IB IL AO 2/SF ...
Inline terminal with two analog outputs
4 x
AUTOMATION
Data sheet
6655_en_06
1
© PHOENIX CONTACT 2010-03-15
Description
The terminal is designed for use within an Inline station. It is
used to output analog voltage or current signals. The signals
are available with a 16-bit resolution.
Features
–
–
–
–
–
–
–
Two analog signal outputs to connect either voltage or
current signals
Actuator connection in 2-wire technology with shield
connection
Two current ranges, one voltage range:
0 mA to 20 mA, 4 mA to 20 mA,
0 V to 10 V
Process data update including conversion time of the
digital/analog converter 99%
No-load operation
44 µs
72 µs
Ohmic load RL = 2 kΩ
46 µs
74 µs
Ohmic/capacitive load RL = 2 kΩ / CL = 10 nF
47 µs
95 µs
Ohmic/capacitive load RL = 2 kΩ / CL = 220 nF
79 µs
350 µs
Ohmic/inductive load RL = 2 kΩ / LL = 3.3 mH
48 µs
75 µs
Signal rise times: Current output 0 mA to 20 mA (typical values)
10% to 90%
0% to > 99%
Ohmic load RL = 500 Ω
126 µs
380 µs
Ohmic/capacitive load RL = 500 Ω/CL = 10 nF
140 µs
425 µs
Ohmic/capacitive load RL = 500 Ω/CL = 220 nF
350 µs
1200 µs
Ohmic/inductive load RL = 500 Ω/LL = 3.3 mH
110 µs
368 µs
Signal rise times: Current output 4 mA to 20 mA (typical values)
10% to 90%
0% to > 99%
Ohmic load RL = 500 Ω
140 µs
508 µs
Ohmic/capacitive load RL = 500 Ω/CL = 10 nF
145 µs
534 µs
Ohmic/capacitive load RL = 500 Ω/CL = 220 nF
380 µs
1200 µs
Ohmic/inductive load RL = 500 Ω/LL = 3.3 mH
116 µs
410 µs
Tolerance and temperature response of the outputs for TA = 25°C
Output range
Absolute tolerance
Typical
Maximum
Relative tolerance
Typical
Maximum
0 V to 10 V
±0.8 mV
±2.0 mV
±0.008%
0 mA to 20 mA
±2 µA
±6 µA
±0.01%
±0.02%
±0.03%
4 mA to 20 mA
±2 µA
±6 µA
±0.01%
±0.03%
Tolerance and temperature response of the outputs for TA = -25°C to +55°C
Output range
Temperature coefficient
Typical
Maximum
0 V to 10 V
±8 ppm/K
0 mA to 20 mA
±18 ppm/K
±25 ppm/K
±45 ppm/K
4 mA to 20 mA
±18 ppm/K
±45 ppm/K
Outside the specified range, tolerances at the analog outputs might increase when gradually switching off the 24 V supply voltage UANA. They
occur below UANA = +13.5 V. If UANA continues to fall, an I/O error is triggered.
All percentage tolerance values refer to the relevant measuring range final value.
The maximum tolerance values contain the theoretical maximum possible tolerances. The validity of the values is 12 months at least.
The data refers to nominal operation (installation on horizontal DIN rail, US = 24 V). Please also observe the values for temperature drift and the
tolerances under EMC influences. The tolerances for the different voltage and current output areas are documented with a high level of accuracy
for the keying.
6655_en_06
PHOENIX CONTACT
4
IB IL AO 2/SF ...
Additional tolerances influenced by electromagnetic fields
Type of electromagnetic interference
Typical deviation from the
output range final value
(voltage output)
Relative
Typical deviation of the
output range final value
(current output)
Relative
Electromagnetic fields;
Field strength 10 V/m
according to EN 61000-4-3/IEC 61000-4-3
< 0.1%
< 0.1%
Conducted interference
Class 3 (test voltage 10 V)
according to EN 61000-4-6/IEC 61000-4-6
< 0.1%
< 0.3%
Fast transients (burst)
2 kV supply, 1 kV output
according to EN 61000-4-4/IEC 61000-4-4
Class A
Class A
Fast transients (burst)
4 kV supply, 2 kV output
according to EN 61000-4-4/IEC 61000-4-4
Class B
Class B
Protective equipment
Transient protection for voltage and current outputs
Electrical isolation/isolation of the voltage areas
Electrical isolation of the logic level from the I/O area is ensured through optocouplers and the DC/DC converters.
