    DIGITAL OUTPUT TERMINAL BLOCK

  • 数据手册
  • 价格&库存
2861687 数据手册
IB IL 24 DO 8 ... Inline Terminal With Eight Digital Outputs AUTOMATIONWORX Data Sheet Description – – – – – – – Connections for eight digital actuators Connection of actuators in 2, 3, and 4-wire technology Nominal current of each output: 0.5 A Total current of the terminal: 4 A Short-circuit and overload protected outputs Diagnostic and status indicators Approved for use within a safety-related segment circuit (not valid for IB IL 24 DO 8-PAC/SN) on l in ec om po ne The terminal is designed for use within an Inline station. It is used to output digital signals. nt Features s. © PHOENIX CONTACT - 08/2005 co m 4 x This data sheet is only valid in association with the IB IL SYS PRO UM E user manual or the Inline system manual for your bus system. Please observe the notes on page 4 when using the terminal within a safety-related segment circuit. Make sure you always use the latest documentation. It can be downloaded at www.download.phoenixcontact.com. A conversion table is available on the Internet at www.download.phoenixcontact.com/general/7000_en_00.pdf. This data sheet is valid for the terminals listed under "Ordering Data" on page 12. 5558_en_07 PHOENIX CONTACT GmbH & Co. KG • Flachsmarktstraße 8 • 32825 Blomberg • Germany Phone: +49-(0) 5235-3-00 • Fax: +49-(0) 5235-3-4 12 00 • www.phoenixcontact.com www.phoenixcontact.com/salesnetwork 1 IB IL 24 DO 8 ... Distinguishing the Product Versions The product versions with and without "PAC" only differ in the scope of supply (see "Ordering Data" on page 12). Their function and technical data are identical. – – Without PAC: With PAC: Local Diagnostic/Status Indicators and Terminal Point Assignment Local Diagnostic and Status Indicators Without accessories Including connectors and labeling fields D 1 2 The product versions with and without "SN" only differ with regard to the numbering of the terminal points on the different connector versions (see Figure 2 on page 3). Their function and technical data are identical. nt 500 kbps 2 Mbps Figure 1 Further differing technical data are particularly identified. 5 5 5 8 C 0 0 2 Local diagnostic and status indicators Des. Color Meaning D Green Diagnostics 1, 2 Yellow Status indicators of the outputs Function Identification Pink 2 Mbps: white stripe in the vicinity of the D LED on l in ec om po For greater clarity, the designation IB IL 24 DO 8 is used throughout this document. ne Without 2MDB: With 2MBD: 2 8 m PAC without SN: Connectors consecutively numbered With PAC/SN: Connectors not consecutively numbered The terminal functions with and without "2MBD" are identical. The essential difference between them is the transmission speed. – – 1 2 co – 1 2 s. – D O 1 5558_en_07 PHOENIX CONTACT 2 IB IL 24 DO 8 ... Terminal Point Assignment for Each Connector B 1 x 2 x x 1 .1 1 1 2 .1 1 .1 1 1 .2 2 2 2 .2 1 .2 2 1 .3 3 3 2 .3 1 .3 1 .4 4 4 2 .4 1 .4 1 2 1 2 1 2 1 2 1 .1 2 .1 3 .1 4 .1 5 .1 6 .1 7 .1 8 .1 1 1 1 .2 2 .2 1 1 3 .2 1 .3 2 .3 3 3 .3 1 .4 4 2 .4 3 .4 2 8 .2 3 8 .3 4 8 .4 8 .2 8 .3 3 3 5 .4 4 .4 7 .3 6 .3 3 3 4 4 8 .1 2 2 5 .3 4 .3 7 .2 6 .2 2 2 3 3 1 1 1 5 .2 4 .2 2 2 x 4 4 7 .4 6 .4 4 4 8 .4 m 4 x 6 9 5 0 A 0 0 7 Terminal point numbering: individual connectors (A) and connector sets (B) s. Figure 2 co A – – Using the IB IL 24 DO 8-PAC/SN or IB IL 24 DO 8-2MBD-PAC/SN with the supplied connectors Using individual connectors (IB IL SCN-8 or IB IL SCN-8-CP) B – – Using the IB IL 24 DO 8-PAC or IB IL 24 DO 8-2MBD-PAC with the original connector set Using a connector set (IB IL DI/DO 8-PLSET or IB IL DI/DO 8-PLSET/CP) Assignment x.1 Signal output (OUT 1) x.2 Segment voltage US for 4-wire termination om Terminal Point po ne nt A in ec Measuring points for the supply voltage Ground contact (GND) for 2, 3, and 4-wire termination x.4 FE connection for 3 and 4-wire termination on l x.3 5558_en_07 PHOENIX CONTACT 3 IB IL 24 DO 8 ... Notes on Using the Terminals Within a Safety-Related Segment Circuit The terminals of the following hardware version and later (listed below) are approved for use within a safety-related segment circuit. 1 The IB IL 24 DO 8-PAC/SN terminal is not approved for use within a safety-related segment circuit. IB IL 2 4 D O 8 O rd e r-N o .: 2 7 2 6 2 6 9 M o d u le - ID : X X Hardware Version 05 05 IB IL DO 8-2MBD IB IL 24 DO 8-2MBD-PAC IB IL 24 DO 8-2MBD-PAC/SN 04 04 04 0 5 /- 5 5 5 8 A 0 0 8 Figure 3 Imprinting on an Inline terminal m IB IL 24 DO 8 IB IL 24 DO 8-PAC H W /S W IN T E R B U S co 500 kbps 27 26 26 9 28 61 28 9 2 Mbps 28 19 03 7 28 61 68 7 28 78 22 7 Order Designation The instructions of the current data sheet of the safety terminal that opens the safety-related segment circuit must be followed to ensure that the function of the safety-related segment circuit is not affected! s. Order No. Up-to-date documentation can be downloaded at www.download.phoenixcontact.com. on l in ec om po ne nt The hardware version is imprinted on the side of the housing of every terminal (1 in Figure 3). 5558_en_07 PHOENIX CONTACT 4 IB IL 24 DO 8 ... Internal Circuit Diagram L o c a l b u s O P C U L 4 2 4 2 2 4 4 2 2 2 2 M ) Internal wiring of the terminal points om Figure 4 Key: Protocol chip (bus logic including voltage conditioning) LED in ec OPC po ne + 2 4 V (U ) S nt + 2 4 V (U s. co m 2 5 5 5 8 C 0 0 3 Other symbols used are explained in the IB IL SYS PRO UM E user manual or in the Inline system manual for your bus system. on l Optocoupler Transistor Digital output Electrically isolated area 5558_en_07 PHOENIX CONTACT 5 IB IL 24 DO 8 ... Connection Example Programming Data/Configuration Data INTERBUS 2 D 1 1 2 0 bytes Output address area 1 byte Parameter channel (PCP) 0 bytes Register length (bus) 1 byte For the programming data/configuration data of other bus systems, please refer to the corresponding electronic device data sheet (GSD, EDS). 1 2 1 2 1 2 1 1 1 1 1 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 ne nt 1 1 s. 2 om in ec O U T + 2 4 V O U T 8 bits Input address area Other Bus Systems 2 1 A Figure 5 1 2 Process data channel 8 1 B 5 5 5 8 2 0 0 4 Typical actuator connection 4-wire termination 3-wire termination on l A B 1 2 81hex po D O 4 3 BDhex (189dec) Length code co 1 ID code m When connecting the actuators observe the assignment of the terminal points to the process data (see page 7). The numbers above the module illustration identify the connector slots. 