MACX MCR-EX-SL-RPSS-2I-2I
2-channel repeater power supply, Ex i
Data sheet
105571_en_00
1
© PHOENIX CONTACT 2014-05-13
Description
The 2-channel repeater power supply is designed for the
operation of intrinsically safe (Ex-i) 2-wire measuring transducers installed in the Ex area.
The 2-wire measuring transducers are supplied with power
and analog 4...20 mA measured values from the Ex area are
transferred to the non-Ex area.
The output of the module is active.
The analog measured value on the Ex or non-Ex side can be
overlayed with digital (HART) communication signals and
transmitted bidirectionally.
Sockets are integrated into the COMBICON connectors for
connecting HART communicators.
The module is suitable for safety-related applications up to
SIL 3 according to IEC/EN 61508.
Features
–
–
–
–
–
–
–
–
–
–
–
–
–
–
2-channel
4 ... 20 mA input, intrinsically safe, [Ex ia], powered
4 ... 20 mA output, active
HART-compatible
Error indication according to NAMUR NE 43
Up to SIL 3 according to IEC/EN 61508
5-way electrical isolation
Safe electrical isolation between inputs and outputs,
supply
Power supply possible via DIN rail connector
Installation in Ex zone 2 permitted
Plug-in connection terminal blocks, either screw or
spring-cage connection technology (Push-in technology)
Housing width of 12.5 mm
Low power dissipation
High transmission accuracy
WARNING: Explosion hazard
The device is an associated item of equipment (category 1) with “intrinsic safety” protection type and can be
installed in zone 2 potentially explosive areas as a category 3 device. It meets the requirements of EN 600790:2009, EN 60079-11:2012, and EN 60079-15:2010.
When installing and operating the device, the applicable safety directives (including national safety directives),
accident prevention regulations, as well as general technical regulations must be observed.
Make sure you always use the latest documentation.
It can be downloaded from the product at phoenixcontact.net/products.
This data sheet is valid for all products listed on the following page:
MACX MCR-EX-SL-RPSS-2I-2I
2
Table of contents
1
Description .............................................................................................................................. 1
2
Table of contents ..................................................................................................................... 2
3
Ordering data .......................................................................................................................... 3
4
Technical data ......................................................................................................................... 3
5
Safety regulations and installation notes.................................................................................. 5
5.1
Installation notes ................................................................................................................. 5
5.2
Intrinsic safety ..................................................................................................................... 5
5.3
Installation in Zone 2............................................................................................................. 5
5.4
Safety-related applications (SIL) .............................................................................................. 5
6
Installation ............................................................................................................................... 6
6.1
Structure ........................................................................................................................... 6
6.2
Basic circuit diagram with connection terminal blocks ................................................................... 6
6.3
Dimensions ........................................................................................................................ 7
6.4
Assembly........................................................................................................................... 7
6.5
Connecting the cables .......................................................................................................... 8
6.6
Power supply ...................................................................................................................... 9
7
Comparison of the safety data ................................................................................................. 9
8
Safety-related applications .................................................................................................... 10
8.1
Safety characteristic data .................................................................................................... 10
8.2
Conditions ....................................................................................................................... 11
8.3
Installation and startup ........................................................................................................ 11
8.4
Notes on operation ............................................................................................................. 11
8.5
Recurring checks ............................................................................................................... 12
8.6
Repair ............................................................................................................................. 12
8.7
Standards ........................................................................................................................ 12
8.8
Abbreviations ................................................................................................................... 13
105571_en_00
PHOENIX CONTACT
2
MACX MCR-EX-SL-RPSS-2I-2I
3
Ordering data
Description
Type
Order No.
Pcs. / Pkt.
Ex i measuring transducer repeater power supply, 2-channel; HART-trans- MACX MCR-EX-SL-RPSS-2I-2I
parent. Supplies Ex i 2-wire measuring transducers and transmits the 4 - 20
mA signal from the Ex area to the safe area. 5-way electrical isolation, up
to SIL 3 according to IEC 61508; screw connection.
