https://www.phoenixcontact.com/gb/products/2865007
Signal conditioner - MINI MCR-SL-U-UI-NC - 2865007
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
MCR 3-way isolation amplifier, with configurable input/output, for electrical isolation and conversion of analog
signals up to 30 V, with screw connection, standard configuration
Product Description
The 6.2 mm wide configurable 3-way isolating amplifier MINI MCR-SL-U-UI-... is used for electrical isolation, conversion, amplification and filtering
of standard signals.
The signals 0...24 V and 0...30 V can be processed on the input side.
The analog signals 0...20 mA, 4...20 mA, 0...10 V, 2...10 V, 0...5 V or 1..5 V are available electrically isolated on the output side.
The DIP switches, which can be accessed on the side of the housing, can be used to configure the input and output signal ranges.
Power (19.2 V DC to 30 V DC) can be supplied through connection terminal blocks on the modules or in conjunction with the DIN rail connector.
Why buy this product
Power supply possible via the foot element (TBUS)
Low power consumption
Highly-compact isolating amplifier for electrical isolation, conversion, amplification, and filtering of 24 V or
30 V DC signals to create standard analog signals
Up to 12 signal combinations can be configured using DIP switches
3-way isolation
Key Commercial Data
Packing unit
1 STK
GTIN
GTIN
4046356046565
Weight per Piece (excluding packing)
65.800 g
Custom tariff number
85437090
Country of origin
Germany
Technical data
Note
04/16/2018 Page 1 / 8
https://www.phoenixcontact.com/gb/products/2865007
Signal conditioner - MINI MCR-SL-U-UI-NC - 2865007
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
6.2 mm
Height
93.1 mm
Depth
102.5 mm
Ambient conditions
Ambient temperature (operation)
-20 °C ... 65 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Input data
Number of inputs
1
Configurable/programmable
Yes, unconfigured
Voltage input signal
0 V ... 24 V
0 V ... 30 V
max. input voltage
50 V DC
Input resistance of voltage input
approx. 125 kΩ (0 ... 24 V)
approx. 155 kΩ (0 ... 30 V)
Output data
Number of outputs
1
Configurable/programmable
Yes, unconfigured
Voltage output signal
0 V ... 10 V
0 V ... 5 V
1 V ... 5 V
2 V ... 10 V
Current output signal
0 mA ... 20 mA
4 mA ... 20 mA
Max. output voltage
≤ 12.5 V
Max. output current
28 mA
Short-circuit current
≤ 22 mA
Load/output load voltage output
> 10 kΩ
Load/output load current output
< 500 Ω (at 20 mA)
Ripple
< 20 mVPP (at 500 Ω)
< 20 mVPP (at 10 kΩ)
Power supply
Nominal supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2
1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the
supply voltage. It can be snapped onto a 35 mm DIN rail according to
EN 60715))
Max. current consumption
< 19 mA (at 24 V DC incl. load)
04/16/2018 Page 2 / 8
https://www.phoenixcontact.com/gb/products/2865007
Signal conditioner - MINI MCR-SL-U-UI-NC - 2865007
Technical data
Power supply
Power consumption
< 450 mW
Connection data
Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section AWG min.
26
Conductor cross section AWG max.
12
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Stripping length
12 mm
Screw thread
M3
General
No. of channels
1
Maximum transmission error
< 0.1 % (of final value)
< 0.4 % (Without adjustment)
Maximum temperature coefficient
< 0.01 %/K
Temperature coefficient, typical
< 0.002 %/K
Limit frequency (3 dB)
approx. 100 Hz
Step response (10-90%)
approx. 3.5 ms
Protective circuit
Transient protection
Electrical isolation
Basic insulation according to EN 61010
Overvoltage category
II
Degree of pollution
2
Rated insulation voltage
50 V AC/DC
Test voltage, input/output/supply
1.5 kV (50 Hz, 1 min.)
Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be
minimal deviations.
Color
green
Housing material
PBT
Mounting position
any
Assembly instructions
To bridge the supply voltage, the DIN rail connector (ME 6,2 TBUS-2
1,5/5-ST-3,81 GN, Order No. 2869728) can be used. It can be snapped
onto a 35 mm DIN rail according to EN 60715.