5558_en_07 PHOENIX CONTACT 6 IB IL 24 DO 8 ... Process Data For the assignment of the illustrated (byte.bit) view to your INTERBUS control or computer system, please refer to data sheet DB EN IBS SYS ADDRESS, Order No. 90 00 99 0. Assignment of the Terminal Points to the OUT Process Data Byte 0 7 Bit 4 4 3 2 3 1 2 0 1 8.1 7.1 6.1 5.1 4.1 3.1 2.1 1.1 Terminal point (+24 V) 8.2 7.2 6.2 5.2 4.2 3.2 2.2 1.2 Terminal point (GND) 8.3 7.3 6.3 5.3 4.3 3.3 2.3 1.3 Terminal point (FE) 8.4 7.4 6.4 5.4 4.4 3.4 2.4 1.4 s. Terminal point (signal) Slot 4 2 3 1 2 2 1 2 1 1 2 1 po LED nt Status indicator Slot 5 ne Assignment 6 co (Byte.bit) view Byte m The following table applies to the IB IL 24 DO 8-PAC and IB IL 24 DO 8-2MBD-PAC terminals with the original connector set and when using the IB IL DI/DO 8-PLSET and IB IL DI/DO 8-PLSET/CP connector sets (see also Figure 2 on page 3, detail B). om The following table applies to the IB IL 24 DO 8-PAC/SN and IB IL 24 DO 8-2MBD-PAC/SN terminals with the original connector set and when using the IB IL SCN-8 or IB IL SCN-8-CP connectors (see also Figure 2 on page 3, detail A). Bit Status indicator 5558_en_07 Slot 7 6 Byte 0 5 4 4 3 3 2 1 2 0 1 Terminal point (signal) 2.1 1.1 2.1 1.1 2.1 1.1 2.1 1.1 Terminal point (+24 V) 2.2 1.2 2.2 1.2 2.2 1.2 2.2 1.2 Terminal point (GND) 2.3 1.3 2.3 1.3 2.3 1.3 2.3 1.3 Terminal point (FE) 2.4 1.4 2.4 1.4 2.4 1.4 2.4 1.4 on l Assignment in ec (Byte.bit) view Byte Slot LED 4 2 3 1 2 2 1 2 1 1 2 1 PHOENIX CONTACT 7 IB IL 24 DO 8 ... Technical Data General Data Housing dimensions (width x height x depth) Weight Operating mode Connection method for actuators Permissible temperature (operation) Permissible temperature (storage/transport) Permissible humidity (operation) 48.8 mm x 120 mm x 71.5 mm 130 g (without connectors) Process data mode with 1 byte 2, 3, and 4-wire technology -25°C to +55°C -25°C to +85°C 75% on average, 85% occasionally co m In the range from - 25°C to + 55°C appropriate measures against increased humidity (> 85%) must be taken. Permissible humidity (storage/transport) 75% on average, 85% occasionally s. For a short period, slight condensation may appear on the outside of the housing if, for example, the terminal is brought into a closed room from a vehicle. ne po Interface Local bus 80 kPa to 106 kPa (up to 2000 m above sea level) 70 kPa to 106 kPa (up to 3000 m above sea level) IP20 according to IEC 60529 Class 3 according to VDE 0106, IEC 60536 nt Permissible air pressure (operation) Permissible air pressure (storage/transport) Degree of protection Class of protection in ec Transmission Speed IB IL 24 DO 8 IB IL 24 DO 8-PAC IB IL 24 DO 8-PAC/SN IB IL DO 8-2MBD IB IL 24 DO 8-2MBD-PAC IB IL 24 DO 8-2MBD-PAC/SN om Through data routing 500 kbps 500 kbps 500 kbps 2 Mbps 2 Mbps 2 Mbps 7.5 V DC 60 mA, maximum 0.45 W, maximum 24 V DC (nominal value) 4 A (8 x 0.5 A), maximum Power Consumption (2 Mbps) Communications power Current consumption from the local bus Power consumption from the local bus Segment supply voltage US Nominal current consumption at US 7.5 V DC 85 mA, maximum 0.64 W, maximum 24 V DC (nominal value) 4 A (8 x 0.5 A), maximum on l Power Consumption (500 kbps) Communications power Current consumption from the local bus Power consumption from the local bus Segment supply voltage US Nominal current consumption at US 5558_en_07 PHOENIX CONTACT 8 IB IL 24 DO 8 ... Digital Outputs Number Nominal output voltage UOUT Differential voltage for Inom Nominal current Inom per channel Tolerance of the nominal current Total current Protection 8 24 V DC ≤1V 0.5 A +10% 4A Short-circuit; overload m Supply of the Module Electronics and I/O Through Bus Terminal/Power Terminal Connection method Through potential routing co Always 4 channels are thermally coupled, i.e. an error case in one channel can affect the other channels. Nominal load Ohmic Lamp Inductive Signal delay upon power up of Nominal ohmic load