Temperature measuring transducer - MINI MCR-SLPT100-UI-200-SP-NC
2864202
https://www.phoenixcontact.com/us/products/2864202
Please be informed that the data shown in this PDF document is generated from our Online Catalog. Please find the complete data in the user
documentation. Our General Terms of Use for Downloads are valid.
MCR temperature transducer, configurable, for Pt 100 temperature sensors, with spring-cage
connection, not configured. Replacement part: 2902052 MINI MCR-2-RTD-UI-PT.
Your advantages
• Power supply possible via the foot element (TBUS)
• Optimized temperature measuring range of -50°C to +200°C for increased accuracy
• For 2-, 3-, 4-conductor Pt 100 sensors in accordance with IEC 60751
• Error indication via diagnostic LED and analog signal
• Input and output signals can be configured via DIP switches
• Highly-compact temperature transducer for electrical isolation, conversion, amplification, and filtering of
• Pt 100 signals to create standard signals
• 3-way isolation
Commercial Data
Item number
2864202
Packing unit
1 pc
Minimum order quantity
1 pc
Note
Made to Order (non-returnable)
Sales Key
C01
Product Key
CK1221
Catalog Page
Page 104 (C-7-2015)
GTIN
4046356046466
Weight per Piece (including packing)
91.7 g
Weight per Piece (excluding packing)
59.9 g
Customs tariff number
85437090
Country of origin
DE
Oct 27, 2022, 7:33 AM
Page 1 (9)
Temperature measuring transducer - MINI MCR-SLPT100-UI-200-SP-NC
2864202
https://www.phoenixcontact.com/us/products/2864202
Technical Data
Product properties
Product type
Temperature transmitter
Insulation characteristics
Overvoltage category
II
Pollution degree
2
Electrical properties
Rated insulation voltage
50 V AC/DC
Electrical isolation
Basic insulation in accordance with EN 61010
Maximum power dissipation for nominal condition
235.5 mW
Test voltage, input/output/supply
1.5 kV AC (50 Hz, 60 s)
Protective circuit
Transient protection
Step response (0–99%)
< 200 ms
Maximum temperature coefficient
< 0.02 %/K
Transmission error in the set measuring range
((50 K / Δ Temp)+ 0.05)%
Transmission error in the full measuring range
≤ 0,25 %
Supply
Nominal supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (The DIN rail connector (ME 6,2 TBUS-2
1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the
supply voltage. It can be snapped onto a 35 mm DIN rail in
accordance with EN 60715)
Max. current consumption
< 21 mA (at 24 V DC)
Power consumption
< 500 mW
Input data
Signal:
Number of inputs
1
Input signal
Temperature
Measurement
Sensor types (RTD) that can be used
Pt 100 (IEC 60751/EN 60751)
Temperature measuring range
-50 °C ... 200 °C
Temperature measuring range
min. 50 K
Sensor type:
-50 °C ... 200 °C (configurable)
Sensor input current
1 mA (constant)
Max. permissible overall conductor resistance
10 Ω (Per cable)
Connection technology
2-, 3-, 4-conductor
Output data
Oct 27, 2022, 7:33 AM
Page 2 (9)
Temperature measuring transducer - MINI MCR-SLPT100-UI-200-SP-NC
2864202
https://www.phoenixcontact.com/us/products/2864202
Signal:
Number of outputs
1
Configurable/programmable
Yes
Voltage output signal
0 V ... 10 V
10 V ... 0 V
0 V ... 5 V
1 V ... 5 V
Max. voltage output signal
approx. 12.5 V
Non-load voltage
approx. 12.5 V
Current output signal
0 mA ... 20 mA
4 mA ... 20 mA
20 mA ... 0 mA
20 mA ... 4 mA
Max. current output signal
23 mA
Short-circuit current
approx. 10 mA
Load/output load voltage output
> 10 kΩ
Load/output load current output
< 500 Ω (at 20 mA)
Ripple
< 20 mVPP (at 500 Ω)
< 20 mVPP (at 10 kΩ)
Connection data
Connection method
Spring-cage connection
Stripping length
8 mm
Conductor cross section solid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 12
Dimensions
Dimensional drawing
Width
6.2 mm
Height
93.1 mm
Depth
102.5 mm
Material specifications
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 2
Oct 27, 2022, 7:33 AM
Page 3 (9)
Temperature measuring transducer - MINI MCR-SLPT100-UI-200-SP-NC
2864202
https://www.phoenixcontact.com/us/products/2864202
Housing material
PBT
Environmental and real-life conditions
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-20 °C ... 65 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (non-condensing)
Approval data
CE
Certificate
CE-compliant
ATEX
Identification
II 3 G Ex nA IIC T4 Gc X
UL, USA / Canada
Identification
UL 508 Recognized
Class I, Div. 2, Groups A, B, C, D T5
GL
Identification
GL EMC 2 D
EMC data
Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Noise immunity
EN 61000-6-2
Note
When being exposed to interference, there may be minimal
deviations.
Electrostatic discharge
Standards/regulations
EN 61000-4-2
Electrostatic discharge
Comments
Safety measures must be taken to prevent electrostatic
discharge.
Electromagnetic HF field
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Typical deviation from the measuring range final value
10 %
Fast transients (burst)
Designation
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Typical deviation from the measuring range final value
10 %
Oct 27, 2022, 7:33 AM
Page 4 (9)
Temperature measuring transducer - MINI MCR-SLPT100-UI-200-SP-NC
2864202
https://www.phoenixcontact.com/us/products/2864202
Surge current load (surge)
Standards/regulations
EN 61000-4-5
Surge current load (surge)
Comments
Criterion B
Conducted interference
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Typical deviation from the measuring range final value
10 %
Standards and regulations
Electrical isolation
Basic insulation in accordance with EN 61010
Mounting
Mounting type
DIN rail mounting
Mounting position
any
Oct 27, 2022, 7:33 AM
Page 5 (9)
Temperature measuring transducer - MINI MCR-SLPT100-UI-200-SP-NC
2864202
https://www.phoenixcontact.com/us/products/2864202
Drawings
Dimensional drawing
6,2
102,5
93,1
Oct 27, 2022, 7:33 AM
Page 6 (9)
Temperature measuring transducer - MINI MCR-SLPT100-UI-200-SP-NC
2864202
https://www.phoenixcontact.com/us/products/2864202
Block diagram
IN
Sensor / Field
PT 100
ϑ
ϑ
OUT
1
ϑ
1
2
2
3
3
4
OUT U,I
active
GND 1
PLC / DCS
5 +
6 –
+24V
4
GND 2
5
passive
6
7 +
8 –
+24V
GND 2
Oct 27, 2022, 7:33 AM
Page 7 (9)
Temperature measuring transducer - MINI MCR-SLPT100-UI-200-SP-NC
2864202
https://www.phoenixcontact.com/us/products/2864202
Classifications
ECLASS
ECLASS-9.0
27210129
ECLASS-10.0.1
27210129
ECLASS-11.0
27210129
ETIM
ETIM 7.0
EC002919
Oct 27, 2022, 7:33 AM
Page 8 (9)
Temperature measuring transducer - MINI MCR-SLPT100-UI-200-SP-NC
2864202
https://www.phoenixcontact.com/us/products/2864202
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the
manufacturer’s declaration available under “Downloads”
Phoenix Contact 2022 © - all rights reserved
https://www.phoenixcontact.com
Phoenix Contact USA
586 Fulling Mill Road
Middletown, PA 17057, United States
(+717) 944-1300
info@phoenixcon.com
Oct 27, 2022, 7:33 AM