Common potentials
24 V I/O voltage, 24 V segment voltage, and GND have the same potential. FE is a separate potential area.
Separate potentials in the system consisting of bus coupler/power terminal and I/O terminal
Test distance
Test voltage
7.5 V supply (bus logic), 24 V supply UANA / I/O
500 V AC, 50 Hz, 1 min.
7.5 V supply (bus logic), 24 V supply UANA/functional earth ground
500 V AC, 50 Hz, 1 min.
24 V supply (I/O) / functional earth ground
500 V AC, 50 Hz, 1 min.
Error messages to the higher-level control or computer system
Failure or insufficient analog supply voltage UANA
Yes, I/O error message sent to the bus coupler
Approvals
For the latest approvals, please visit www.phoenixcontact.net/catalog.
6655_en_06
PHOENIX CONTACT
5
IB IL AO 2/SF ...
4
Local diagnostic and status
indicators and terminal point
assignment
4.2
Function identification
Yellow
2 Mbps: White stripe in the vicinity of the D LED
4.3
Terminal point assignment
Connector Terminal Signal
point
1
1.1, 2.1
+U
D
O -S
A O 2 S F
1.2, 2.2
1.3, 2.3
1.4, 2.4
1.1
B1
AGND
Shield
+I0-20
2.1
+I4-20
3
1.2, 2.2
1.3, 2.3
1.4, 2.4
1.1, 2.1
B2
AGND
Shield
+U
4
1.2, 2.2
1.3, 2.3
1.4, 2.4
1.1
B1
AGND
Shield
+I0-20
2.1
+I4-20
1.2, 2.2
1.3, 2.3
1.4, 2.4
B2
AGND
Shield
2
1
2
1 .1
1
1
2 .1
1 .2
2
2
2 .2
1 .3
3
3
2 .3
1 .4
4
4
2 .4
6 6 5 5 B 0 0 1
Figure 1
4.1
Terminal with an appropriate connector
Local diagnostic and status indicators
Des.
D
O-S
Color
Green
Orange
Meaning
Diagnostics
Original default state parameterized
Note on the O-S LED:
Assignment
Voltage output of
channel 1
Jumper 1
Analog ground
Shield connection
Current output
of channel 1
0 mA to 20 mA
Current output
of channel 1
4 mA to 20 mA
Jumper 2
Analog ground
Shield connection
Voltage output of
channel 2
Jumper 1
Analog ground
Shield connection
Current output
of channel 2
0 mA to 20 mA
Current output
of channel 2
4 mA to 20 mA
Jumper 2
Analog ground
Shield connection
By default upon delivery, the terminal parameters are set as
follows:
Data format:
Behavior of the outputs in
the event of an error (failsafe):
IB IL
Outputs hold the last value
(hold)
As soon as these parameters are identified on the terminal,
the O-S LED will light up. If at least one of the parameters is
different (because of non-volatile or volatile
parameterization) the LED will not light up.
After power up the non-volatile stored parameterization
always becomes valid.
6655_en_06
PHOENIX CONTACT
6
IB IL AO 2/SF ...
5
Installation instructions
High current flowing through potential jumpers UM and US
leads to a temperature rise in the potential jumpers and
inside the terminal. To keep the current flowing through the
potential jumpers of the analog terminals as low as possible,
always place the analog terminals after all the other
terminals at the end of the main circuit. (For the sequence of
the Inline terminals: see also IL SYS INST UM E user
manual or Inline system manual for your bus system).
6
Installation instruction
Installing jumpers may influence the accuracy of the
channels independently of each other. Without using
jumpers the voltage channels have a high level of accuracy
and the current channels have a low level of accuracy.
Installing a jumper for a channel increases the accuracy of a
current output. This also reduces the accuracy of the
voltage output. Only install the jumper when using a current
channel. Installing a jumper when using a voltage channel
will not be indicated as an error. Changing the jumper will
only take effect upon power up.
