, 50 Ω)
1 ms, typical
1 ms, typical
50 ms (1.2 H, 50 Ω), typical
300 Hz, maximum
on
l
This switching frequency is limited by the selected data rate, the number of bus devices, the bus structure,
the software and the control or computer system used.
Nominal lamp load
300 Hz, maximum
This switching frequency is limited by the selected data rate, the number of bus devices, the bus structure,
the software and the control or computer system used.
Nominal inductive load
Overload response
Response time with ohmic overload (12Ω)
Restart frequency with ohmic overload
Restart frequency with lamp overload
Response with inductive overload
Response time in the event of a short circuit
Reverse voltage protection against short pulses
5558_en_07
0.5 Hz (1.2 H, 48 Ω), maximum
Auto restart
3 s, approximately
400 Hz, approximately
400 Hz, approximately
Output may be damaged
400 ms, approximately
Protected against reverse voltages
PHOENIX CONTACT
9
IB IL 24 DO 8 ...
co
m
The output follows the supply voltage without delay.
-15 V ≤ Udemag ≤ -46 V
(Udemag = demagnetization voltage)
400 mJ, maximum
Integrated 45 V Zener diode in the output chip
0.7 A, minimum
300 µA, maximum
2 V, maximum
25 mA, maximum
100 mW at 1 kΩ load resistance, typical
1.5 A for 20 ms, maximum
s.
One-time unsolicited energy
Protective circuit type
Overcurrent shutdown
Output current when switched off
Output voltage when switched off
Output current with ground connection interrupted
Switching power with ground connection interrupted
Inrush current with lamp load
Up to 2 A DC
Protective elements in the bus terminal or power terminal
No
5 ms, typical
nt
Digital Outputs (Continued)
Resistance to permanently applied reverse voltages
Resistance to polarity reversal of the supply voltage
Resistance to permanently applied surge voltage
Validity of output data after connecting the 24 V voltage
supply (power up)
Response upon power down
Limitation of the voltage induced on circuit interruption
om
po
ne
Output Characteristic Curve When Switched On (Typical)
Output Current (A)
0
0.1
0.2
0.3
0.4
0.5
Differential Output Voltage (V)
0
0.04
0.08
0.12
0.16
0.20
on
l
2 Mbps
in
ec
Power Dissipation
Formula to Calculate the Power Dissipation of the Electronics
500 kbps
8
P
P
E L
E L
= 0 .1 9 W
+ Σ (0 .1 0 W
= 0 .4 6 W
+ S
n = 1
+ IL
2
n
8
n = 1
(0 .1 0 W
+ IL
n
2
x 0 . 4 0 Ω)
x 0 .4 0 W )
Where
PEL
Total power dissipation in the terminal
n
Index of the number of set outputs n = 1 to 8
Load current of output n
ILn
Power Dissipation of the Housing PHOU
2.7 W, maximum
(within the permissible operating temperature)
Limitation of Simultaneity, Derating
Derating
5558_en_07
No limitation of simultaneity,
no derating
PHOENIX CONTACT
10
IB IL 24 DO 8 ...
Safety Equipment
Overload/short circuit in segment circuit
Surge voltage
Electronic; with two 4-channel drivers
Protective circuits of the power terminal;
Polarity reversal of the supply voltage
Protection up to 33 V DC
Protective circuits of the power terminal;
Reverse voltage
It is necessary to protect the voltage supply. The power
supply unit should be able to supply 4 times (400%) the
nominal current of the fuse.
Protection up to 2 A DC
m
Electrical Isolation/Isolation of the Voltage Areas
s.
co
To provide electrical isolation between the logic level and the I/O area, it is necessary to supply the station
bus terminal and the digital output terminal described here using the bus terminal or a power terminal from
separate power supply units. Interconnection of the power supply units in the 24 V area is not permitted.
(See also the IB IL SYS PRO UM E user manual).
om
po
ne
nt
Common Potentials
The 24 V main voltage, 24 V segment voltage, and GND have the same potential. FE is a separate potential area.
Separate Potentials in the System Consisting of Bus Terminal/Power Terminal and I/O Terminal
- Test Distance
- Test Voltage
5 V supply incoming remote bus / 7.5 V supply (bus logic)
500 V AC, 50 Hz, 1 min
5 V supply outgoing remote bus / 7.5 V supply (bus logic)
500 V AC, 50 Hz, 1 min
7.5 V supply (bus logic) / 24 V supply (I/O)
500 V AC, 50 Hz, 1 min
24 V supply (I/O) / functional earth ground
500 V AC, 50 Hz, 1 min
in
ec
Error Messages to the Higher-Level Control or Computer System
Short circuit/overload of an output
Yes
An error message is generated when an output is short circuited and switched on. In addition, the diagnostic
LED (D) flashes on the terminal at 2 Hz (medium) under these conditions.
No
on
l
Operating voltage out of range
5558_en_07
PHOENIX CONTACT
11
IB IL 24 DO 8 ...
Ordering Data
Terminals
Pcs./Pkt.
IB IL 24 DO 8
IB IL 24 DO 8-PAC
27 26 26 9
28 61 28 9
1
1
IB IL 24 DO 8-PAC/SN
28 62 94 5
1
m
Order No.
1
1
s.
IB IL 24 DO 8-2MBD-PAC/
SN
28 78 22 7
1
Order Designation
Order No.
Pcs./Pkt.
po
Description
28 19 03 7
28 61 68 7
co
IB IL DO 8-2MBD
IB IL 24 DO 8-2MBD-PAC
ne
Connectors
Order Designation
nt
Description
Transmission Speed 500 kbps
Terminal with eight digital outputs; without accessories
Terminal with eight digital outputs;
including accessories (connectors consecutively numbered
and labeling fields)
Terminal with eight digital outputs;
including accessories (connectors not consecutively
numbered and labeling fields)
Transmission Speed 2 Mbps
Terminal with eight digital outputs; without accessories
Terminal with eight digital outputs; including accessories
(connectors consecutively numbered and labeling fields)
Terminal with eight digital outputs; including accessories
(connectors not consecutively numbered and labeling
fields)
om
Four of the listed connectors or one connector set are needed for the complete fitting of the IB IL 24 DO 8
and IB IL DO 8-2MBD terminals.
on
l
in
ec
Connector with eight spring-cage connections
(green, w/o color print)
Connector with eight spring-cage connections
(green, with color print)
Connector set with 32 spring-cage connections
(green, w/o color print)
Connector set with 32 spring-cage connections
(green, with color print)
IB IL SCN-8
27 26 33 7
10
IB IL SCN-8-CP
27 27 60 8
10
IB IL DI/DO 8-PLSET
28 60 95 0
1
IB IL DI/DO 8-PLSET/CP
28 60 96 3
1
Documentation
Description
"Configuring and Installing the INTERBUS Inline Product
Range" user manual
"Automation Terminals of the Inline Product Range" user
manual
Data sheet for the
IB IL 24 SAFE 1 (-PAC) safety terminal
Order Designation
IB IL SYS PRO UM E
Order No.
27 43 04 8
IL SYS INST UM E
26 98 73 7
DB EN IB IL 24 SAFE 1 (-PAC)
90 04 91 3
© PHOENIX CONTACT 08/2005
5558_en_07
PHOENIX CONTACT