2865382
1
Ex i measuring transducer repeater power supply, 2-channel; HART-trans- MACX MCR-EX-SL-RPSS-2I-2I-SP
parent. Supplies Ex i 2-wire measuring transducers and transmits the 4 - 20
mA signal from the Ex area to the safe area. 5-way electrical isolation, up
to SIL 3 according to IEC 61508; spring-cage connection.
2924676
1
Accessories
Order No.
Pcs. / Pkt.
DIN rail connector for DIN rail mounting. Universal for TBUS housing. Gold- ME 6,2 TBUS-2 1,5/5-ST-3,81 GN
plated contacts, 5-pos. Plug component
2869728
10
Power and error message module
MACX MCR-PTB
2865625
1
Power and error message module, spring-cage terminal blocks
MACX MCR-PTB-SP
2924184
1
4
Type
Technical data
Input data
Description of the input
Intrinsically safe
Current input signal
4 mA ... 20 mA
Transmitter supply voltage
> 16 V (at 20 mA)
Underload/overload signal range
0 mA ... 24 mA
Output
Output description
Current output
Current output signal
4 mA ... 20 mA (active)
Transmission Behavior
1:1 to input signal
Load/output load current output
≤ 450 Ω (20 mA)
≤ 375 Ω (24 mA)
Output behavior in the event of an error
< 3.6 mA (In the event of cable break at the input (as per NE 43))
> 22.5 mA (In the event of cable short circuit at the input (as per NE 43))
Underload/overload signal range
0 mA ... 24 mA
Supply
Nominal supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (24 V DC (-20% ... +25%))
Max. current consumption
< 100 mA (24 V / 20 mA)
Power loss
< 1.4 W (at 24 V DC / 20 mA)
General data
HART function
Yes
Protocols supported
HART
Signal bandwidth
as per HART specifications
Transmission error, typical
< 0.05 % (of final value)
Maximum transmission error
< 0.1 % (of final value)
Maximum temperature coefficient
< 0.01 %/K
Step response (10-90%)
< 1.3 ms (for 4 mA ... 20 mA step)
Degree of protection
IP20
Inflammability class according to UL 94
V0
105571_en_00
PHOENIX CONTACT
3
MACX MCR-EX-SL-RPSS-2I-2I
General data [...]
Surge voltage category
II
Pollution degree
2
Diameter Test socket
2.3 mm
Status display
Green LED (supply voltage)
Dimensions W / H / D
12.5 mm / 99 mm / 114.5 mm
Type of housing
PA 66-FR green
Connection data
Screw connection
Conductor cross section, solid
0.2 mm² ... 2.5 mm²
0.2 mm² ... 1.5 mm²
Conductor cross section, stranded
0.2 mm² ... 2.5 mm²
0.2 mm² ... 1.5 mm²
Conductor cross section AWG/kcmil
24 ... 14
24 ... 16
Stripping length
7 mm
8 mm
Tightening torque
0.5 Nm ... 0.6 Nm
Spring-cage connection
Ambient conditions
Ambient temperature (operation)
-20 °C ... 60 °C (Any mounting position)
Ambient temperature (storage/transport)
-40 °C ... 80 °C
Permissible humidity (operation)
10 % ... 95 % (non-condensing)
Maximum altitude for use above sea level
≤ 2000 m
Electrical isolation
Input/output, power supply
Rated insulation voltage (surge voltage category II; pollution degree 2, safe
isolation as per EN 61010-1)
50 Hz, 1 min., test voltage
2.5 kV
Input/output
Peak value in accordance with EN 60079-11
375 V
Input/power supply
Peak value in accordance with EN 60079-11
375 V
Output 1/output 2/ power supply
50 Hz, 1 min., test voltage
1.5 kV
300 Vrms
Safety data as per ATEX
Max. output voltage Uo
25.2 V
Max. output current Io
93 mA
Max. output power Po
587 mW
Group ( Max. external inductivity Lo / Max. external capacitance Co )
IIB : 4 mH / 820 nF
IIC : 2 mH / 107 nF
Safety-related maximum voltage Um
253 V AC (125 V DC)
Conformance with EMC Directive 2004/108/EC
Noise immunity according to EN 61000-6-2
When being exposed to interference, there may be minimal deviations.
