ILB DN 24 DI16 DO16
Inline Block IO Module
for DeviceNet™ With 16 Digital Inputs
and 16 Digital Outputs
AUTOMATIONWORX
Data Sheet
6885_en_05
© PHOENIX CONTACT - 03/2007
Description
Input Features
The ILB DN 24 DI16 DO16 module is designed for use
within a DeviceNet™ network. It is used to acquire and
output digital signals.
–
–
–
–
DeviceNet™ Features
–
–
–
–
–
–
I/O peer-to-peer communication
Direct peer-to-peer communication
Consistent configuration
Faulted node recovery
Baud rates: 125 kbaud, 250 kbaud, 500 kbaud
I/O slave messages:
Polling, cyclic transmission,
change of state (COS), bit strobing
–
Connections for 16 digital sensors
Connection of sensors in 2 and 3-wire technology
Maximum permissible load current per sensor: 125 mA
Maximum permissible load current from the sensor
supply: 2.0 A
Diagnostic and status indicators
Output Features
–
–
–
–
–
–
Connections for 16 digital actuators
Connection of actuators in 2 and 3-wire technology
Nominal current per output: 0.5 A
Total current of all outputs: 8 A
Short-circuit and overload protected outputs
Diagnostic and status indicators
Please refer to the "Mounting and Removing Inline Block IO Modules" application note (see "Ordering Data"
on page 2).
Make sure you always use the latest documentation.
It can be downloaded at www.download.phoenixcontact.com.
Here you will also find the current EDS file.
A conversion table is available on the Internet at
www.download.phoenixcontact.com/general/7000_en_00.pdf.
ILB DN 24 DI16 DO16
Ordering Data
Product
Description
Inline Block IO module for DeviceNet™ with 16 digital inputs and 16 digital
outputs
Type
Order No.
Pcs./Pkt.
ILB DN 24 DI16 DO16
2862602
1
Accessories: Connector
Description
Type
Order No.
Pcs./Pkt.
TWIN-COMBICON connector for bus connection
TMSTBP 2,5/ 5-STF-5,08 GNAU CP
2862576
1
Accessories: Connectors as Replacement Item
Description
Type
Order No.
Pcs./Pkt.
Connector for the supply (color print)
IB IL SCN-PWR IN-CP
2727637
5
Connector, with color print, for digital 4-channel or 16-channel Inline output
terminals
IB IL SCN-12-OPC
2727624
10
Connector, with color print, for digital 4-channel or 16-channel Inline input
terminals
IB IL SCN-12-IPC
2727611
10
Accessories: Other
Description
Type
Order No.
Pcs./Pkt.
CLIPFIX 35-5
3022276
50
Documentation
Description
Type
Order No.
Pcs./Pkt.
"Mounting and Removing Inline Block IO Modules" application note
AH ILB INSTALLATION
9014931
1
"Configuring a DeviceNet™ System Using Devices in the Fieldline Product
Range" user manual
FLS FLM DN SYS PRO UM E
2699082
1
"Addressing of 16-Channel ILB Modules" application note
AH ILB 24 DI/DO 16 ADDRESS
9014962
1
Recommended end clamp; placed both to the right and left of the module to
secure it on the DIN rail
6885_en_05
PHOENIX CONTACT
2
ILB DN 24 DI16 DO16
Technical Data
General Data
Housing dimensions with connectors (width x height x depth)
156 mm x 55 mm x 141 mm
Weight
500 g, approximately (with connectors)
Operating mode
Process data mode with 4 bytes
Transmission speed
125 kbaud, 500 kbaud
Type of sensor and actuator connection
2 and 3-wire technology
Housing Dimensions
55
141
120
156
6885A003
Figure 1
Housing dimensions of the module (dimensions in mm)
Ambient Conditions
Regulations
Developed according to VDE 0160/EN 50178/IEC 62103, UL 508
Ambient temperature (operation)
-25°C to +60°C
Ambient temperature (storage/transport)
-25°C to +85°C
Humidity (operation/storage/transport)
10% to 95% according to EN 61131-2
Air pressure (operation)
80 kPa to 108 kPa (up to 2000 m above sea level)
Air pressure (storage/transport)
66 kPa to 108 kPa (up to 3500 m above sea level)
Degree of protection according to IEC 60529
