MINI MCR-SL-...CP-I-I... One- and two-channel passive isolators INTERFACE Data sheet 101948_en_01 1 © PHOENIX CONTACT 2010-11-16 Description MINI MCR-SL-...CP-I-I(-SP) passive isolators are used for electrical isolation and filtering of analog 0(4)...20 mA standard current signals without additional supply voltage. Features – – – – One- or two-channel passive isolators Input and output signal range 0...20 mA or 4...20 mA Approval for Ex-zone 2 (nA) Screw or spring-cage connection can be provided Attention: Correct usage in potentially explosive areas The module is a category 3 item of electrical equipment. It is absolutely vital to follow the instructions provided here during installation and observe the information in the "Safety regulations and installation notes". Make sure you always use the latest documentation. It can be downloaded from the product at www.phoenixcontact.net/catalog. This data sheet is valid for all products listed on the following page: MINI MCR-SL-...CP-I-I... 2 Table of contents 1 Description .............................................................................................................................. 1 2 Table of contents ..................................................................................................................... 2 3 Ordering data .......................................................................................................................... 3 4 Technical data ......................................................................................................................... 3 5 Safety regulations and installation notes.................................................................................. 5 5.1 Installation notes ................................................................................................................. 5 5.2 Installation in the Ex area (zone 2)............................................................................................ 5 6 Installation ............................................................................................................................... 6 6.1 Connection notes ................................................................................................................ 6 6.2 Structure ........................................................................................................................... 6 6.3 Block diagram ..................................................................................................................... 6 6.4 Power supply ...................................................................................................................... 6 6.5 Assembly........................................................................................................................... 7 6.6 Connecting the wires ............................................................................................................ 7 7 Connection/application example ............................................................................................. 8 101948_en_01 PHOENIX CONTACT 2 MINI MCR-SL-...CP-I-I... 3 Ordering data Description Type Order No. Pcs. / Pkt. MCR loop-powered isolator, 1-channel, for the electrical isolation of current signals without auxiliary power, with screw connection MINI MCR-SL-1CP-I-I 2864419 1 MCR passive isolator, 1-channel, for the electrical isolation of current sig- MINI MCR-SL-1CP-I-I-SP nals without auxiliary power, with spring-cage connection 2864749 1 MCR passive isolator, 2-channel, for the electrical isolation of current signals without auxiliary power, with screw connection MINI MCR-SL-2CP-I-I 2864655 1 MCR passive isolator, 2-channel, for the electrical isolation of current signals without auxiliary power, with spring-cage connection MINI MCR-SL-2CP-I-I-SP 2864781 1 Accessories Type Order No. Pcs. / Pkt. DIN rail connector (TBUS), 5-pos., for bridging the supply voltage, can be snapped onto NS 35/... DIN rails according to EN 60715 ME 6,2 TBUS-2 1,5/5-ST-3,81 GN 2869728 10 Eight MINI analog signal converters with screw connection method can be connected to a control system using a system adapter and system cabling with a minimum of wiring and very low error risk. MINI MCR-SL-V8-FLK 16-A 2811268 1 Label for extended marking of MINI MCR modules in connection with the MINI MCR-DKL MINI MCR-DKL-LABEL 2810272 10 Fold up transparent cover for MINI MCR modules with additional labeling option using insert strips and flat Zack marker strip 6.2 mm MINI MCR DKL 2308111 10 4 Technical data Input Description of the input Current input Configurable/programmable No Max. voltage input signal 18 V Current input signal 0 mA ... 