MACX MCR-EX-SL-RPSSI-I(-SP)
Repeater power supply Ex
INTERFACE
Data sheet
103568_en_01
1
© PHOENIX CONTACT - 11/2008
Description
The repeater power supply Ex
MACX MCR-EX-SL-RPSSI-I(-SP) has been designed for
the operation of intrinsically safe measuring transducers
and mA current sources installed in the Ex area.
The 2-wire measuring transducers are supplied with power
and analog 0/4 ... 20 mA measuring values from the Ex area
are transmitted to the non-Ex area. 4-wire measuring
transducers and mA current sources can be operated via a
non-feeding input. The module output can be operated
actively or passively.
The analog measuring value can be overlaid with digital
(HART) communication signals on the Ex or non-Ex side
and transmitted bidirectionally.
An additional resistance can be switched in the output
circuit in order to increase the HART impedance in
low-ohmic systems using a terminal point.
1.1
–
–
–
–
–
–
–
–
–
–
Properties
Single-channel
HART-compatible
Input 0/4 mA ... 20 mA, [Ex ia] IIC, feeding and
non-feeding
Output 0/4 mA ... 20 mA (active or passive)
Error indication according to NAMUR NE 43
SIL 2 according to EN 61508
Electrical 3-way isolation
Installation in zone 2 permissible
Power supply via DIN rail connector possible
With screw
(MACX MCR-EX-SL-RPSSI-I)
or spring-cage connection
(MACX MCR-EX-SL-RPSSI-I-SP)
Test sockets are integrated into the COMBICON
connectors for connecting the HART communicators.
The devices can be installed in zone 2 with the "n"
(EN 60079-15) protection type.
WARNING: Explosion hazard
The device is an item of associated electrical equipment for intrinsically safe circuits. It is designed for
use in zone 2, if specific conditions are observed.
When installing and operating the device, the applicable safety directives (including national safety directives),
accident prevention regulations, as well as general technical regulations, must be observed.
WARNING: Explosion hazard
Observe the safety regulations and installation notes on page 5.
Make sure you always use the latest documentation.
It can be downloaded at www.phoenixcontact.com.
This data sheet is valid for all products listed on the following page:
MACX MCR-EX-SL-RPSSI-I(-SP)
Table of contents
1
Description.................................................................................................................................. 1
2
Ordering data.............................................................................................................................. 2
3
Technical data ............................................................................................................................ 2
4
Safety regulations and installation notes..................................................................................... 5
5
Installation .................................................................................................................................. 6
6
Comparison of safety data .................................................................................................................................. 8
7
Safety-related applications (SIL 2) .............................................................................................. 9
2
Ordering data
Repeater power supply Ex
Description
Type
Order No.
Pcs./Pkt.
Repeater power supply Ex,
with screw connection
MACX MCR-EX-SL-RPSSI-I
2865340
1
Repeater power supply Ex,
with spring-cage connection
MACX MCR-EX-SL-RPSSI-I-SP
2924016
1
Type
Order No.
Pcs./Pkt.
ME 6.2 TBUS-2 1.5/5-ST-3.81 GN
2869728
10
MACX MCR-PTB
MACX MCR-PTB-SP
2865625
2924184
1
1
Accessories
Description
DIN rail connectors (T-BUS), 5-pos., for bridging the supply voltage, can be
snapped onto NS 35/... DIN rail in acc. with EN 60715
Power and error message module, including the relevant DIN rail connector
ME 17.5 TBUS 1.5/5-ST-3.81 GN
Screw connection
Spring-cage connection
For additional accessories, please refer to the "INTERFACE" catalog from Phoenix Contact.