IP20
Class of protection
Class 3 according to VDE 0106/IEC 60536
Air and creepage distances
According to DIN VDE 0110/IEC 60664, IEC 60664A,
DIN VDE 0160/EN 50178/IEC 62103
Housing material
Plastic, PVC-free, PBT, self-extinguishing (V0)
Pollution degree according to
EN 60664-1/IEC 60664-1, EN 61131-2/IEC 61131-2
2; condensation not permitted during operation
Surge voltage class
II
6885_en_05
PHOENIX CONTACT
3
ILB DN 24 DI16 DO16
Electrical Isolation/Isolation of the Voltage Areas
Test Distance
Test Voltage
DeviceNet™ / I/O
500 V AC, 50 Hz, 1 min
DeviceNet™ / functional earth ground
500 V AC, 50 Hz, 1 min
I/O / functional earth ground
500 V AC, 50 Hz, 1 min
Mechanical Requirements
Vibration test, sinusoidal vibrations according to
EN 60068-2-6/IEC 60068-2-6
5g load, 2.5 hours in each space direction
Shock test according to EN 60068-2-27/IEC 60068-2-27
25g load for 11 ms, half sinusoidal wave,
3 shocks in each space direction and orientation
Broadband noise according to EN 60068-2-64/IEC 60068-2-64
0.78g load, 2.5 hours in each space direction
Conformance With EMC Directive 89/336/EEC
Noise Immunity Test According to EN 61000-6-2
Electrostatic discharge (ESD)
EN 61000-4-2
IEC 61000-4-2
Criterion B
Electromagnetic fields
EN 61000-4-3
IEC 61000-4-3
Criterion A
Fast transients (burst)
EN 61000-4-4/
IEC 61000-4-4
Criterion B
6 kV contact discharge
8 kV air discharge
Field strength: 10 V/m
Remote bus: 2 kV
Power supply: 2 kV
I/O cables: 2 kV
Criterion A
All interfaces: 1 kV
Surge voltage
EN 61000-4-5
IEC 61000-4-5
Criterion B
DC supply lines: ±0.5 kV/±1.0 kV (symmetrical/asymmetrical)
Signal cables: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical)
Conducted interference
EN 61000-4-6
IEC 61000-4-6
Criterion A
Test voltage 10 V
Noise Emission Test According to EN 61000-6-4
Noise emission of housing
EN 55011
Class A
Interface
DeviceNet™ interface
RS-485; COMBICON connector;
shielding directly connected with functional earth ground
24 V Module Supply
Communications Power UL
Nominal value
24 V DC
Tolerance
11 V DC to 25 V DC according to the ODVA specification
Ripple
±5% according to EN 61131-2
Permissible range
11.0 V DC to 30.0 V DC
Current consumption at UL
25 mA
Safety equipment
Surge protection and protection against polarity reversal
Connection
Via power connectors
6885_en_05
PHOENIX CONTACT
4
ILB DN 24 DI16 DO16
24 V Module Supply (Continued)
Sensor and Actuator Supply; US and UA
Nominal value
24 V DC
Tolerance
-15%/+20% according to EN 61131-2
Ripple
±5% according to EN 61131-2
Permissible range
19.2 V DC to 30.0 V DC
Current consumption at US
2A
Current consumption at UA1 and UA2
2x4A
Safety equipment for the sensor supply
Surge, overload and short-circuit protection
Safety equipment for the actuator supply
Surge protection
Connection
Via power connectors
Digital Outputs
Number
16
Connection method for actuators
2 and 3-wire technology
Nominal output voltage UOUT
24 V DC
Differential voltage at Inom
≤1V
Nominal current Inom per channel
0.5 A
Total current
2x4A
Protection
Short-circuit and overload protection
Nominal load
48 Ω/12 W
Ohmic
Lamp
12 W
Inductive
12 VA (1.2 H, 50 Ω)
Switching frequency with nominal inductive load
0.5 Hz (1.2 H, 50 Ω), maximum
Overload response
Auto restart
Response with inductive overload
Output may be damaged
Reverse voltage protection against short pulses
Protected against reverse voltages
Resistance to permanently applied reverse voltages
Protected against reverse voltages, permissible current 2 A, maximum
Validity of output data after connecting the 24 V supply voltage (power up)
5 ms, typical
Response upon power down
The output follows the supply voltage without delay.