20 mA 4 mA ... 20 mA Max. current input signal 40 mA Response current Approx. 190 µA Input voltage limitation 18 V Voltage dissipation 1.7 V (at I = 20 mA) Output Output description Current output Current output signal 0 mA ... 20 mA 4 mA ... 20 mA Configurable/programmable No Ripple < 10 mVrms (at 600 Ω) Load/output load current output < 600 Ω (at I = 20 mA output signal) Supply Supply voltage range 101948_en_01 (no separate supply voltage necessary) PHOENIX CONTACT 3 MINI MCR-SL-...CP-I-I... General data Limit frequency (3 dB) 75 Hz Maximum transmission error ≤ 0.1 % (of final value) Maximum temperature coefficient ≤ 0.002 %/K (of measured value / 100 Ω load) Step response (10-90%) 5 ms (At 600 Ω load) Electrical isolation Basic insulation according to EN 61010 Surge voltage category II Mounting position Any Degree of protection IP20 Pollution degree 2 Rated insulation voltage 50 V AC/DC Dimensions W / H / D 6.2 mm / 93.1 mm / 102.5 mm Type of housing PBT green Connection data Screw connection Spring-cage conn. Conductor cross section, solid 0.14 mm² ... 2.5 mm² 0.2 mm² ... 2.5 mm² Conductor cross section, stranded 0.2 mm² ... 2.5 mm² 0.2 mm² ... 2.5 mm² Stripping length 12 mm 8 mm Ambient conditions Ambient temperature (operation) -20 °C ... 65 °C Ambient temperature (storage/transport) -40 °C ... 85 °C Conformance with EMC Directive 2004/108/EC Noise immunity according to EN 61000-6-2 Noise emission according to EN 61000-6-4 Conformance / approvals Conformance CE-compliant ATEX  II 3 G Ex nA II T6 X UL, USA / Canada UL 508 Recognized Shipbuilding GL EMC 2 D 101948_en_01 PHOENIX CONTACT 4 MINI MCR-SL-...CP-I-I... 5 Safety regulations and installation notes 5.1 Installation notes – – – – – The device is designed for installation in zone 2 potentially explosive areas. Installation, operation, and maintenance may only be carried out by qualified electricians. Follow the installation instructions described. When installing and operating the device, the applicable regulations and safety directives (including national safety directives), as well as general technical regulations, must be observed. The technical data is provided in this package slip and on the certificates (conformity assessment, additional approvals where applicable). It is not permissible to open or modify the device. Do not repair the device yourself but replace it with an equivalent device. Repairs may only be carried out by the manufacturer. The manufacturer is not liable for damage resulting from violation. The IP20 degree of protection (EN 60529) of the device is intended for use in a clean and dry environment. Do not subject the device to any load that exceeds the described limits. The device is not designed for use in atmospheres with a danger of dust explosions. 101948_en_01 5.2 – – – – – – Installation in the Ex area (zone 2) Observe the specified conditions for use in potentially explosive areas. The device must be installed in a housing (control or distributor box) which meets the requirements of EN 6007915 and provides at least IP54 (EN 60529) degree of protection. During installation and when connecting the supply and signal circuits, observe the requirements of EN 6007914. Devices may only be connected to circuits in zone 2 if they are suitable for operation in Ex zone 2 and for the prevailing conditions at the place of use. In potentially explosive areas, terminals may only be snapped onto or off the DIN rail connector and wires may only be connected or disconnected when the power is switched off. The device must be stopped and immediately removed from the Ex area if it is damaged, has been subjected to an impermissible load, has been stored incorrectly, or if it malfunctions. You can download the latest documents for these devices from www.phoenixcontact.net/catalog. PHOENIX CONTACT 5 MINI MCR-SL-...CP-I-I... 6.3 6 Installation 6.1 Connection notes OUT IN Attention: Electrostatic discharge! The device contains components that can be damaged or destroyed by electrostatic discharge. When handling the device, observe the necessary safety precautions against electrostatic discharge (ESD) according to EN 613405-1 and EN 61340-5-2. 