Nominal lamp load s. nt ne om po 100 µs, typical 100 ms, typical (with switching frequencies up to 8 Hz; above this frequency the lamp load responds like an ohmic load) 100 ms (1.2 H, 50 Ω), typical in ec Nominal inductive load Signal delay upon power down of Nominal ohmic load Nominal lamp load Nominal inductive load Switching frequency with Nominal ohmic load 48 Ω / 12 W 12 W 12 VA (1.2 H, 50 Ω) 1 ms, typical 1 ms, typical 50 ms (1.2 H, 50 Ω), typical 300 Hz, maximum on l This switching frequency is limited by the selected data rate, the number of bus devices, the bus structure, the software and the control or computer system used. Nominal lamp load 300 Hz, maximum This switching frequency is limited by the selected data rate, the number of bus devices, the bus structure, the software and the control or computer system used. Nominal inductive load Overload response Response time with ohmic overload (12Ω) Restart frequency with ohmic overload Restart frequency with lamp overload Response with inductive overload Response time in the event of a short circuit Reverse voltage protection against short pulses 5558_en_07 0.5 Hz (1.2 H, 48 Ω), maximum Auto restart 3 s, approximately 400 Hz, approximately 400 Hz, approximately Output may be damaged 400 ms, approximately Protected against reverse voltages PHOENIX CONTACT 9 IB IL 24 DO 8 ... co m The output follows the supply voltage without delay. -15 V ≤ Udemag ≤ -46 V (Udemag = demagnetization voltage) 400 mJ, maximum Integrated 45 V Zener diode in the output chip 0.7 A, minimum 300 µA, maximum 2 V, maximum 25 mA, maximum 100 mW at 1 kΩ load resistance, typical 1.5 A for 20 ms, maximum s. One-time unsolicited energy Protective circuit type Overcurrent shutdown Output current when switched off Output voltage when switched off Output current with ground connection interrupted Switching power with ground connection interrupted Inrush current with lamp load Up to 2 A DC Protective elements in the bus terminal or power terminal No 5 ms, typical nt Digital Outputs (Continued) Resistance to permanently applied reverse voltages Resistance to polarity reversal of the supply voltage Resistance to permanently applied surge voltage Validity of output data after connecting the 24 V voltage supply (power up) Response upon power down Limitation of the voltage induced on circuit interruption om po ne Output Characteristic Curve When Switched On (Typical) Output Current (A) 0 0.1 0.2 0.3 0.4 0.5 Differential Output Voltage (V) 0 0.04 0.08 0.12 0.16 0.20 on l 2 Mbps in ec Power Dissipation Formula to Calculate the Power Dissipation of the Electronics 500 kbps 8 P P E L E L = 0 .1 9 W + Σ (0 .1 0 W = 0 .4 6 W + S n = 1 + IL 2 n 8 n = 1 (0 .1 0 W + IL n 2 x 0 . 4 0 Ω) x 0 .4 0 W ) Where PEL Total power dissipation in the terminal n Index of the number of set outputs n = 1 to 8 Load current of output n ILn Power Dissipation of the Housing PHOU 2.7 W, maximum (within the permissible operating temperature) Limitation of Simultaneity, Derating Derating 5558_en_07 No limitation of simultaneity, no derating PHOENIX CONTACT 10 IB IL 24 DO 8 ... Safety Equipment Overload/short circuit in segment circuit Surge voltage Electronic; with two 4-channel drivers Protective circuits of the power terminal; Polarity reversal of the supply voltage Protection up to 33 V DC Protective circuits of the power terminal; Reverse voltage It is necessary to protect the voltage supply. The power supply unit should be