Conformance
CE-compliant
ATEX
II 3 G Ex nA IIC T4 Gc X
UL, USA/Canada
UL 508 Recognized
Class I, Div. 2, Groups A, B, C, D T5
GL
GL EMC 2 D
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 2
04/16/2018 Page 3 / 8
https://www.phoenixcontact.com/gb/products/2865007
Signal conditioner - MINI MCR-SL-U-UI-NC - 2865007
Technical data
General
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 2
EMC data
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Typical deviation from the measuring range final value
5%
Designation
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Typical deviation from the measuring range final value
5%
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Typical deviation from the measuring range final value
5%
Standards and Regulations
Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Connection in acc. with standard
CUL
Standards/regulations
EN 61000-4-2
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Electrical isolation
Basic insulation according to EN 61010
Conformance
CE-compliant
ATEX
II 3 G Ex nA IIC T4 Gc X
UL, USA/Canada
UL 508 Recognized
Class I, Div. 2, Groups A, B, C, D T5
GL
GL EMC 2 D
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 2 HL 1 - HL 2 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 2 HL 1 - HL 2 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 2 HL 1 - HL 2 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R26
HL 1 - HL 2 HL 1 - HL 2 HL 1 - HL 2
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”,
Category “Manufacturer's declaration”
Drawings
04/16/2018 Page 4 / 8
https://www.phoenixcontact.com/gb/products/2865007
Signal conditioner - MINI MCR-SL-U-UI-NC - 2865007
Application drawing
Block diagram
OUT U
0...24V
US
0...10V
IN U
OUT
GND1
GND2
1
3
UB+
5
+ 1
6
2
– 2
GND3
GND3
OUT U,I
5 +
5
+ 3
GND 1
+24V
passive
GND 2
6
6 –
+24V
7 +
Controller
7
– 4
4
IN U
PLC / DCS
active
GND
UB +
1
4-wire
UPS
2
OUT
IN
Sensor / Field
GND 3
GND 3
8 –
8
24V
MINI MCR-SL-U-UI
+24V
GND 3
Mains voltage
Zone 2
Div. 2
Signal conversion to uninterruptible power supply (UPS)
Dimensional drawing
93,1
102,5
6,2
Classifications
eCl@ss
eCl@ss 4.0
27210120
eCl@ss 4.1
27210120
eCl@ss 5.0
27210120
eCl@ss 5.1
27210120
eCl@ss 6.0
27210120
eCl@ss 7.0
27210120
eCl@ss 8.0
27210120
eCl@ss 9.0
27210120
ETIM
ETIM 4.0
EC002653
ETIM 5.0
EC002653
ETIM 6.0
EC002653
UNSPSC
UNSPSC 6.01
30211506
04/16/2018 Page 5 / 8
https://www.phoenixcontact.com/gb/products/2865007
Signal conditioner - MINI MCR-SL-U-UI-NC - 2865007
Classifications
UNSPSC
UNSPSC 7.0901
39121008
UNSPSC 11
39121008
UNSPSC 12.01
39121008
UNSPSC 13.2
39121008
Approvals
Approvals
Approvals
UL Recognized / cUL Recognized / GL / EAC / cULus Recognized
Ex Approvals
UL Listed / cUL Listed / ATEX / cULus Listed
Approval details
UL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 238705
cUL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 238705
GL
http://exchange.dnv.com/tari/
24916-05 HH
EAC
EAC-Zulassung
cULus Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
Accessories
Accessories
DIN rail connector
04/16/2018 Page 6 / 8
https://www.phoenixcontact.com/gb/products/2865007
Signal conditioner - MINI MCR-SL-U-UI-NC - 2865007
Accessories
DIN rail bus connectors - ME 6,2 TBUS-2 1,5/5-ST-3,81 GN - 2869728
DIN rail connector for DIN rail mounting. Universal for TBUS housing. Gold-plated contacts, 5-pos.
Marking material
Marking label - MINI MCR-DKL-LABEL - 2810272
Label for extended marking of MINI MCR modules in connection with the MINI MCR-DKL
Transparent cover - MINI MCR DKL - 2308111
Fold up transparent cover for MINI MCR modules with additional labeling option using insert strips and flat Zack
marker strip 6.2 mm
Power module
Power terminal block - MINI MCR-SL-PTB - 2864134
MCR power terminal block for supplying several MINI Analog modules via the DIN rail connector, with screw
connection, maximum current consumption of up to 2 A
Power terminal block - MINI MCR-SL-PTB-SP - 2864147
MCR power terminal block for supplying several MINI Analog modules via the DIN rail connector, with spring-cage
connection, maximum current consumption of up to 2 A
Power supply
04/16/2018 Page 7 / 8
https://www.phoenixcontact.com/gb/products/2865007
Signal conditioner - MINI MCR-SL-U-UI-NC - 2865007
Accessories
Power supply unit - MINI-SYS-PS-100-240AC/24DC/1.5 - 2866983
Primary-switched MINI POWER supply for DIN rail mounting, input: 1-phase, output: 24 V DC/1.5 A
Power supply unit - MINI-PS-100-240AC/24DC/1.5/EX - 2866653
Primary-switched power supply MINI POWER for DIN rail mounting, input: 1-phase, output: 24 V DC/1,5 A, for the
potentially explosive area
System adapter
System adapter - MINI MCR-SL-V8-FLK 16-A - 2811268
Eight MINI analog signal converters with screw connection method can be connected to a control system using a
system adapter and system cabling with a minimum of wiring and very low error risk.
Phoenix Contact 2018 © - all rights reserved
http://www.phoenixcontact.com
04/16/2018 Page 8 / 8