3
Technical data
Input
Input
Current input, intrinsically safe
Input signal
Repeater power supply operation (terminal assignment 4.1, 4.2)
4 mA ... 20 mA
Supply voltage
> 16 V (at 20 mA)
> 15.3 V (at 22.5 mA)
Isolating amplifier operation (terminal assignment 5.1, 5.2)
0 mA ... 20 mA, 4 mA ... 20 mA
Voltage drop
< 3.5 V
Output
Output
Current output, short-circuit-proof
Output signal, active
Repeater power supply operation
4 mA ... 20 mA
Isolating amplifier operation
0 mA ... 20 mA, 4 mA ... 20 mA
103568_en_01
PHOENIX CONTACT
2
MACX MCR-EX-SL-RPSSI-I(-SP)
Output (continued)
Output signal, passive
Repeater power supply operation
4 mA ... 20 mA (external source voltage 14 V ... 26 V)
Isolating amplifier operation
0 mA ... 20 mA, 4 mA ... 20 mA (external source voltage 14 V ... 26 V)
Transmission behavior
Load
1:1
600 Ω at 20 mA
525 Ω at 22.5 mA
Output ripple
22.5 mA (23 mA, typical)
General data
Supply voltage range
19.2 V DC ... 30 V DC
Current consumption
Repeater power supply operation
< 60 mA (at 24 V DC)
Isolating amplifier operation
< 35 mA (at 24 V DC)
Power dissipation
Repeater power supply operation
< 1.1 W (at 24 V DC/20 mA)
Isolating amplifier operation
< 0.9 W (at 24 V DC/20 mA)
Temperature coefficient
Maximum
Typical
Step response (10% ... 90%)
< 0.01%/K
< 0.004%/K
< 600 μs (for jump 4 mA ... 20 mA)
Transmission error
Maximum
< 0.1% (of final value)
Typical
< 0.05% (of final value)
Communication
HART protocol
Signal bandwidth
From Ex area to non-Ex area
0 kHz ... 3 kHz
From non-Ex area to Ex area
200 Hz ... 10 kHz
Test sockets, e.g., for HART communication
COMBICON with 2 mm sockets
Electrical isolation
Input/output/power supply
300 Vrms (rated insulation voltage, surge voltage category II, pollution degree
2, safe isolation as per EN 61010, EN 50178)
2.5 kV AC (50 Hz, 1 min., test voltage)
Input/output
375 V (peak value according to EN 60079-11)
Input/power supply
375 V (peak value according to EN 60079-11)
Ambient temperature
Operation
-20°C ... +60°C (any mounting position)
Storage/transport
-40°C ... +80°C
Permissible humidity (operation)
10% ... 95% (no condensation)
Status indicator
Green LED (supply voltage)
Housing material
Polyamide
Color
Green
Degree of protection
IP20
Width x length x height
12.5 mm x 114.5 mm x 99 mm (without connection terminal blocks)
103568_en_01
PHOENIX CONTACT
3
MACX MCR-EX-SL-RPSSI-I(-SP)
General data (continued)
Inflammability class according to UL 94
V0
Type
Terminal housing for mounting on DIN rails
Conformance
EMC Directive 2004/108/EC
EN 61000-6-2, EN 61000-6-4, EN 61326-1
Ex Directive (ATEX)
EN 60079-0, EN 60079-11, EN 60079-15
Safety data according to ATEX for intrinsically safe circuits
Repeater power supply operation
Maximum voltage Uo
Maximum current Io
Maximum power Po
25.2 V
93 mA
587 mW
Gas group
IIC
Maximum inductance Lo
Maximum capacitance Co
2 mH
107 nF
Isolating amplifier operation
Maximum voltage Ui
Maximum current Ii
Maximum capacitance/inductance Ci and Li
Maximum voltage Um
30 V
130 mA
Negligible
253 V AC (125 V DC)
Certificates
ATEX
X II (1) GD [Ex ia] IIC
BVS 08 ATEX E 054 X
X II 3 (1GD) G Ex nA [ia] IIC T4
BVS 08 ATEX E 054 X
IECEx
[Ex ia] IIC; Ex nA [ia] IIC T4
UL USA/Canada
UL applied for
Functional safety (SIL)
SIL 2 according to EN 61508
IECEx BVS 08.0016X
Connection data MACX MCR-EX-SL-RPSSI-I
Conductor cross-section
Solid (minimum/maximum)
0.2 mm2/2.5 mm2
Stranded (minimum/maximum)
0.2 mm2/2.5 mm2
AWG/kcmil (minimum/maximum)
24/14
Stripping length
7 mm
Connection method
Pluggable screw connection
Tightening torque
Minimum 0.5 Nm/maximum 0.6 Nm
Connection data MACX MCR-EX-SL-RPSSI-I-SP
Conductor cross-section
Solid (minimum/maximum)
0.2 mm2/1.5 mm2
Stranded (minimum/maximum)
0.2 mm2/1.5 mm2
AWG/kcmil (minimum/maximum)
24/16
Stripping length
8 mm
Connection method
Spring-cage connection
103568_en_01
PHOENIX CONTACT
4
MACX MCR-EX-SL-RPSSI-I(-SP)
4
Safety regulations and installation notes
4.1
Installation and operation
Installation in zone 2
Follow the installation instructions.