Limitation of the voltage induced on circuit interruption
-41.0 V
One-time unsolicited energy
1 J, maximum
Protective circuit type
Integrated free running circuit in the output chip
Overcurrent shutdown
0.7 A, minimum
Maximum output current when switched off
10 µA
When not loaded, a voltage can be measured even at an output that is not set.
6885_en_05
PHOENIX CONTACT
5
ILB DN 24 DI16 DO16
Digital Inputs
Number
16
Connection method for sensors
2 and 3-wire technology
Input design
According to EN 61131-2 Type 1
Definition of switching thresholds
Maximum low-level voltage
ULmax < 5 V
Minimum high-level voltage
UHmin > 15 V
Common potentials
Sensor supply US, ground
Nominal input voltage UIN
24 V DC
Permissible range
-30 V < UIN < +30 V DC
Nominal input current for UIN
5 mA, typical
Current flow
Linear in the range 1 V < UIN < 30 V
Delay time
≤ 500 µs
Permissible cable length to the sensor
100 m
Use of AC sensors
AC sensors in the voltage range < UIN are limited in application
Power Dissipation
Formula to Calculate the Power Dissipation of the Electronics
n
m
PTOT = 1.92 W + IS x 0.06 W + S (0.04 W + I x 0.28 W) + S 0.125 W
2
i=1
2
Li
j=1
Where
PTOT
IS
i
n
ILi
j
m
Total power dissipation of the module
Current from the sensor supply
Index
Number of set outputs (n = 1 to 16)
Load current of the output i
Index
Number of set inputs (m = 1 to 16)
Limitation of Simultaneity, Derating
No limitation of simultaneity, no derating
Approvals
For the latest approvals, please visit www.download.phoenixcontact.com.
6885_en_05
PHOENIX CONTACT
6
ILB DN 24 DI16 DO16
Internal Circuit Diagram
N T
IO
M D
8 x
8 x
D N
8 x
8 x
5 V
2 4 V
U
U
A 1
A 2
D O 1 ...8
U
L
U
D O 9 ..1 6
D I1 ...8
D I9 ..1 6
S
1 6 x
O U T
1 6 x
IN
D e v ic e N e t
6 8 8 5 A 0 0 2
Figure 2
Internal wiring of the terminal points
Key:
LED
D N
DeviceNet™ protocol chip (bus logic)
Power supply unit with electrical isolation
Optocoupler
Short-circuit-proof output
Short-circuit-proof sensor supply
6885_en_05
PHOENIX CONTACT
7
ILB DN 24 DI16 DO16
Local Diagnostic and Status Indicators
B U S
E
1
1
1
2
I1
N T
1
2
3
2
3
4
I2
2
3
4
I3
4
3
I4
4
IO
M D
IN
E
1
1
O 1
U S
2
3
4
E
1
2
3
O 2
4
1
2
3
O 3
4
2
3
O 4
4
O U T
U A 1
U A 2
U L
P W R 1
P W R 2
P W R
Figure 3
6 8 8 5 A 0 0 5
Diagnostic and status indicators of the ILB DN 24 DI16 DO16 module
Designation
BUS
NT
Color
Meaning
Red/green LED
ON (green)
Network status
Module online, connection established.
ON (red)
Flashing (green)
Group 2 devices are assigned to a master.
Error that prevents communication with the network
(e.g., bus offline or double device ID).
Device online, connections not established.
Device has finished the "Dup_MAC_ID" test but has not established
connections to other nodes.
Flashing (red)
Flashing (red-green)
OFF
Group 2 devices are not assigned to a master.
One or more connections are in timeout state.
Network access error
Device not online.
Device has not yet finished the "Dup_MAC_ID" test.
Device is not supplied with voltage.
6885_en_05
PHOENIX CONTACT
8
ILB DN 24 DI16 DO16
Designation
IO
MD
Color
Red/green LED
ON (green)
ON (red)
Flashing (green)
Flashing (red)
Flashing (red-green)
OFF
Red/green LED
ON (green)
ON (red)
Flashing (green)
Flashing (red)
Flashing (red-green)
OFF
Meaning
I/O status (input/output)
One or more outputs are active, no error state is present.