6.2 Block diagram Structure (+) 0-20mA 1 2 (–) GND = 5 (+) 0-20mA 6 (–) GND (+) 0-20mA 1 2 (–) GND = 5 (+) 0-20mA 6 (–) GND (+) 0-20mA 3 4 (–) GND Figure 2 3 6.4 1 4 = 7 (+) 0-20mA 8 (–) GND Block diagram Power supply ATTENTION: -I P-I or -2C 5 5 lat so -SL 4 6 eI CR 28 6 t M siv as A outpu NI .: P MI d.-No el .20m mA le . nn 0 Or ha 0(4). at 2 ll scatput C u 2 0 W f f ou 60 1% o 0 mA min. 49°F , ut: 2 , 1 ..+1 < 0 at z . / O d: In . Loa rror: 2 V 50 H / -4° < x , E C ) Ma sm. rop: ,5kV +65° DC 1 .. 5V n (1)I . 1 Tra age D e: 20°. In max lt ag (byD 1 Vo volt p.: +1 GN t m ) s C D Te . Te 1 ) 5V b IN - 2 I(2 . 1 In max + 1 Am 5 (1) t I Ou 2 D GN (2) t I 4 D GN 6 Ou X XX XX XX CeriaEl No. X 5 T OU 6- 7 + UT 2 O IN -4 8- ww in w. ter fac e.p Never connect the supply voltage directly to the DIN rail connector. It is not permitted to draw power from the DIN rail connector or from individual modules. Supply via the module (byD 3 GN +3 2 2 ho en o ixc nta ct. co m 7 The MINI passive isolators do not need a separate power supply. The necessary power is supplied by a current loop on the input side, e.g. in the form of a transmitter (see the section titled "Connection/Application example"). S Figure 1 1. 2. 3. 4. 5. 6. 7. Structure However, MINI passive isolators can be snapped onto a DIN rail connector – no electrically conductive connection is established. This means that it is not necessary to disconnect an existing connection involving DIN rail connector elements. Input: Standard signals (channel 1) Input: Standard signals (channel 2) Cover Groove for ZBF 6 zack marker strip Output: Standard signals (channel 1) Output: Standard signals (channel 2) Universal snap-on foot for EN DIN rails 101948_en_01 PHOENIX CONTACT 6 MINI MCR-SL-...CP-I-I... 6.5 Assembly Screw connection: B A B A D www.interface.phoenixcontact.com C E Figure 4 • • Figure 3 – 6.6 Insert the wire into the corresponding connection terminal block. Use a screwdriver to tighten the screw in the opening above the connection terminal block. Spring-cage connection: Mount the module on a 35 mm DIN rail according to EN 60715. When using the DIN rail connector, first place it into the DIN rail (see A – C). It is used to bridge the power supply. It is also absolutely vital that you snap the module and the DIN rail connector into position in the correct direction: the snap-on foot should be at the bottom and the connector on the left. A B Connecting the wires The MINI MCR-SL-1CP-I-I... is available with two types of connection: – Screw terminal blocks (MINI MCR-SL-1CP-I-I) – Spring-cage terminal blocks (MINI MCR-SL-1CP-I-I-SP) Figure 5 • • 101948_en_01 Screw connection www.interface.phoenixcontact.com – Mounting and removing X XXX XXX o. X al N Seri X XXX XXX o. X al N Seri Spring-cage connection Insert a screwdriver into the opening above the connection terminal block. Insert the wire into the corresponding connection terminal block. PHOENIX CONTACT 7 MINI MCR-SL-...CP-I-I... 7 Connection/application example When using passive isolators, you must make sure that the current sourcing voltage of the measuring transducer UB is sufficient to drive the maximum current of 20 mA via the passive isolator with a voltage drop UV = 1.7 V and load RB. This means: UB ≥ UE = 1.7 V + 20 mA x RB UB UV = 1,7 V I UE I I I RB MINI MCR-SL-1CP-I-I Figure 6 101948_en_01 Power supply PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49-(0) 5235-3-00 PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300 www.phoenixcontact.com 8
2864655 价格&库存

很抱歉,暂时无法提供与“2864655”相匹配的价格&库存,您可以联系我们找货

免费人工找货
2864655
    •  国内价格 香港价格
    • 1+4023.731731+499.14206

    库存:2