WARNING: Explosion hazard
NOTE: Installation, operation, and maintenance
may only be carried out by qualified specialist
personnel.
When installing and operating the device, the applicable
safety directives (including national safety directives),
accident prevention regulations, as well as general
technical regulations, must be observed.
The device is associated equipment of the "Ex-i"
protection type and suitable for installation in
zone 2.
Observe the specified conditions for use in potentially
explosive areas.
WARNING: Explosion hazard
Install the device in a suitable housing with a
minimum of IP54 degree of protection.
Observe the requirements of IEC 60079-14/
EN 60079-14, e.g., steel housing with a wall
thickness of 3 mm.
NOTE: The circuits inside the device must not be
accessed.
Do not repair the device yourself, but replace it with an
equivalent device. Repairs may only be carried out by the
manufacturer.
WARNING: Explosion hazard
NOTE: The device is suitable for IP20 degree of
protection if:
– It is installed outside potentially explosive
areas.
– The environment is clean and dry.
Disconnect the block power supply before:
– Snapping it on or disconnecting it
– Connecting or disconnecting cables of
non-intrinsically safe circuits
WARNING: Explosion hazard
Install the device in a suitable housing with a suitable degree
of protection in accordance with IEC 60529 in order to
protect it from mechanical and electrical damage.
Only use category 3G modules (ATEX 94/9/EC).
Installation in areas with a danger of dust explosions
For the safety data, please refer to the operating instructions
and certificates (EC examination certificate, other
approvals, if necessary).
4.2
WARNING: Explosion hazard
The device is not designed for installation in
areas with a danger of dust explosions.
Safety regulations for installation in potentially
explosive areas
Regulations for intrinsically safe circuits
WARNING: Explosion hazard
When carrying out measurements on the
intrinsically safe side, be sure to observe the
relevant regulations regarding the connection of
intrinsically safe equipment.
Only use devices approved for use in
intrinsically safe circuits.
Connection to the intrinsically safe circuit in areas with
a danger of dust explosions (zones 20, 21, and 22) is
only permitted if the equipment connected to this circuit is
approved for this zone (e.g., category 1D, 2D or 3D).
4.3
Use in safety-related applications (SIL 2)
When using the MACX MCR-EX-SL-RPSSI-I(-SP) in
safety-related applications, observe the instructions in
Section 7, as the requirements differ for safety-related
functions.
WARNING: Explosion hazard
If the device has been used in
non-intrinsically safe circuits, it must not be
used again in intrinsically safe circuits. Clearly
label the module as being non-intrinsically safe.
103568_en_01
PHOENIX CONTACT
5
MACX MCR-EX-SL-RPSSI-I(-SP)
Output (with HART communication)
Installation
NOTE: Electrostatic discharge
The device contains components that can be
damaged or destroyed by electrostatic discharge.
When handling the device, observe the
necessary safety precautions against
electrostatic discharge (ESD) according to
EN 61340-5-1 and EN 61340-5-2.
5.1
Basic circuit diagram
Ex area
Operating Circuit
mode
impedance
Source
passive
input card
Drain
active
input card
Safe area
*
OUT
IN
Source
4.2
- 4.2
3.2
4.1
+ 4.1
3.1
2.2
5.2
- 5.2
5.1
+ 5.1
250 W
2.1
-
+
GND +24V
Figure 1
≥ 250 Ω
< 250 Ω
3.2 (+) and 2.2 (-)
2.1 (+) and 2.2 (-)
2.2 and 3.2
2.2 and 3.2
Connection of the HART communicator on the test
sockets of the terminals
Sink
+
5.2
Structure
-
1
+
1.2
GND
1.1
+24V
1.1
1.2
2.2
2.1
3.1
Power
Zone 0,1,2
Div. 1,2
≥ 250 Ω
< 250 Ω
Connection
of the input
of the HART
card on the communicator *
terminal
3.1 (+) and 3.2 (-)
3.1 and 3.2
3.1 (+) and 2.1 (-)
3.1 and 3.2
3.2
4
Zone 2
Div. 2
2
1.2
1.1 2.2
2.1 3.2
3.1
3
Basic circuit diagram with connection terminal
blocks
R
PW
MACX MCR-EX-SL-RPSSI-I
5
Input (intrinsically safe)
–
–
Repeater power supply operation (2-wire transmitter or
2-wire -measuring transducer)
Connection to terminal 4.1 (+) and 4.2 (-)
Input isolating amplifier operation (4-wire transmitter or
current sources)
Connection to terminal 5.1 (+) and 5.2 (-)
HART communicators can be connected as shown in the
basic circuit diagram. Test sockets (diameter 2 mm) have
been integrated into the connection terminal blocks for this.