Encoding table
Represen- Connec- Jumper Status
tation in
tor
Figure 2
A
X*
J1
Not
installed
Y*
J2
Not
installed
B
X*
J1
Installed
Y*
J2
Not
installed
Meaning
High level of
accuracy
0 V to +10 V
High level of
accuracy
0 mA to
+20 mA
C
X*
J1
Not
High level of
installed accuracy
Y*
J2
Installed 4 mA to
+20 mA
X*Y* represent connectors 1 and 2 (channel 1) or
connectors 3 and 4 (channel 2).
A
C h a n n e l 1 C h a n n e l 2
Y
X
1
2
1
2
1
1
2
B
Y
X
Y
X
2
1
2
1
1
2
1 1
1 1
1 1
1
1
11
1
2
2 2
2 2
2 2
2
2
22
2
3 3
3 3
3 3
4 4
4 4
4 4
J 1
1
3
4
3
33
3
4
4
44
C
Y
X
3
2
2
1
Y
1
2
2
1 1
1
1
1 1
1
2
2 2
2
2
2 2
2
J 2
1
3 3
3
4
1
X
4
4 4
3 3
3
3
4
4
4 4
3
4
6 6 5 5 A 0 0 3
Figure 2
6655_en_06
Figure for the encoding table
PHOENIX CONTACT
7
IB IL AO 2/SF ...
7
Internal basic circuit diagram
L o c a l b u s
U
O P C
L +
A N A
L -
U
U
2 4 V
µ P
E E P R O M
S E C
+ 7 ,5 V
/ + 1 5 V
R E F
4
U
I0
-2 0
I4
I0
U
-2 0
+ 2 4 V (U S )
-2 0
I4
-2 0
2
+ 2 4 V (U M )
1
6 6 5 5 B 0 0 9
Figure 3
Internal basic circuit diagram
Key:
Protocol chip
OPC
µ P
Reference voltage
Optocoupler
Amplifier
Microprocessor
Digital/analog converter
Protective circuit (security)
S E C
R E F
1
Analog ground, electrically isolated
from ground of the potential jumper
Electrically erasable re-programmable
read-only memory
E E P R O M
x x x
DC/DC converter with electrical
isolation
X X X
Other symbols used are explained in the
IL SYS INST UM E user manual.
6655_en_06
PHOENIX CONTACT
8
IB IL AO 2/SF ...
8
Electrical isolation
Local bus (IN)
Bus connection
OPC
UL (7.5 V DC)
Local bus (OUT)
D
O-S
/SF
AO2
D
UL (7.5 V DC)
O-S
UANA (24 V DC)
UANA (24 V DC)
AO2SF
24 V
A
5V
+-15 V
1
Electrical isolation
between area A and B
5V
+-15 V
Figure 4
Analog outputs
6857A008
Connection notes
Always connect the analog actuators using shielded,
twisted pair cables.
At the terminal, connect one end of the shielding to FE. At
the module, fold the outer cable sheath back and connect
the shield to the terminal via the shield connection clamp.
The clamp connects the shield directly to FE on the module
side.
1
2
1
2
J2
1
11
11
11
1
2
22
22
22
2
3
33
33
33
3
4
44
44
44
4
B
Use connectors with shield connection when
installing the actuator. On free slots you may use
one of the connectors listed in the ordering data.
Figure 5 and Figure 6 show the connection
schematically (without shield connector).
OUT2
6655C007
Actuator connection to the voltage and current
outputs using 2-wire technology with shield
connection
B: Channel 2, signals for one actuator at the current output
4 mA to 20 mA with high precision
D
O-S
AO2
/SF
D
O-S
AO2SF
1
J1
Connection examples
I
A: Channel 1, signals for an actuator at the voltage output
0 V to 10 V
When using cables longer than 10 m in environments prone
to interference, we recommend connecting the shield on the
actuator to the FE potential additionally via an RC element.
The capacitor C should typically have values of 1 nF to
15 nF. The resistor R should have a resistance of at least
10 MΩ.
10
2
A
Electrical isolation of the individual function
areas
Figure 5
9
1
OUT1
U
FE potential
2
B
I/O interface
OUT1
I
1
2
1
2
1
2
J2
1
11
11
11
1
2
22
22
22
2
3
33
33
33
3
4
44
44
44
4
A
Figure 6
2
I
B
OUT2
6655C008
Actuator connection to the current outputs
using 2-wire technology with shield connection
J1, J2: External jumpers
A: Channel 1, signals for an actuator at the current output
0 mA to 20 mA with a high level of accuracy
B: Channel 2, signals for an actuator at the current output
4 mA to 20 mA with a high level of accuracy
6655_en_06
PHOENIX CONTACT
9
IB IL AO 2/SF ...