Error parameterization due to undervoltage or overload at US
Error parameterization due to undervoltage at +24 V DC or at UA
Inputs and outputs maintain their state despite error message.
Error parameterization is not active.
Error state detected due to undervoltage at +24 V DC or UA.
Baud rate setting/detection (autobaud)
No output is active, no error state is present.
Device status (module diagnostics)
Normal operation
Unrecoverable error
– Device not configured, or device configuration not complete or faulty
– Device in standby mode
Recoverable error
Selftest
No supply voltage
PWR
US
UL
UA1
UA2
Green
Green
Green
Green
Sensor supply
24 V communications power
Actuator supply 1 (connector 3 and connector 4 for actuators)
Actuator supply 2 (connector 5 and connector 6 for actuators)
E
1-4
Red
Yellow
Short circuit or overload at one of the outputs
Status indicators of the outputs
E
1-4
Red
Yellow
Short circuit or overload of the sensor supply
Status indicators of the inputs
OUT
IN
The NT, IO and MD LEDs may flash green and red at the same time.
If the error LED (E) of a group of 8 outputs is on (e.g., connector 3 and connector 4), this indicates that a short
circuit or overload is present at one or more of the outputs in this group.
Default setting of the error parameterization:
– All outputs are deactivated.
– All inputs remain unchanged.
6885_en_05
PHOENIX CONTACT
9
ILB DN 24 DI16 DO16
Setting the Address and Baud Rate
Configure the hardware on the module using the 10-pos.
DIP switch. This switch can be used to set both the
DeviceNet™ address and the baud rate. For the meaning
of the switches, please refer to the following tables.
Connecting DeviceNet™, the Supply,
Actuators, and Sensors
Connecting DeviceNet™
A D D R E S S
2
3
4
5
6
7
8
9
1 .1
1 .2
1 .3
1 .4
1 .5
1 0
2 .1
2 .2
2 .3
2 .4
2 .5
X 1
6 8 8 5 A 0 0 4
Figure 4
6 8 8 5 A 0 0 7
DIP switches of the module
DIP switch 1 (SW1) is the MSB (most significant bit) of the
node ID and DIP switch 7 (SW7) is the LSB (least
significant bit).
Switch the power off and back on to accept
address changes.
DIP Switch Address Settings (MAC ID)
ON
OFF
SW1
64
0
SW2
32
0
SW3
16
0
SW4
8
0
SW5 SW6
4
2
0
0
SW7
1
0
The DeviceNet™ transmission speed is set using DIP
switches 8 to 10. The following table shows the switch
settings for different baud rates.
DIP Switch Baud Rate Settings
SW8
ON
ON
OFF
OFF
ON
D e v ic e N e t
1
SW9
ON
OFF
ON
OFF
ON
6885_en_05
SW10
OFF
OFF
OFF
OFF
ON
Baud Rate
Can be set using software
500 kbaud
250 kbaud
125 kbaud
Auto (default)
Figure 5
Pin assignment of the TWIN-COMBICON
connector
Connect the DeviceNet™ via a TWIN-COMBICON
connector to the module. For the pin assignment, please
refer to the following table:
Pin
1.1, 2.1
1.2, 2.2
1.3, 2.3
1.4, 2.4
1.5, 2.5
Color
Red
White
Bare
Blue
Black
Signal
V+
CAN H
Drain
CAN L
V-
Description
+24 V DC for UL
CAN High
Shield
CAN Low
GND
In the DeviceNet™ system, a termination
resistor (121 Ω / 0.25 W with 1% tolerance)
must be fitted at each end of the main line.