4.2
4.1 5.2
5.1
Figure 2
1
2
3
4
Structure
Pluggable COMBICON connection terminal blocks with
test sockets
Status indicator (green LED, supply voltage)
Metal lock for fixing on the DIN rail
Connection option for DIN rail connector
WARNING: Explosion hazard
The instructions given in "Safety regulations for
installation in potentially explosive areas" on
page 5 must be followed.
5.3
Dimensions
99
12.5
7
Operating mode
Source
passive input card
Drain
active input card
103568_en_01
Input card connection to
the terminal
3.1 (+) and 3.2 (-)
114.5
Output (without HART communication)
3.2 (+) and 2.2 (-)
Figure 3
Dimensions (in mm)
PHOENIX CONTACT
6
MACX MCR-EX-SL-RPSSI-I(-SP)
5.4
Mounting
–
WARNING: Explosion hazard
If the device has been used in
non-intrinsically safe circuits, it must not be
used again in intrinsically safe circuits.
Clearly label the module as being non-intrinsically
safe.
A
B
–
C
5.6
Screw connection:
– Insert the wire into the corresponding connection
terminal block.
– Use a screwdriver to tighten the screw in the
opening above the connection terminal block.
Spring-cage connection:
– Insert a screwdriver in the opening above the
connection terminal block.
– Insert the wire into the corresponding connection
terminal block.
Power supply
NOTE: Never connect the supply voltage directly
to the DIN rail connector.
It is not permitted to draw power from the DIN rail
connector or from individual modules.
1
The modules can be powered via the connection terminal
blocks 1.1 (+24 V) and 1.2 (GND) or via the DIN rail
connector (ME 6.2 TBUS-..., order no. 2869728).
2
Figure 4
–
–
–
–
–
5.5
–
–
–
Mounting and removal
Mount the module on a 35 mm DIN rail according to
EN 60715.
When using the DIN rail connector, first place it into the
DIN rail (see A – C, Figure 4). It is used to bridge the
power supply.
Please also ensure you observe the direction of the
module and DIN rail connector when snapping into
position:
Snap-on foot below (2) and connector left (1).
Install the module in a suitable housing to meet the
requirements for the protection class.
Before startup, check that the repeater power supply is
operating and wired correctly, especially with regard to
the wiring and labeling of the intrinsically safe circuits.
Connecting the cables
Pluggable screw terminal blocks (on
MACX MCR-EX-SL-RPSSI-I); litz wires provided with
ferrules.
Pluggable spring-cage terminal blocks (on
MACX MCR-EX-SL-RPSSI-I-SP); litz wires provided
with ferrules.
Lay intrinsically safe and non-intrinsically safe cables
separately.
Permissible cable cross-section: 0.2 mm2 to 2.5 mm2.
103568_en_01
Depending on the number of modules to be powered, the
voltage is either fed via the MACX MCR-EX-SL-RPSSI-I or
the power and error evaluation module
MACX MCR-PTB(-SP) on the DIN rail connector.
Supply via the module
Where the total current consumption of the aligned modules
does not exceed 400 mA, the power can be fed in via a
module's connection terminal blocks. We recommend
connecting a 630-mA-fuse (normal-blow or slow-blow)
upstream.
Supply via the power and error evaluation module
MACX MCR-PTB(-SP)
The supply voltage is fed in via the module
MACX MCR-PTB(-SP) on the DIN rail connectors. The
supply voltage can be provided as either simple or
redundant.
The module MACX MCR-PTB(-SP) has integrated error
evaluation. An auxiliary voltage failure or fuse error is
registered to a relay contact and displayed via a flashing
LED.