11
Programming data/
configuration data
11.1
Local bus (INTERBUS)
ID code
Length code
Process data channel
Input address area
Output address area
Parameter channel (PCP)
Register length (bus)
11.2
5Bhex (91dec)
02hex
32 bits
2 words
2 words
0 bytes
2 words
Other bus systems
For the programming data of other bus systems,
please refer to the corresponding electronic
device data sheet (e.g., GSD, EDS).
6655_en_06
PHOENIX CONTACT
10
IB IL AO 2/SF ...
12
Process data
For the assignment of the illustrated (byte.bit)
view to your INTERBUS control or computer
system, please refer to the
DB GB IBS SYS ADDRESS data sheet.
12.1
Assignment of the terminal points to OUT process data
(Word.Bit) view Word
Bit
(Byte.Bit) view Byte
Bit
Assignment
IB IL format
Assignment
IB ST format
Terminal points Signal
slot 1
AGND
Shielding (FE)
Terminal points Signal
slot 2
AGND
Shielding (FE)
(Word.Bit) view Word
Bit
(Byte.Bit) view Byte
Bit
Assignment
IB IL format
Assignment
IB ST format
Terminal points Signal
slot 3
AGND
Shielding (FE)
Terminal points Signal
slot 4
AGND
Shielding (FE)
SB
0
15
14
13
7
SB
SB
6
5
15
14
13
7
SB
SB
6
5
12 11
Byte 0
4
3
10
9
Word 0
8
7
6
5
1
0
7
6
5
Output value channel 1
Output value channel 1
Terminal point 1.1.1: Voltage output
Terminal point 1.1.3, 1.2.3
Terminal point 1.1.4, 1.2.4
Terminal point 2.1.1: Current output 0 mA to 20 mA
Terminal point 2.2.1: Current output 4 mA to 20 mA
Terminal point 2.1.3, 2.2.3
Terminal point 2.1.4, 2.2.4
12 11
Byte 2
4
3
2
4
3
Byte 1
4
3
10
9
2
Word 1
8
7
6
5
4
3
Byte 3
4
3
1
0
7
6
5
Output value channel 2
Output value channel 2
Terminal point 3.1.1: Voltage output
Terminal point 3.1.3, 3.2.3
Terminal point 3.1.4, 3.2.4
Terminal point 4.1.1: Current output 0 mA to 20 mA
Terminal point 4.2.1: Current output 4 mA to 20 mA
Terminal point 4.1.3, 4.2.3
Terminal point 4.1.4, 4.2.4
2
1
0
2
1
0
0
0
0
2
1
0
2
1
0
0
0
0
Sign bit
In "IB ST" format bits 2 through 0 are irrelevant. Set these bits to "0".
6655_en_06
PHOENIX CONTACT
11
IB IL AO 2/SF ...
12.2
Assignment of the IN process data
(Word.Bit) view Byte
Bit
(Byte.Bit) view Byte
Bit
Assignment
(Word.Bit) view Byte
Bit
(Byte.Bit) view Byte
Bit
Assignment
SB
F
H
12.3
15
14
13
7
SB
6
5
15
14
13
7
SB
6
5
Word 0
12 11 10 9
8
7
6
5
Byte 0
4
3
2
1
0
7
6
5
Mirrored channel 1 output value
4
3
Byte 1
4
3
Word 1
12 11 10 9
8
7
6
5
Byte 2
4
3
2
1
0
7
6
5
Mirrored channel 2 output value
4
3
Byte 3
4
3
OUT process data
OUT 0
12.4
0
2
F
1
0
0
H
2
1
0
2
F
1
0
0
H
OUT1
IN process data
Bits 15 through 3 of the process data output values are
mirrored in the IN process data. Bit 15 is the sign bit. Bits 2
through 0 are available as status bits. The bits contain
information on the parameterized behavior of the terminal.
