https://www.phoenixcontact.com/us/products/2864574
Temperature measuring transducer - MCR-FL-T-LP-I-EX - 2864574
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
MCR head-mounted temperature transducers: Programmable loop-powered temperature transducers.
Resistance thermometers, thermocouples, resistance-type sensors and voltage sensors.
Product Features
■
■
■
■
■
■
■
■
Input for resistance thermometers, thermocouples, and linear mV signals, Ex ia IIC
Configuration via software
Can be installed in zone 1
2-way electrical isolation
Single-channel
Loop-powered
HART-compatible (MCR-FL-TS-LP-I-EX)
4
20 mA/20
4 mA output
Key Commercial Data
Packing unit
1 pc
Weight per Piece (excluding packing)
106.6 g
Custom tariff number
85437090
Country of origin
Germany
Technical data
Dimensions
Width
12.5 mm
Height
99 mm
Depth
114.5 mm
04/08/2016 Page 1 / 5
https://www.phoenixcontact.com/us/products/2864574
Temperature measuring transducer - MCR-FL-T-LP-I-EX - 2864574
Technical data
Ambient conditions
Degree of protection
IP20
Input data
Configurable/programmable
Yes, programmable
Sensor types (RTD) that can be used
Pt, Ni (100, 500, 1000); min. measurement range 10 K
Sensor types that can be used (TC)
B, C, D, E, J, K, L, N, R, S, T, U; min. measurement range 50 K/500 K
Connection method
2, 3, 4-wire
Input signal range
10 Ω ... 400 Ω (min. measurement range 10 Ω)
10 Ω ... 2000 Ω (min. measurement range 100 Ω)
-10 mV ... 100 mV (min. measurement range 5 mV)
Output data
Signal output
Current output
Current output signal
4 mA ... 20 mA
20 mA ... 4 mA
Max. current output signal
≤ 23 mA
Output current with short-circuit
≤ 3.6 mA or ≥ 21 mA (adjustable, not for thermocouples)
Output current with wire break
≤ 3.6 mA or ≥ 21 mA (adjustable)
Output current range with overrange/underrange
3.8 mA ... 20.5 mA
Load/output load current output
≤ 520 Ω (At UV = 24 V; Usupply - 12 V / 0.023 A)
Power supply
Designation
Loop-powered
Supply voltage range
12 V DC ... 30 V DC
Max. current consumption
< 3.5 mA
Connection data
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
14
Stripping length
8 mm
Screw thread
M3
Connection method
Screw connection
Tightening torque, min
0.5 Nm
Tightening torque max
0.6 Nm
General
04/08/2016 Page 2 / 5
https://www.phoenixcontact.com/us/products/2864574
Temperature measuring transducer - MCR-FL-T-LP-I-EX - 2864574
Technical data
General
Step response (10-90%)
很抱歉,暂时无法提供与“2864574”相匹配的价格&库存,您可以联系我们找货
免费人工找货