5.7
Level shift
NOTE: A level shift between input and output is
not planned. 4 ... 20 mA input signals, therefore,
become 4 ... 20 mA output signals.
In the same way, active input signals from
0 ... 20 mA become electrically isolated
0 ... 20 mA output signals.
PHOENIX CONTACT
7
MACX MCR-EX-SL-RPSSI-I(-SP)
6
Comparison of safety data
WARNING: Explosion hazard
Compare the safety data before connecting a
device located in the Ex-i area to the
MACX MCR-EX-SL-RPSSI-I(-SP).
Safety data for
Field devices:
Ui, Ii, Pi, Li, Ci
Repeater power supply Ex: Uo, Io, Po, Lo, Co
For the values for Uo, Io, Po, Lo, and Co please refer to
"Safety data according to ATEX for intrinsically safe circuits"
on page 4.
Ex-i requirements (simple circuits):
Ui ≥ Uo
Ii ≥ Io
Pi ≥ Po
Li + Lc ≤ Lo
Ci + Cc ≤ Co
(Lc and Cc depend on the cables/lines used.)
103568_en_01
PHOENIX CONTACT
8
MACX MCR-EX-SL-RPSSI-I(-SP)
7
Safety-related applications (SIL 2)
7.1
Safety integrity requirements
Conditions
–
Failure rates
–
–
Type A device (according to EN 61508-2)
Safety Integrity Level (SIL) 1 and 2
–
λsd
λsu*
λdd
λdu
SFF† DCS‡
**
0 FIT 486.7 FIT 0 FIT 50 FIT 90.7% 0%
DCD‡
0%
*
The SU (Safe Undetected) category includes failures that do not
cause a spurious trip.
†
SFF = Safe Failure Fraction
‡
DC = Diagnostic Coverage (safe or dangerous)
**
FIT = Failure In Time (1 FIT = 1 failure/109 h)
–
–
–
PDFAVG values
T[PROOF] =
PFDAVG* =
*
1 year
2.19E-04
4 years
8.76E-04
5 years
1.1E-03
7.2
1.
PFD = Probability of Failure on Demand
2.
PFH* = 4.99 * 10-8/h
* PFH = Probability of Failure per Hour
The boxes marked in white mean that the calculated
PFDAVG values are within the allowed range for SIL 2
according to table 2 of EN 61508-1, but do not fulfill the
requirement to not cover more than 10% of this range, i.e.,
to be better than or equal to 1.00E-03.
The boxes marked in gray mean that the calculated PFDAVG
values are within the allowed range for SIL 2 according to
table 2 of EN 61508-1, and do fulfill the requirement to not
cover more than 10% of this range, i.e., to be better than or
equal to 1.00E-03.
3.
4.
5.
The failure rates of the components used remain
constant throughout the period of use.
Propagation of errors by the device in the system is not
taken into consideration.
The repair time (= replacement) should be eight hours.
The failure rates of the external power supply unit are
not taken into consideration.
The average temperature at which the device is to be
used is +40°C. This is based on standard industrial
conditions.
The failure rates given refer to an ambient temperature
of +40°C. For an ambient temperature of +60°C, you
will need to multiply the failure rates by a factor of 2.5.
The factor of 2.5 is based on empirical values gathered.
Proof test
Carry out the appropriate steps to prevent incorrect
use.
A signal ranging from 4 ... 20 mA is set on the input of
the MACX MCR-EX-SL-RPSSI-I(-SP). The output must
be set to the same value.
Setting ≤ 3.6 mA or > 22 mA verifies that the
subsequent processing can provide signals outside the
range.
If the output value deviates from the input value by more
than 3 x the specified accuracy rating, the
MACX MCR-EX-SL-RPSSI-I(-SP) should be checked.
In the event of an error, the device must be replaced by
an equivalent device.
Restore the safety circuit to full functionality.
Return to normal operation.
Failure limit
The operating mode is based on low demand mode. The
percentage of the device at PFH/PFD for the overall safety
loop is less than 10%.
Sensor
25%
Figure 5
103568_en_01
Switching
amplifier
< 10%
Processing
Actuator
15%
50%
Safety loop
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49 - 52 35 - 30 0
PHOENIX CONTACT • P.O. Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717 - 94 4 - 13 00
www.phoenixcontact.com
9