https://www.phoenixcontact.com/gb/products/2864082
Frequency transducer - MINI MCR-SL-UI-F - 2864082
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Analog frequency transducers for converting analog standard signals into frequency signals or PWM signals,
configurable via DIP switch, with screw connection
Product Description
The 6.2 mm wide configurable analog frequency transducer MINI MCR-SL-UI-F... is used for converting analog standard signals into frequency
signals or into pulse width modulated (PWM) signals.
On the input side, there are the analog signals 0...20 mA, 4...20 mA, 0...10 mA, 2...10 mA, 0...10 V, 2...10 V, 0...5 V or 1...5 V
The DIP switches are accessible on the side of the housing and allow the following parameters to be configured:
– Input signal,
– Output signal,
– Output behavior in case the measuring range is exceeded or undershot and
– Filter type (for eliminating malfunctions in the input signal)
Voltage (19.2 V DC to 30 V DC) can be supplied through connection terminal blocks on the modules or in conjunction with the DIN rail connector.
Why buy this product
Power supply possible via the foot element (TBUS)
Error indication via diagnostic LED and analog signal
PWM output of 5 ... 95 %
Highly-compact analog-to-frequency transducer for electrical isolation, amplification, conversion, and filtering of standard signals to create
frequencies or PWM signals
Input and output signals can be configured via DIP switches
Configurable interference filter
3-way isolation
Key Commercial Data
Packing unit
1 STK
GTIN
GTIN
4046356046435
Weight per Piece (excluding packing)
108.300 g
Custom tariff number
85437090
Country of origin
Germany
04/16/2018 Page 1 / 8
https://www.phoenixcontact.com/gb/products/2864082
Frequency transducer - MINI MCR-SL-UI-F - 2864082
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
6.2 mm
Height
93.1 mm
Depth
102.5 mm
Ambient conditions
Ambient temperature (operation)
-20 °C ... 65 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Maximum altitude
≤ 2000 m
Input data
Configurable/programmable
Yes
Current input signal
0 mA ... 20 mA
4 mA ... 20 mA
0 mA ... 10 mA
2 mA ... 10 mA
Input resistance current input
approx. 50 Ω
Voltage input signal
0 V ... 5 V
1 V ... 5 V
0 V ... 10 V
2 V ... 10 V
Input resistance of voltage input
approx. 110 kΩ
Output data
Number of outputs
1
Frequency output
0 Hz ... 10 kHz
0 Hz ... 5 kHz
0 Hz ... 2.5 kHz
0 Hz ... 1 kHz
0 Hz ... 500 Hz
0 Hz ... 250 Hz
0 Hz ... 100 Hz
0 Hz ... 50 Hz
Load min.
4 mA ≤ (UL / RL) ≤ 20 mA
Output signal PWM
7.8 kHz (10 bit)
3.9 kHz (10 bit)
1.9 kHz (12 bit)
977 Hz (12 bit)
488 Hz (14 bit)
04/16/2018 Page 2 / 8
https://www.phoenixcontact.com/gb/products/2864082
Frequency transducer - MINI MCR-SL-UI-F - 2864082
Technical data
Output data
244 Hz (14 bit)
122 Hz (16 bit)
61 Hz (16 bit)
Load min.
12 mA ≤ (UL / RL) ≤ 20 mA
Maximum switching voltage
30 V
Load current maximum
20 mA
Overrange/underrange
Can be set (via DIP switch)
Type of protection
Short-circuit protection, polarity reversal protection
Step response (0–99%)
< 15 ms (+ (1/f) smallest filter)
< 1 s (+ (1/f) largest filter)
Power supply
Nominal supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2
1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the
supply voltage. It can be snapped onto a 35 mm DIN rail according to
EN 60715))
Max. current consumption
< 10 mA (at 24 V DC)
Power consumption
< 200 mW
Connection data
Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section AWG min.
26
Conductor cross section AWG max.
12
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Stripping length
12 mm
Screw thread
M3
General
No. of channels
1
Maximum transmission error
≤ 0.1 % (> 7 kHz ≤ 0.2 %)
Maximum temperature coefficient
< 0.02 %/K
Temperature coefficient, typical
< 0.02 %/K
Electrical isolation
Basic insulation according to EN 61010
Overvoltage category
II
Degree of pollution
2
Rated insulation voltage
30 V AC
Test voltage, input/output/supply
1.5 kV (50 Hz, 1 min.)
Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
04/16/2018 Page 3 / 8
https://www.phoenixcontact.com/gb/products/2864082
Frequency transducer - MINI MCR-SL-UI-F - 2864082
Technical data
General
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be
minimal deviations.