PHOENIX CONTACT
10
ILB DN 24 DI16 DO16
Connecting the Supply, Actuators, and Sensors
1
1
1
2 .1
1 .2
2
2
2 .2
3
3
4
4
1 .3
1 .4
1
1 .1
1 .2
1 -2
Figure 6
2
1
2 .1
2
2 .2
1
2
1 .3
3
3
2 .3
1 .4
4
4
2 .4
2
1 .1
1 .5
1 .6
2 .3
2 .4
5
6
6
2 .5
5
3 -1 0
Terminal point assignment of Inline
connectors
2 .6
6 8 8 5 A 0 0 6
Terminal Point Assignment of Power Connectors
(Connectors 1 and 2 in Figure 6)
Terminal Point Assignment
Connector 1 (PWR 1)
1.1, 2.1
24 V sensor supply US
1.2, 2.2
24 V communications power UL,
(voltage for module test, not intended
for use within the DeviceNet™
network)
1.3, 2.3
GND
1.4, 2.4
FE
Connector 2 (PWR 2)
1.1, 2.1
24 V actuator supply UA1, UA2
1.2, 2.2
24 V communications power UL,
(voltage for module test, not intended
for use within the DeviceNet™
network)
1.3, 2.3
GND
1.4, 2.4
FE
If the module is used in a DeviceNet™
network, UL must be connected to the
COMBICON connector. Therefore, connect UL
to the COMBICON connector at pin V+ and
pin V-.
The connection options at Inline connectors 1
and 2 are designed for test purposes only.
The terminal points can have a total current of
8 A per terminal point. The maximum current
carrying capacity of 8 A must not be exceeded.
If the total output current in your application is
> 8 A, supply the module via a minimum of two
terminal points connected in parallel.
The supply points have the same ground
potential. All ground supplies on a module are
electrically connected with one another.
The communications power is also electrically
connected via all contacts. In this way, it can
supply all potentials with just one supply
without the need for additional terminals, see
"Connection Example" on page 13.
6885_en_05
PHOENIX CONTACT
11
ILB DN 24 DI16 DO16
Terminal Point Assignment of Output Connectors (Connectors 3 to 6 in Figure 6 on page 11)
Terminal Point
Assignment
Connector 3
(O1)
Connector 4
(O2)
Connector 5
(O3)
Connector 6
(O4)
1.1, 2.1
1.1, 2.1
1.1, 2.1
1.1, 2.1
Signal output (OUT)
1.2, 2.2
1.2, 2.2
1.2, 2.2
1.2, 2.2
Ground contact (GND) for 2 and 3-wire termination
1.3, 2.3
1.3, 2.3
1.3, 2.3
1.3, 2.3
FE connection for 3-wire termination
1.4, 2.4
1.4, 2.4
1.4, 2.4
1.4, 2.4
Signal output (OUT)
1.5, 2.5
1.5, 2.5
1.5, 2.5
1.5, 2.5
Ground contact (GND) for 2 and 3-wire termination
1.6, 2.6
1.6, 2.6
1.6, 2.6
1.6, 2.6
FE connection for 3-wire termination
Terminal Point Assignment of Input Connectors (Connectors 7 to 10 in Figure 6 on page 11)
Terminal Point
Assignment
Connector 7
(I1)
Connector 8
(I2)
Connector 9
(I3)
Connector 10
(I4)
1.1, 2.1
1.1, 2.1
1.1, 2.1
1.1, 2.1
Signal input (IN)
1.2, 2.2
1.2, 2.2
1.2, 2.2
1.2, 2.2
Sensor voltage for 2 and 3-wire termination
1.3, 2.3
1.3, 2.3
1.3, 2.3
1.3, 2.3
Ground contact (GND) for 3-wire termination
1.4, 2.4
1.4, 2.4
1.4, 2.4
1.4, 2.4
Signal input (IN)
1.5, 2.5
1.5, 2.5
1.5, 2.5
1.5, 2.5
Sensor voltage for 2 and 3-wire termination
1.6, 2.6
1.6, 2.6
1.6, 2.6
1.6, 2.6
Ground contact (GND) for 3-wire termination
6885_en_05
PHOENIX CONTACT
12
ILB DN 24 DI16 DO16
Connection Example
2
1
2
1
2
1
8
2
1
9
2
1
1 0
2
1
2
1 1
1 1
1 1
1 1
1 1
1 1
1
2
2 2
2 2
2 2
2 2
2 2
2 2
2 2
2 2
2 2
2
3
3 3
3 3
3 3
3 3
3 3
3 3
3 3
3 3
3 3
3
4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4 4
4
5
5 5
5 5
5 5
5 5
5 5
5 5
5 5
5
6
6 6
6 6
6 6
6 6
6 6
6 6
6 6
6
U
+
A 1
U
-
+ 2 4 V
1 1
O U T 1 6
1 1
O U T 6
1 1
+
S
2
7
1
D e v ic e N e t
U
1
6
1 4
1
2
5
IN
1
4
+ 2 4 V
2
3
1 5
1
2
IN
1
A 2
6 8 8 5 A 0 1 0
Figure 7
Connection example
If the module is used in a DeviceNet™
network, UL must be connected to the
COMBICON connector. Therefore, connect UL
to the COMBICON connector at pin V+ and
pin V-.
