https://www.phoenixcontact.com/us/products/2864723
Signal conditioner - MINI MCR-SL-I-I-SP - 2864723
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
MCR 3-way isolating amplifier, for electrical isolation of analog signals, with spring-cage connection, input signal:
0 ... 20 mA / 4 ... 20 mA, output signal: 0 ... 20 mA / 4 ... 20 mA
Why buy this product
Power supply possible via the foot element (TBUS)
Entry-level alternative to configurable signal conditioners
Low power consumption
3-way isolation
Highly-compact isolating amplifier for electrical isolation, conversion, amplification, and filtering of standard analog signals
Fixed signal combinations
Key Commercial Data
Packing unit
1 STK
GTIN
GTIN
4017918974923
Weight per Piece (excluding packing)
63.800 g
Custom tariff number
85437090
Country of origin
Germany
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
6.2 mm
07/21/2018 Page 1 / 8
https://www.phoenixcontact.com/us/products/2864723
Signal conditioner - MINI MCR-SL-I-I-SP - 2864723
Technical data
Dimensions
Height
93.1 mm
Depth
102.5 mm
Ambient conditions
Ambient temperature (operation)
-20 °C ... 65 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Input data
Number of inputs
1
Configurable/programmable
no
Current input signal
0 mA ... 20 mA
4 mA ... 20 mA
Max. input current
50 mA
Input resistance current input
approx. 50 Ω
Output data
Number of outputs
1
Configurable/programmable
no
Current output signal
0 mA ... 20 mA
4 mA ... 20 mA
Max. output current
28 mA
Load/output load current output
< 500 Ω (at 20 mA)
Ripple
< 20 mVPP (at 500 Ω)
Power supply
Nominal supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2
1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the supply
voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
Max. current consumption
< 20 mA
Power consumption
< 450 mW
Connection data
Connection method
Spring-cage connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Stripping length
8 mm
07/21/2018 Page 2 / 8
https://www.phoenixcontact.com/us/products/2864723
Signal conditioner - MINI MCR-SL-I-I-SP - 2864723
Technical data
General
No. of channels
1
Maximum transmission error
≤ 0.1 % (of final value)
Maximum temperature coefficient
< 0.01 %/K
Temperature coefficient, typical
< 0.002 %/K
Limit frequency (3 dB)
approx. 100 Hz
Step response (10-90%)
approx. 3.2 ms
Protective circuit
Transient protection
Electrical isolation
Basic insulation according to EN 61010
Overvoltage category
II
Degree of pollution
2
Rated insulation voltage
50 V AC/DC
Test voltage, input/output/supply
1.5 kV (50 Hz, 1 min.)
Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be minimal
deviations.
Color
green
Housing material
PBT
Mounting position
any
Assembly instructions
The T connector can be used to bridge the supply voltage. It can be
snapped onto a 35 mm DIN rail according to EN 60715.
