MCR 3-way signal conditioner, with configurable input/output, for electrical isolation and
conversion of analog signals up to 30 V with screw connection, order configuration. Replacement
part: 2902036 MINI MCR-2-UI-UI-C.
Product Description
The 6.2 mm wide configurable 3-way isolating amplifier MINI MCR-SL-U-UI-... is used for electrical isolation, conversion, amplification and filtering
of standard signals.
The signals 0...24 V and 0...30 V can be processed on the input side.
The analog signals 0...20 mA, 4...20 mA, 0...10 V, 2...10 V, 0...5 V or 1..5 V are available electrically isolated on the output side.
The DIP switches, which can be accessed on the side of the housing, can be used to configure the input and output signal ranges.
Power (19.2 V DC to 30 V DC) can be supplied through connection terminal blocks on the modules or in conjunction with the DIN rail connector.
Your advantages
• Power supply possible via the foot element (TBUS)
• Low power consumption
• 3-way isolation
• Up to 12 signal combinations can be configured using DIP switches
• 30 V DC signals to create standard analog signals
• Highly-compact isolating amplifier for electrical isolation, conversion, amplification, and filtering of 24 V or
Commercial Data
Item number
2864053
Packing unit
1 pc
Minimum order quantity
1 pc
Note
Made to Order (non-returnable)
Sales Key
C01
Product Key
CK1211
Catalog Page
Page 96 (C-7-2015)
Weight per Piece (including packing)
88.1 g
Weight per Piece (excluding packing)
66.2 g
Customs tariff number
85437090
Country of origin
DE
Oct 27, 2022, 7:34 AM
Page 1 (13)
Signal conditioner - MINI MCR-SL-U-UI
2864053
https://www.phoenixcontact.com/us/products/2864053
Technical Data
Product properties
Product type
Signal conditioner
No. of channels
1
Insulation characteristics
Overvoltage category
II
Pollution degree
2
Electrical properties
No. of channels
1
Rated insulation voltage
50 V AC/DC
Electrical isolation
Basic insulation in accordance with EN 61010
Electrical isolation between input and output
yes
Limit frequency (3 dB)
approx. 100 Hz
Test voltage, input/output/supply
1.5 kV AC (50 Hz, 60 s)
Protective circuit
Transient protection
Step response (10-90%)
3.5 ms
Maximum temperature coefficient
< 0.01 %/K
Temperature coefficient, typical
< 0.002 %/K
Maximum transmission error
< 0.1 % (of final value)
< 0.4 % (Without adjustment)
Supply
Nominal supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (The DIN rail connector (ME 6,2 TBUS-2
1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the
supply voltage. It can be snapped onto a 35 mm DIN rail in
accordance with EN 60715)
Max. current consumption
< 19 mA (at 24 V DC incl. load)
Power consumption
< 450 mW
Input data
Signal:
Number of inputs
1
Configurable/programmable
Yes, preconfigured
Voltage input signal
0 V ... 24 V
0 V ... 30 V
Max. voltage input signal
50 V DC
Input resistance of voltage input
approx. 125 kΩ (0 ... 24 V)
approx. 155 kΩ (0 ... 30 V)
Output data
Oct 27, 2022, 7:34 AM
Page 2 (13)
Signal conditioner - MINI MCR-SL-U-UI
2864053
https://www.phoenixcontact.com/us/products/2864053
Signal:
Number of outputs
1
Configurable/programmable
Yes, preconfigured
Voltage output signal
0 V ... 10 V
0 V ... 5 V
1 V ... 5 V
2 V ... 10 V
Max. voltage output signal
≤ 12.5 V
Non-load voltage
≤ 12.5 V
Current output signal
0 mA ... 20 mA
4 mA ... 20 mA
Max. current output signal
28 mA
Short-circuit current
≤ 22 mA
Load/output load voltage output
> 10 kΩ
Load/output load current output
< 500 Ω (at 20 mA)
Ripple
< 20 mVPP (at 500 Ω)
< 20 mVPP (at 10 kΩ)
Connection data
Connection method
Screw connection
Stripping length
12 mm
Screw thread
M3
Conductor cross section solid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
26 ... 12
Dimensions
Dimensional drawing
Width
6.2 mm
Height
93.1 mm
Depth
102.5 mm
Material specifications
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 2
Housing material
PBT
Oct 27, 2022, 7:34 AM
Page 3 (13)
Signal conditioner - MINI MCR-SL-U-UI
2864053
https://www.phoenixcontact.com/us/products/2864053
Environmental and real-life conditions
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-20 °C ... 65 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Approval data
CE
Certificate
CE-compliant
ATEX
Identification
II 3 G Ex nA IIC T4 Gc X
UL, USA / Canada
Identification
UL 508 Recognized
Class I, Div. 2, Groups A, B, C, D T5
GL
Identification
GL EMC 2 D
EMC data
Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Noise immunity
EN 61000-6-2
Note
When being exposed to interference, there may be minimal
deviations.
Electrostatic discharge
Standards/regulations
EN 61000-4-2
Electrostatic discharge
Comments
Safety measures must be taken to prevent electrostatic
discharge.