IN0
MSB
LSB
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
IB IL
OV
SB
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
SB
OV
X X X
5660A006
Figure 7
OUT
MSB
LSB
SB
OV
X
1
Sign bit
Format of output data
HOLD/RESET
The OUT process data specifies the output values in each
cycle.
IB ST
2
OUT process data words in IB IL and IB ST
formats
Process data output word
Most significant bit
Least significant bit
Sign bit
Output value
Irrelevant bit
Set the irrelevant bits to 0.
MSB
LSB
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
SB
F 0 H
OV*
6655B002
Figure 8
IN
MSB
LSB
SB
OV*
F
H
IN process data words
Process data input word
Most significant bit
Least significant bit
Sign bit
Mirrored output value
Format of output data
HOLD/RESET
Bits 2 through 0 have the following meaning:
Bit
2
1
0
6655_en_06
IN1
Designa- Meaning
tion
F
Format of output
data
Reserved
H
HOLD/RESET see
page 15
Bit x = 0 Bit x = 1
IB IL
IB ST
HOLD
RESET
PHOENIX CONTACT
12
IB IL AO 2/SF ...
13
Formats for representing the output values
"IB IL" is the default format on the terminal. To ensure that
the terminal can be operated in the ST data format, the
output value representation can be switched to the "IB ST"
format.
13.1
"IB IL" format
The output value is represented in bits 14 through 0. An
additional bit (bit 15) is available as a sign bit. The sign bit is
0 for the output value 0 V to 10 V. If the sign bit is 1, which
corresponds to a negative value, the value 0 V (or 0 mA/
4 mA) is output.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
SB
OV
SB
OV
Sign bit
Output value
Bits 2 through 0 are not mirrored in the input data.
13.2
Significant output values in the "IB IL" format
The terminal has two analog output channels, which are
able to output voltages in the range of 0 V to +10 V or
currents in the range of 0 mA to 20 mA and 4 mA to 20 mA
with a resolution of 15 bits plus the sign bit.
Value range 0 V to +10 V
Area
Overflow
Overload
capability
range
Nominal range
Underflow
6655_en_06
Output data word
(two's complement)
hex
dec
7FFF
32767
7F01
32513
7F00
32512
7531
30001
7530
3A98
0001
0000
< 0000
30000
15000
1
0
7FFC
7FFC
4000
000C
≤0004
4 mA to +20 mA
IOutput
mA
19.9961
19.9961
12.0000
4.003906
4.0000
All three ranges are available in parallel for this
terminal. Therefore, bit 2, which is designed to
distinguish the measuring ranges 0 mA to 20 mA/
4 mA to 20 mA in the ST format, is irrelevant.
6655_en_06
PHOENIX CONTACT
14
IB IL AO 2/SF ...
14
Output behavior
14.1
Output behavior during error-free operation
(normal operation)
14.2
After power up the stored values for the data format and the
behavior of the outputs are read in the event of an error
(reset value). These are either the values of the
configuration upon delivery or a non-volatile stored
configuration.
Output behavior in the event of an error (failsafe)
In the event of an error the outputs respond according to the
parameterization (see "Parameterization" on page 17). That
means the outputs hold the last value (HOLD, default
setting) or they return to zero (RESET, can be
parameterized).
The data format and the behavior of the outputs in the event
of an error can be parameterized non-volatile or volatile by a
process data sequence during runtime (see
"Parameterization" on page 17).
14.3
Output behavior of the voltage and current outputs
Switching
operation/state of
the supply voltage
UANA from 0 V to 24 V
UANA from 24 V to 0 V
Local bus stopped
Local bus stopped
Bus reset
(e.g., remote bus
cable break)
UANA
UL
xxxx
14.4
Take the output behavior in the event of an error
into account when configuring your system,
especially a fail-safe behavior that was possibly
parameterized twice (for the bus coupler and the
analog terminal).