The connection options at Inline connectors 1
and 2 are designed for test purposes only (see
"Terminal Point Assignment of Power
Connectors (Connectors 1 and 2 in Figure 6)"
on page 11).
The module has an FE spring (metal clip) on
the bottom of the electronics base. This spring
creates an electrical connection to the DIN rail.
Use grounding terminals to connect the
DIN rail to protective earth ground. The module
is grounded when it is snapped onto the
DIN rail.
To ensure reliable functional earth grounding
of the module even when the DIN rail is dirty or
the metal clip is damaged, Phoenix Contact
also recommends grounding the module via
one of the FE terminal points.
The numbers above the module illustration
identify the connector slots.
6885_en_05
PHOENIX CONTACT
13
ILB DN 24 DI16 DO16
Device Data
ID number
120hex
Input address area
4 bytes
Output address area
4 bytes
Process Data
Byte 0 (inputs)
Byte 1 (inputs)
Byte 0
Byte 1
Input Address Area (Produced Process Data)
Byte 2
Byte 3
(reading back output byte 0)
(reading back output byte 1)
Output Address Area (Consumed Process Data)
Reserved
Reserved
Please refer to the application note for addressing 16-channel ILB modules.
The documentation can be downloaded at www.download.phoenixcontact.com.
Here you will also find the current EDS file.
Assignment of Terminal Points to the OUT Process Data Word (Slots 3 to 6)
(Word.bit) view Word
Bit
(Byte.bit) view Byte
Bit
Module
Slot
Terminal point (signal)
Terminal point (GND)
Terminal point FE
Status indicator Slot
LED
15
14
13
7
12 11
Byte 0
4
3
10
9
Word 0
8
7
6
5
4
3
Byte 1
4
3
2
4
3
Byte 1
4
3
2
1
0
6
5
2
1
0
7
6
5
2
1
0
4 (O2)
3 (O1)
6 (O4)
5 (O3)
2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1
2.5 1.5 2.2 1.2 2.5 1.5 2.2 1.2 2.5 1.5 2.2 1.2 2.5 1.5 2.2 1.2
2.6 1.6 2.3 1.3 2.6 1.6 2.3 1.3 2.6 1.6 2.3 1.3 2.6 1.6 2.3 1.3
4 (O2)
3 (O1)
6 (O4)
5 (O3)
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
Assignment of Terminal Points to the IN Process Data Word (Slots 7 to 10)
(Word.bit) view Word
Bit
(Byte.bit) view Byte
Bit
Module
Slot
Terminal point (signal)
Terminal point (24 V)
Terminal point (GND)
Status indicator Slot
LED
6885_en_05
15
7
14
13
12 11
Byte 0
4
3
10
9
Word 0
8
7
6
5
1
0
6
5
2
1
0
7
6
5
2
1
0
8 (I2)
7 (I1)
10 (I4)
9 (I3)
2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1
2.5 1.5 2.2 1.2 2.5 1.5 2.2 1.2 2.5 1.5 2.2 1.2 2.5 1.5 2.2 1.2
2.6 1.6 2.3 1.3 2.6 1.6 2.3 1.3 2.6 1.6 2.3 1.3 2.6 1.6 2.3 1.3
8 (I2)
7 (I1)
10 (I4)
9 (I3)
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
PHOENIX CONTACT
14
(Byte.bit) view
Device
6885_en_05
5
4
3
2
US overload
Actuator supply failure
Short circuit of digital outputs
Initiator supply
24 V supply voltage
Undervoltage UL
Reserved
Reserved
Reserved
Reserved
Not configured or
unknown I/O
Reserved
Bit 2
Short circuit of
digital outputs
Reserved
Bit 3
Module type
unknown
Reserved
Bit 4
Error handling
active
Bit 5
1
0
Communications power failure at Inline connector
6
US failure
Bit 6
Communications power failure at COMBICON connector
7
Reserved
Byte
Bit
Error
0: NMV has been re-initialized (possibly due to a
hardware fault).