Electromagnetic HF field
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Typical deviation from the measuring range final value
5%
Fast transients (burst)
Designation
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Typical deviation from the measuring range final value
5%
Surge current load (surge)
Standards/regulations
EN 61000-4-5
Oct 27, 2022, 7:34 AM
Page 4 (13)
Signal conditioner - MINI MCR-SL-U-UI
2864053
https://www.phoenixcontact.com/us/products/2864053
Surge current load (surge)
Comments
Criterion B
Conducted interference
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Typical deviation from the measuring range final value
5%
Standards and regulations
Electrical isolation
Basic insulation in accordance with EN 61010
Mounting
Mounting type
DIN rail mounting
Assembly instructions
The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item
no. 2869728) can be used to bridge the supply voltage. It can be
snapped onto a 35 mm DIN rail in accordance with EN 60715.
Mounting position
any
Oct 27, 2022, 7:34 AM
Page 5 (13)
Signal conditioner - MINI MCR-SL-U-UI
2864053
https://www.phoenixcontact.com/us/products/2864053
Drawings
Dimensional drawing
6,2
102,5
93,1
Oct 27, 2022, 7:34 AM
Page 6 (13)
Signal conditioner - MINI MCR-SL-U-UI
2864053
https://www.phoenixcontact.com/us/products/2864053
Block diagram
IN
Sensor / Field
OUT U
US 4-wire
GND
1
OUT
+
2
2
–
+
–
4
3
1
IN U
GND 1
+24V
OUT U, I
active
GND 2
PLC / DCS
5
6
+24V
GND 3
5
+
GND 3
passive
6
–
7
+
8
–
+24V
GND 3
Oct 27, 2022, 7:34 AM
Page 7 (13)
Signal conditioner - MINI MCR-SL-U-UI
2864053
https://www.phoenixcontact.com/us/products/2864053
Application drawing
0...24V
IN U
OUT
GND1
GND2
1
UPS
2
3
4
UB+
GND3
0...10V
5
6
UB +
GND3
MINI MCR-SL-U-UI
Controller
7
8
24V
Mains voltage
Signal conversion to uninterruptible power supply (UPS)
Oct 27, 2022, 7:34 AM
Page 8 (13)
Signal conditioner - MINI MCR-SL-U-UI
2864053
https://www.phoenixcontact.com/us/products/2864053
Classifications
ECLASS
ECLASS-9.0
27210120
ECLASS-10.0.1
27210120
ECLASS-11.0
27210120
ETIM
ETIM 7.0
EC002653
Oct 27, 2022, 7:34 AM
Page 9 (13)
Signal conditioner - MINI MCR-SL-U-UI
2864053
https://www.phoenixcontact.com/us/products/2864053
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the
manufacturer’s declaration available under “Downloads”
Oct 27, 2022, 7:34 AM
Page 10 (13)
Signal conditioner - MINI MCR-SL-U-UI
2864053
https://www.phoenixcontact.com/us/products/2864053
Accessories
DIN rail bus connectors
DIN rail bus connectors - ME 6,2 TBUS-2 1,5/5-ST-3,81 GN - 2869728
https://www.phoenixcontact.com/us/products/2869728
DIN rail connector for DIN rail mounting. Universal for TBUS housing. Goldplated contacts, 5-pos.
Power terminal block
Power terminal block - MINI MCR-SL-PTB - 2864134
https://www.phoenixcontact.com/us/products/2864134
MCR power terminal block for supplying several MINI Analog modules via the
DIN rail connector, with screw connection, maximum current consumption of up
to 2 A
Oct 27, 2022, 7:34 AM
Page 11 (13)
Signal conditioner - MINI MCR-SL-U-UI
2864053
https://www.phoenixcontact.com/us/products/2864053
Power supply unit
Power supply unit - MINI-SYS-PS-100-240AC/24DC/1.5 - 2866983
https://www.phoenixcontact.com/us/products/2866983
Please use the following item in new systems: 2904614
Primary-switched MINI POWER power supply for DIN rail mounting, input: 1phase, output: 24 V DC/1.5 A
Marking label
Marking label - MINI MCR-DKL-LABEL - 2810272
https://www.phoenixcontact.com/us/products/2810272
Label for extended marking of MINI MCR modules in connection with the MINI
MCR-DKL
Oct 27, 2022, 7:34 AM
Page 12 (13)
Signal conditioner - MINI MCR-SL-U-UI
2864053
https://www.phoenixcontact.com/us/products/2864053
Transparent cover
Transparent cover - MINI MCR DKL - 2308111
https://www.phoenixcontact.com/us/products/2308111
Fold up transparent cover for MINI MCR modules with additional labeling option
using insert strips and flat Zack marker strip 6.2 mm
Phoenix Contact 2022 © - all rights reserved
https://www.phoenixcontact.com
Phoenix Contact USA
586 Fulling Mill Road
Middletown, PA 17057, United States
(+717) 944-1300
info@phoenixcon.com
Oct 27, 2022, 7:34 AM
Page 13 (13)