Color
green
Housing material
PBT
Mounting position
any
Conformance
CE-compliant
ATEX
II 3 G Ex nA IIC T4 Gc X
UL, USA/Canada
UL 508 Recognized
Class I, Div. 2, Groups A, B, C, D T4
Certificate of classification
DNV GL TAA00000N1
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 2
EMC data
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Typical deviation from the measuring range final value
2%
Designation
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Typical deviation from the measuring range final value
2%
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Typical deviation from the measuring range final value
2%
Standards and Regulations
Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Connection in acc. with standard
CUL
Standards/regulations
EN 61000-4-2
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Electrical isolation
Basic insulation according to EN 61010
Conformance
CE-compliant
ATEX
II 3 G Ex nA IIC T4 Gc X
UL, USA/Canada
UL 508 Recognized
Class I, Div. 2, Groups A, B, C, D T4
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 2 HL 1 - HL 2 HL 1 - HL 2
04/16/2018 Page 4 / 8
https://www.phoenixcontact.com/gb/products/2864082
Frequency transducer - MINI MCR-SL-UI-F - 2864082
Technical data
Standards and Regulations
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 2 HL 1 - HL 2 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 2 HL 1 - HL 2 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R26
HL 1 - HL 2 HL 1 - HL 2 HL 1 - HL 2
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”,
Category “Manufacturer's declaration”
Drawings
Block diagram
Diagram
Frequency output
T
T
T
T
T
T
Variable frequency / Period duration T
PWM output (pulse width modulation)
T
T
T
T
T
T
Variable pulse-pause ratio / Fixed period duration T
Dimensional drawing
93,1
102,5
6,2
Classifications
eCl@ss
eCl@ss 4.0
27210120
eCl@ss 4.1
27210120
eCl@ss 5.0
27210120
eCl@ss 5.1
27210120
eCl@ss 6.0
27210120
04/16/2018 Page 5 / 8
https://www.phoenixcontact.com/gb/products/2864082
Frequency transducer - MINI MCR-SL-UI-F - 2864082
Classifications
eCl@ss
eCl@ss 7.0
27210120
eCl@ss 8.0
27210120
eCl@ss 9.0
27210120
ETIM
ETIM 4.0
EC002653
ETIM 5.0
EC002653
ETIM 6.0
EC002653
UNSPSC
UNSPSC 6.01
30211506
UNSPSC 7.0901
39121008
UNSPSC 11
39121008
UNSPSC 12.01
39121008
UNSPSC 13.2
39121008
Approvals
Approvals
Approvals
UL Recognized / cUL Recognized / BV / EAC / DNV GL / cULus Recognized
Ex Approvals
UL Listed / cUL Listed / ATEX / cULus Listed
Approval details
UL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 238705
cUL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 238705
BV
http://www.veristar.com/portal/veristarinfo/generalinfo/
approved/approvedProducts/equipmentAndMaterials
39933/A0_BV
04/16/2018 Page 6 / 8
https://www.phoenixcontact.com/gb/products/2864082
Frequency transducer - MINI MCR-SL-UI-F - 2864082
Approvals
EAC
EAC-Zulassung
http://exchange.dnv.com/tari/
TAA00000N1
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
DNV GL
cULus Recognized
Accessories
Accessories
DIN rail connector
DIN rail bus connectors - ME 6,2 TBUS-2 1,5/5-ST-3,81 GN - 2869728
DIN rail connector for DIN rail mounting. Universal for TBUS housing. Gold-plated contacts, 5-pos.
Marking material
Transparent cover - MINI MCR DKL - 2308111
Fold up transparent cover for MINI MCR modules with additional labeling option using insert strips and flat Zack
marker strip 6.2 mm
Marking label - MINI MCR-DKL-LABEL - 2810272
Label for extended marking of MINI MCR modules in connection with the MINI MCR-DKL
Power module
04/16/2018 Page 7 / 8
https://www.phoenixcontact.com/gb/products/2864082
Frequency transducer - MINI MCR-SL-UI-F - 2864082
Accessories
Power terminal block - MINI MCR-SL-PTB - 2864134
MCR power terminal block for supplying several MINI Analog modules via the DIN rail connector, with screw
connection, maximum current consumption of up to 2 A
Power terminal block - MINI MCR-SL-PTB-SP - 2864147
MCR power terminal block for supplying several MINI Analog modules via the DIN rail connector, with spring-cage
connection, maximum current consumption of up to 2 A
Power supply
Power supply unit - MINI-SYS-PS-100-240AC/24DC/1.5 - 2866983
Primary-switched MINI POWER supply for DIN rail mounting, input: 1-phase, output: 24 V DC/1.5 A
Power supply unit - MINI-PS-100-240AC/24DC/1.5/EX - 2866653
Primary-switched power supply MINI POWER for DIN rail mounting, input: 1-phase, output: 24 V DC/1,5 A, for the
potentially explosive area
System adapter
System adapter - MINI MCR-SL-V8-FLK 16-A - 2811268
Eight MINI analog signal converters with screw connection method can be connected to a control system using a
system adapter and system cabling with a minimum of wiring and very low error risk.
Phoenix Contact 2018 © - all rights reserved
http://www.phoenixcontact.com
04/16/2018 Page 8 / 8