Marginal
condition
UL = 0 V
UL = 7.5 V
UANA = 0 V
UANA = 24 V
Process data
word OUT
(hex)
xxxx
xxxx
xxxx
xxxx
xxxx
Behavior/status of the analog output
0 V to 10 V
0 mA to 20 mA
4 mA to 20 mA
0V
0V
0V
0 mA
0 mA
0 mA
Hold last value
Can be parameterized:
Hold last value (default setting)
0 mA
0V
4 mA
0 mA
0 mA
4 mA
Analog supply voltage of the terminal
Supply voltage for module electronics (communications power)
Any value in the range from 0000hex to FFFFhex
Response of the voltage and current outputs to a control command of the controller board
Command
STOP
ALARM STOP (reset)
OUT process data
word
(hexadecimal)
xxxx
xxxx
State after switching operation
Analog output
0 V to 10 V
0 mA to 20 mA
0V
6655_en_06
4 mA to 20 mA
Hold last value
Can be parameterized:
Hold last value (default setting)
0 mA
4 mA
PHOENIX CONTACT
15
IB IL AO 2/SF ...
15
Input data in normal operation and in the event of an error
During error-free operation (normal operation) the
output data is mirrored in the input words as
"acknowledgment" in bits 15 through 3 as soon as it has
been transmitted to the DAC.
Bits 2 through 0 are available as status bits and are used to
display and read the set behavior of the terminal (see "IN
process data" on page 12).
If an error is detected by the terminal, it is indicated by
means of an error code in the first or second process IN
process data word depending on the error type. Possible
error codes are given in the following table.
Error codes:
Output data word
(two's complement)
hex
8010
8020
8040
Cause
Remedy
The jumpers for selecting the "high accuracy" Connect the jumpers correctly.
range are contradictory (e.g., 0 mA to 20 mA
and at the same time 4 mA to 20 mA). The error
message is indicated on the corresponding
channel only.
The user parameterization cannot be stored.
Carry out a power up.
The error message is indicated on both
channels.
Error in the I/O voltage supply
Check the voltage supply on the bus
coupler.
Check that the potential jumpers are
connecting safely.
Replace the terminal.
Terminal is defective.
Replace the terminal.
An I/O error is triggered with codes 8020hex and
8040hex.
The error codes overwrite the status bits (bits 2
through 0) with "0".
6655_en_06
PHOENIX CONTACT
16
IB IL AO 2/SF ...
16
Parameterization
By default upon delivery, the terminal parameters are set as
follows:
Data format:
Behavior of the outputs in
the event of an error:
The following terminal parameters can be configured
according to your conditions using the process data:
IB IL
Outputs hold the last value
(Hold)
Data format:
Behavior of the outputs in
the event of an error (failsafe):
IB ST
Outputs are set to 0 (reset)
In order to parameterize the terminal you must change to
parameterization mode.
Steps to be taken to parameterize the terminal:
Step 1:
Transmission of code 8030hex in the first OUT process data word.
In bits 15 through 3 of the first IN process data word this code is acknowledged as a normal process data
item.
Step 2:
Transmission of the parameterization code in the second OUT process data word.
Bit
bin
hex
15
1
14
0
13
0
12
0
11
0
10
0
8
9
0
8
0
0
7
0
6
1
5
0
4
1
3
p3
5
2
p2
1
0
0
p1
X
Where px are the terminal parameters:
p3: Volatile or non-volatile (0: Volatile; 1: Non-volatile)
p2: Data format (0: IB IL; 1: IB ST)
p1: Reset behavior (0: Hold; 1: Reset)
Both output data words must be written with a maximum time of 10 s between each other. This makes
data consistency over two words unnecessary. The writing sequence is not important. If the time has
elapsed, something else, differing from the parameter value, must be written in the two words. The
parameter words must be kept for 2 s until the parameterization is accepted.
Step 4:
Acceptance of the value is confirmed in bits 15 through 3 of the first input word through mirroring of the
code. No timer is required in the application as monitoring the input data is sufficient. When mirroring,
note that bits 2 through 0 still indicate the current terminal parameterization in each word. As soon as
the new parameterization is valid the corresponding parameter bit is set in the input data.
Step 5:
The terminal is in normal process data mode again. Prior to a new parameterization, the data on both
output words must have changed.
The orange O-S LED on the terminal indicates whether the original configuration is present or whether the active
configuration differs from the default configuration of the terminal upon delivery. The LED is on if the default state
has been parameterized (see also "Local diagnostic and status indicators" on page 6).
6655_en_06
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49-(0) 5235-3-00
PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300
www.phoenixcontact.com
17