1: NMV has been initialized correctly with a
corresponding parameterization at Phoenix Contact.
Byte 1
Bit 7
Undervoltage US
Diagnostic
Data
Byte 0
Reserved
ILB DN 24 DI16 DO16
Diagnostic Data
Mapping of Diagnostic Data in DeviceNet™ (Class 1, Attribute 5)
Bit 1
Bit 0
An error is indicated in class 1, attribute 5 when the respective bit value is "1".
Class 102, Attribute 103 (Error Information)
Byte 0
An error is indicated in class 102, attribute 103 when the respective bit value is "0".
PHOENIX CONTACT
15
ILB DN 24 DI16 DO16
Error Table With Diagnostic Data and Status Indicators
Error Type
Sensor voltage US too low
Actuator supply UA1 or UA2 too low
Short circuit of a sensor supply
Diagnostic Data
Class 102, attribute 103
Byte 0 bit 5 is set to "0"
Class 102, attribute 103
Byte 0 bit 3 is set to "0"
Class 102, attribute 103
Byte 0 bit 4 is set to "0"
Class 102, attribute 103
Byte 0 bit 2 is set to "0"
Short circuit of a digital output
Status Indicators
US LED is off.
IO LED is red.
UA1 or UA2 LED is off.
IO LED flashes green or red if no error
parameterization is activated.
E LED of the sensor supply is red.
IO LED is red.
E LED of the affected output group is red.
IO LED is green.
The output behavior in the event of an error is parameterized using the "Discrete Output Point Object" (09dec, 09hex)(DOP).
Outputs are reset by default.
For additional information, please refer to the FLS FLM DN SYS PRO UM E user manual (see "Ordering Data"
on page 2).
Attributes of the Connection Object (05dec, 05hex) Class
The Connection Object class describes the individual connection types. The following tables have been taken from the
ODVA specification for DeviceNet™.
Attributes of the Connection Object Class
Attribute
Requirement
1
Required
State
USINT
State of the object
2
Required
instance_type
USINT
Indicates either I/O or Messaging
Connection
3
Required
transportClass_trigger
BYTE
Defines behavior of the Connection
4
Required
produced_
connection_id
UINT
Placed in CAN Identifier Field when the
Connection transmits
5
Required
consumed_
connection_id
UINT
CAN Identifier Field value that denotes
message to be received
6
Required
initial_comm_
characteristics
BYTE
Defines the Message Group(s) across which
productions and consumptions associated
with this Connection occur
7
Required
produced_
connection_size
UINT
Maximum number of bytes transmitted
across this Connection
8
Required
consumed_
connection_size
UINT
Maximum number of bytes received across
this Connection
6885_en_05
Attribute Name
Type
Short Description
(According to ODVA)
PHOENIX CONTACT
16
ILB DN 24 DI16 DO16
Attribute
Requirement
Attribute Name
Type
Short Description
(According to ODVA)
9
Required
expected_packet_rate
UINT
Defines timing associated with this
Connection
10, 11
N/A
12
Required
watchdog_
timeout_action
13
Required
produced_
connection_
path_length
14
Required
produced_
connection_path
15
Required
consumed_
connection_
path_length
16
Required
consumed_
connection_path
17
Conditional
N/A
production_inhibit_
time
N/A
USINT
UINT
Not used. These attribute IDs have been
obsoleted and are no longer defined for a
Connection Object
Defines how to handle Inactivity/ Watchdog
Timeouts
Number of bytes in the
produced_connection_path attribute
Array of USINT Specifies the Application Object(s) whose
data is to be produced by this Connection
Object.
UINT
Number of bytes in the consumed_
connection_path attribute
Array of USINT Specifies the Application Object(s) that are
to receive the data consumed by this
Connection Object
UINT
Defines minimum time between new data
production. This attribute is required for I/O
Client connections
© PHOENIX CONTACT 03/2007
6885_en_05
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
Phone: +49 - 52 35 - 30 0 • Fax: +49-(0) 5235-3-4 12 00
www.phoenixcontact.com