Inline Terminal With Two Digital Inputs
DI2
AUTOMATIONWORX
Data Sheet
5549_en_03
© PHOENIX CONTACT - 09/2006
Description
The terminal is designed for use within an Inline station. It is
used to acquire digital input signals.
Features
–
–
–
–
–
Connections for two digital sensors
Connection of sensors in 2, 3, and 4-wire technology
Maximum permissible load current per sensor: 250 mA
Maximum permissible load current from the terminal:
0.5 A
Diagnostic and status indicators
This data sheet is only valid in association with the IB IL SYS PRO UM E user manual or the Inline system
manual for your bus system.
Make sure you always use the latest documentation.
It can be downloaded at www.download.phoenixcontact.com.
A conversion table is available on the Internet at
www.download.phoenixcontact.com/general/7000_en_00.pdf.
This data sheet is valid for the products listed on the following page:
IB IL 24 DI 2 ...
Ordering Data
Products
Description
Type
Order No.
Pcs./Pck.
Inline terminal with two digital inputs; including accessories
(connectors and labeling field);
transmission speed 500 kbps
IB IL 24 DI 2-PAC
2861221
1
Inline terminal with two digital inputs; without accessories
transmission speed 500 kbps
IB IL 24 DI 2
2726201
1
Inline terminal with two digital inputs; without accessories;
transmission speed 2 Mbps
IB IL 24 DI 2-2MBD
2819066
1
Inline terminal with two digital inputs; including accessories
(connectors and labeling field);
transmission speed 2 Mbps
IB IL 24 DI 2-2MBD-PAC
2861713
1
One of the listed connectors is needed for the complete fitting of the IB IL 24 DI 2 and IB IL 24 DI 2-2MBD terminals.
Accessories
Description
Type
Order No.
Pcs./Pck.
Connector with eight spring-cage connections (green, w/o color print)
IB IL SCN-8
2726337
10
Connector with eight spring-cage connections (green, with color print)
IB IL SCN-8-CP
2727608
10
Documentation
Description
Type
Order No.
Pcs./Pck.
"Configuring and Installing the INTERBUS Inline Product Range"
user manual
IB IL SYS PRO UM E
2743048
1
"Automation Terminals of the Inline Product Range"
user manual
IL SYS INST UM E
2698737
1
Technical Data
General Data
Housing dimensions (width x height x depth)
12.2 mm x 120 mm x 71.5 mm
Weight
53 g (with connector); 38 g (without connector)
Mode of operation
Process data mode with 2 bits
Connection method for sensors
2, 3, and 4-wire technology
Permissible temperature (operation)
-25°C to +55°C
Permissible temperature (storage/transport)
-25°C to +85°C
Permissible humidity (operation/storage/transport)
10% / 95% according to EN 61131-2
Permissible air pressure (operation/storage/transport)
70 kPa to 106 kPa (up to 3000 m above sea level)
Degree of protection
IP20 according to IEC 60529
Class of protection
Class 3 according to VDE 0106, IEC 60536
Connection data for Inline Connectors
Connection type
Spring-cage terminals
Conductor cross section
0.2 mm2 to 1.5 mm2 (solid or stranded)
Interface
Local bus
Through data routing
Transmission Speed
IB IL 24 DI 2, IB IL 24 DI 2-PAC
500 kbps
IB IL 24 DI 2-2MBD, IB IL 24 DI 2-2MBD-PAC
2 Mbps
5549_en_03
PHOENIX CONTACT
2
IB IL 24 DI 2 ...
Power Consumption (500 kbps)
Communications power
7.5 V
Current consumption at UL
35 mA, maximum
Power consumption at UL
0.27 W, maximum
Segment supply voltage US
24 V DC (nominal value)
Nominal current consumption at US
0.5 A (2 x 0.25 A), maximum
Power Consumption (2 Mbps)
Communications power
7.5 V
Current consumption at UL
50 mA, maximum
Power consumption at UL
0.375 W, maximum
Segment supply voltage US
24 V DC (nominal value)
Nominal current consumption at US
0.5 A (2 x 0.25 A), maximum
Supply of the Module Electronics and I/O Through the Bus Coupler/Power Terminal
Connection method
Through potential routing
Digital Inputs
Number
2
Input design
According to EN 61131-2 Type 1
Definition of switching thresholds
Maximum low-level voltage
ULmax < 5 V
Minimum high-level voltage
UHmin > 15 V
Common potentials
Segment supply, ground
Nominal input voltage UIN
24 V DC
Permissible range
-3 V < UIN < +30 V DC
Nominal input current for UIN (at 500 kbps)
5 mA
Nominal input current for UIN (at 2 Mbps)
3 mA, minimum
Current flow (500 kbps)
Linear in range 1 V < UIN < 30 V
Current flow (2 Mbps)
See table "Characteristic Curve (at 2 Mbps): Current Depending on the Input
Voltage and the Ambient Temperature TA" on page 4
Delay time
None
Permissible cable length to the sensor
30 m
Use of AC sensors
AC sensors in the voltage range < UIN are limited in application
Input Characteristic Curve (500 kbps)
Input Voltage (V)
5549_en_03
Typical Input Current (mA)
-3 < UIN < 0.7
0
3
0.4
6
1.0
9
1.7
12
2.3
15
3.0
18
3.7
21
4.4
24
5.0
27
5.7
30
6.4
PHOENIX CONTACT
3
IB IL 24 DI 2 ...