able to supply 4 times (400%) the nominal current of the fuse. Protection up to 2 A DC m Electrical Isolation/Isolation of the Voltage Areas s. co To provide electrical isolation between the logic level and the I/O area, it is necessary to supply the station bus terminal and the digital output terminal described here using the bus terminal or a power terminal from separate power supply units. Interconnection of the power supply units in the 24 V area is not permitted. (See also the IB IL SYS PRO UM E user manual). om po ne nt Common Potentials The 24 V main voltage, 24 V segment voltage, and GND have the same potential. FE is a separate potential area. Separate Potentials in the System Consisting of Bus Terminal/Power Terminal and I/O Terminal - Test Distance - Test Voltage 5 V supply incoming remote bus / 7.5 V supply (bus logic) 500 V AC, 50 Hz, 1 min 5 V supply outgoing remote bus / 7.5 V supply (bus logic) 500 V AC, 50 Hz, 1 min 7.5 V supply (bus logic) / 24 V supply (I/O) 500 V AC, 50 Hz, 1 min 24 V supply (I/O) / functional earth ground 500 V AC, 50 Hz, 1 min in ec Error Messages to the Higher-Level Control or Computer System Short circuit/overload of an output Yes An error message is generated when an output is short circuited and switched on. In addition, the diagnostic LED (D) flashes on the terminal at 2 Hz (medium) under these conditions. No on l Operating voltage out of range 5558_en_07 PHOENIX CONTACT 11 IB IL 24 DO 8 ... Ordering Data Terminals Pcs./Pkt. IB IL 24 DO 8 IB IL 24 DO 8-PAC 27 26 26 9 28 61 28 9 1 1 IB IL 24 DO 8-PAC/SN 28 62 94 5 1 m Order No. 1 1 s. IB IL 24 DO 8-2MBD-PAC/ SN 28 78 22 7 1 Order Designation Order No. Pcs./Pkt. po Description 28 19 03 7 28 61 68 7 co IB IL DO 8-2MBD IB IL 24 DO 8-2MBD-PAC ne Connectors Order Designation nt Description Transmission Speed 500 kbps Terminal with eight digital outputs; without accessories Terminal with eight digital outputs; including accessories (connectors consecutively numbered and labeling fields) Terminal with eight digital outputs; including accessories (connectors not consecutively numbered and labeling fields) Transmission Speed 2 Mbps Terminal with eight digital outputs; without accessories Terminal with eight digital outputs; including accessories (connectors consecutively numbered and labeling fields) Terminal with eight digital outputs; including accessories (connectors not consecutively numbered and labeling fields) om Four of the listed connectors or one connector set are needed for the complete fitting of the IB IL 24 DO 8 and IB IL DO 8-2MBD terminals. on l in ec Connector with eight spring-cage connections (green, w/o color print) Connector with eight spring-cage connections (green, with color print) Connector set with 32 spring-cage connections (green, w/o color print) Connector set with 32 spring-cage connections (green, with color print) IB IL SCN-8 27 26 33 7 10 IB IL SCN-8-CP 27 27 60 8 10 IB IL DI/DO 8-PLSET 28 60 95 0 1 IB IL DI/DO 8-PLSET/CP 28 60 96 3 1 Documentation Description "Configuring and Installing the INTERBUS Inline Product Range" user manual "Automation Terminals of the Inline Product Range" user manual Data sheet for the IB IL 24 SAFE 1 (-PAC) safety terminal Order Designation IB IL SYS PRO UM E Order No. 27 43 04 8 IL SYS INST UM E 26 98 73 7 DB EN IB IL 24 SAFE 1 (-PAC) 90 04 91 3 © PHOENIX CONTACT 08/2005 5558_en_07 PHOENIX CONTACT 12
2861687 价格&库存

很抱歉,暂时无法提供与“2861687”相匹配的价格&库存,您可以联系我们找货

免费人工找货