Conformance
CE-compliant
ATEX
II 3 G Ex nA IIC T4 Gc X
UL, USA/Canada
UL 508 Recognized
Class I, Div. 2, Groups A, B, C, D T5
GL
GL EMC 2 D
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 2
EMC data
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Typical deviation from the measuring range final value
10 %
Designation
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Typical deviation from the measuring range final value
10 %
Designation
Conducted interferences
07/21/2018 Page 3 / 8
https://www.phoenixcontact.com/us/products/2864723
Signal conditioner - MINI MCR-SL-I-I-SP - 2864723
Technical data
EMC data
Standards/regulations
EN 61000-4-6
Typical deviation from the measuring range final value
10 %
Standards and Regulations
Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Connection in acc. with standard
CUL
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
EN 61000-4-4
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Electrical isolation
Basic insulation according to EN 61010
Conformance
CE-compliant
ATEX
II 3 G Ex nA IIC T4 Gc X
UL, USA/Canada
UL 508 Recognized
Class I, Div. 2, Groups A, B, C, D T5
GL
GL EMC 2 D
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 2 HL 1 - HL 2 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 2 HL 1 - HL 2 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 2 HL 1 - HL 2 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R26
HL 1 - HL 2 HL 1 - HL 2 HL 1 - HL 2
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category
“Manufacturer's declaration”
Drawings
07/21/2018 Page 4 / 8
https://www.phoenixcontact.com/us/products/2864723
Signal conditioner - MINI MCR-SL-I-I-SP - 2864723
Block diagram
Dimensional drawing
93,1
1
+ 1
IN I
OUT I
5 +
5
active
4-wire
GND
2
– 2
+ 3
– 4
GND 1
passive
GND 2
6 –
+24V
+24V
GND 3
6,2
PLC / DCS
GND 3
6
7 +
102,5
OUT I
US
OUT
IN
Sensor / Field
8 –
+24V
GND 3
Zone 2
Div. 2
Classifications
eCl@ss
eCl@ss 4.0
27210120
eCl@ss 4.1
27210120
eCl@ss 5.0
27210120
eCl@ss 7.0
27210120
eCl@ss 8.0
27210120
eCl@ss 9.0
27210120
ETIM
ETIM 4.0
EC002653
ETIM 5.0
EC002653
ETIM 6.0
EC002653
UNSPSC
UNSPSC 6.01
30211506
UNSPSC 7.0901
39121008
UNSPSC 11
39121008
UNSPSC 12.01
39121008
UNSPSC 13.2
39121008
Approvals
Approvals
Approvals
UL Recognized / cUL Recognized / GL / BV / cULus Recognized
07/21/2018 Page 5 / 8
https://www.phoenixcontact.com/us/products/2864723
Signal conditioner - MINI MCR-SL-I-I-SP - 2864723
Approvals
Ex Approvals
UL Listed / cUL Listed / ATEX / cULus Listed
Approval details
UL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 238705
cUL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 238705
GL
http://exchange.dnv.com/tari/
24916-05 HH
BV
http://www.veristar.com/portal/veristarinfo/generalinfo/
approved/approvedProducts/equipmentAndMaterials
39933/A0_BV
cULus Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
Accessories
Accessories
DIN rail connector
DIN rail bus connectors - ME 6,2 TBUS-2 1,5/5-ST-3,81 GN - 2869728
DIN rail connector for DIN rail mounting. Universal for TBUS housing. Gold-plated contacts, 5-pos.
Marking material
07/21/2018 Page 6 / 8
https://www.phoenixcontact.com/us/products/2864723
Signal conditioner - MINI MCR-SL-I-I-SP - 2864723
Accessories
Transparent cover - MINI MCR DKL - 2308111
Fold up transparent cover for MINI MCR modules with additional labeling option using insert strips and flat Zack marker
strip 6.2 mm
Marking label - MINI MCR-DKL-LABEL - 2810272
Label for extended marking of MINI MCR modules in connection with the MINI MCR-DKL
Power module
Power terminal block - MINI MCR-SL-PTB - 2864134
MCR power terminal block for supplying several MINI Analog modules via the DIN rail connector, with screw connection,
maximum current consumption of up to 2 A
Power terminal block - MINI MCR-SL-PTB-SP - 2864147
MCR power terminal block for supplying several MINI Analog modules via the DIN rail connector, with spring-cage
connection, maximum current consumption of up to 2 A
Power supply
Power supply unit - MINI-SYS-PS-100-240AC/24DC/1.5 - 2866983
Primary-switched MINI POWER supply for DIN rail mounting, input: 1-phase, output: 24 V DC/1.5 A
07/21/2018 Page 7 / 8
https://www.phoenixcontact.com/us/products/2864723
Signal conditioner - MINI MCR-SL-I-I-SP - 2864723
Accessories
Power supply unit - MINI-PS-100-240AC/24DC/1.5/EX - 2866653
Primary-switched power supply MINI POWER for DIN rail mounting, input: 1-phase, output: 24 V DC/1,5 A, for the
potentially explosive area
Phoenix Contact 2018 © - all rights reserved
http://www.phoenixcontact.com
07/21/2018 Page 8 / 8