Characteristic Curve (at 2 Mbps): Current Depending on the Input Voltage and the Ambient Temperature TA
Supply Voltage
Input Current
Input Current acc. to t >= 20 s
for TA = 25°C
for TA = 55°C
18 V
3.0 mA
2.9 mA
24 V
3.9 mA
3.8 mA
2.5 mA
3.5 mA
30 V
4.5 mA
4.2 mA
3.0 mA
The current is reduced depending on the ambient temperature TA and the number of inputs that are switched on (module internal temperature).
Power Dissipation
Formula to Calculate the Power Dissipation of the Electronics
500 kbps
2 Mbps
2
PEL = 0.21 W + S [ UINn x
n=1
Where
PEL
n
UINn
UINn -1.8 V
]
4400 W
P
E L
= 0 .3 7 5 W
+ S
2
n = 1
[ U
IN n
x 0 .0 0 3 A ]
Total power dissipation in the terminal
Index of the number of set inputs n = 1 to 2
Input voltage of the input n
Power Dissipation of the Housing PHOU
0.6 W (within the permissible operating temperature)
Limitation of Simultaneity, Derating
Derating
No limitation of simultaneity, no derating
Safety Equipment
Overload in segment circuit
No
Surge voltage
Protective elements of the power terminal
Polarity reversal
Protective elements of the power terminal
Electrical Isolation/Isolation of the Voltage Areas
To provide electrical isolation between the logic level and the I/O area it is necessary to supply the station bus coupler and the digital input
terminal via the bus coupler or a power terminal from separate power supply units. Interconnection of the power supply units in the 24 V
area is not permitted. (See also user manual.)
Common Potentials
The 24 V main voltage, 24 V segment voltage, and GND have the same potential. FE is a separate potential area.
Separate Potentials in the System Consisting of Bus Coupler/Power Terminal and I/O Terminal
- Test Distance
- Test Voltage
5 V supply incoming remote bus / 7.5 V supply (bus logic)
500 V AC, 50 Hz, 1 min
5 V supply outgoing remote bus / 7.5 V supply (bus logic)
500 V AC, 50 Hz, 1 min
7.5 V supply (bus logic) / 24 V supply (I/O)
500 V AC, 50 Hz, 1 min
24 V supply (I/O) / functional earth ground
500 V AC, 50 Hz, 1 min
Error Messages to the Higher-Level Control or Computer System
None
Approvals
Information on current approvals can be found on the Internet at www.download.phoenixcontact.com.
5549_en_03
PHOENIX CONTACT
4
IB IL 24 DI 2 ...
Local Diagnostic and Status Indicators
and Terminal Point Assignment
1
Internal Circuit Diagram
Local bus
D
2
OPC
DI 2
UL
D
1 2
DI2
1
2
1.1
1
1
2.1
1.2
2
2
2.2
1.3
3
3
2.3
1.4
4
4
+24 V (US)
+24 V (UM)
2.4
5549A002
Figure 1
Terminal with appropriate connectors
5549A003
Local Diagnostic and Status Indicators
Desig. Color Meaning
D
Green Diagnostics
1, 2 Yellow Status indicators of the inputs
Figure 2
Key:
OPC
Function identification
Light blue
Internal wiring of the terminal points
Protocol chip (bus logic including voltage
conditioning)
LED
2 Mbps: white stripe in the vicinity of the D LED
Terminal Point Assignment
Terminal Point
1.1, 2.1
1.2, 2.2
1.3, 2.3
1.4, 2.4
5549_en_03
Assignment
Signal input (IN)
Segment voltage US
for 2, 3, and 4-wire termination
Ground contact (GND)
for 3 and 4-wire termination
FE connection for
4-wire termination
Optocoupler
Digital input
Electrically isolated area
Other symbols used are explained in the
IB IL SYS PRO UM E user manual or in the
Inline system manual for your bus system.
PHOENIX CONTACT
5
IB IL 24 DI 2 ...
Connection Example
Programming Data/Configuration Data
When connecting the sensors observe the
assignment of the terminal points to the
process data (see page 6).
D
1
INTERBUS
ID code
BEhex (190dec)
Length code
C2hex
Process data channel
2 bits
Input address area
2 bits
Output address area
0 bits
Parameter channel (PCP)
0 bits
Register length (bus)
2 bits
2
Other Bus Systems
D I 2
For the programming data/configuration data
of other bus systems, please refer to the
corresponding electronic device data sheet
(e.g., GSD, EDS).
2
1
1
2
2
3
3
4
4
Process Data
Figure 3
Byte.bit
0.1 0.0
Module
Terminal point (signal)
2.1 1.1
Terminal point (+24 V)
2.2 1.2
Terminal point (GND)
2.3 1.3
Terminal point (FE)
2.4 1.4
LED
2
2
B
Typical sensor connections
4-wire termination
3-wire termination
(Byte.bit) view
IN
+ 2 4 V
A
A
B
Assignment of the Terminal Points to the IN Process
Data
+ 2 4 V
IN 1
1
5 5 4 9 A 0 0 4
Status indicator
1
For the assignment of the illustrated (byte.bit)
view to your INTERBUS control or computer
system, please refer to the
DB GB IBS SYS ADDRESS data sheet,
Order No. 9000990.
© PHOENIX CONTACT 09/2006
5549_en_03
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
Phone: +49-(0) 5235-3-00 • Fax: +49-(0) 5235-3-4 12 00
www.phoenixcontact.com
6
很抱歉,暂时无法提供与“2861713”相匹配的价格&库存,您可以联系我们找货
免费人工找货