Noise emission according to EN 61000-6-4
Conformance / approvals
Conformance
CE-compliant, additionally EN 61326
ATEX ( BVS 13 ATEX E 001 X )
II (1) G [Ex ia Ga] IIC/IIB
II (1) D [Ex ia Da] IIIC
II 3(1) G Ex nA [ia Ga] IIC T4 Gc
IECEx ( IECEx BVS 13.0007X )
[Ex ia Ga] IIC/IIB
[Ex ia Da] IIIC
Ex nA [ia Ga] IIC T4 Gc
Functional safety (SIL)
SIL 3
105571_en_00
PHOENIX CONTACT
4
MACX MCR-EX-SL-RPSS-2I-2I
5
Safety regulations and installation notes
5.1
Installation notes
•
•
•
•
•
5.2
•
•
•
The device is a piece of equipment (category 1) which
belongs to the "Intrinsic Safety" ignition protection class
and can be installed in Ex zone 2 as a category 3 device. It meets the requirements of EN 60079-0:2012,
EN 60079-11:2012, EN 60079-15:2010, IEC 60079-0
ed. 6.0, IEC 60079-11 ed. 6.0, and IEC 60079-15
ed. 4.0.
Installation, operation, and maintenance may only be
carried out by qualified electricians. Follow the installation instructions as described. When installing and operating the device, the applicable regulations and safety
directives (including national safety directives), as well
as general technical regulations, must be observed. For
the safety technology data, see this packing slip and the
certificates (EC examination certificate and other approvals if appropriate).
The device must not be opened or modified. Do not repair the device yourself, replace it with an equivalent device. Repairs may only be carried out by the
manufacturer. The manufacturer is not liable for damage resulting from violation.
The IP20 protection (IEC 60529/EN 60529) of the device is intended for use in a clean and dry environment.
The device must not be subject to mechanical strain
and/or thermal loads, which exceed the limits described.
The device complies with the EMC regulations for industrial areas (EMC class A). When using the device in
residential areas, it may cause radio interference.
5.3
•
•
•
5.4
Installation in Zone 2
Observe the specified conditions for use in potentially
explosive areas! Install the device in a suitable approved housing with a minimum of IP54 protection) that
meets the requirements of EN 60079-15. Observe the
requirements of EN 60079-14.
In potentially explosive areas, terminals may only be
snapped onto or off the DIN rail connector and wires
may only be connected or disconnected when the power is switched off.
The device must be stopped and immediately removed
from the Ex area if it is damaged, was subject to an
impermissible load, stored incorrectly or if it malfunctions.
Safety-related applications (SIL)
When using the device in safety-related applications, observe the instructions in “Safety-related applications”, as the
requirements differ for safety-related functions.
Intrinsic safety
The device is approved for intrinsically safe (Ex-i) circuits up to Ex zone 0 (gas) and Ex zone 20 (dust). The
safety technology values for intrinsically safe equipment
and the connecting lines must be observed for the hookup process (IEC/EC 60079-14) and the values specified
in this installation note and/or the EC examination certificate must be observed.
When carrying out measurements on the intrinsically
safe side, observe the relevant regulations regarding
the connection of intrinsically safe equipment. Use only
these approved measuring devices in intrinsically safe
circuits.
If the device was used in circuits which are not intrinsically safe, it is forbidden to use it again in intrinsically
safe circuits. Label the device clearly as being not intrinsically safe.
105571_en_00
PHOENIX CONTACT
5
MACX MCR-EX-SL-RPSS-2I-2I
6
6.2
Installation
Basic circuit diagram with connection terminal
blocks
NOTE: Electrostatic discharge
6.1
OUT
IN
Sensor / Field
The device contains components that can be
damaged or destroyed by electrostatic discharge. When handling the device, observe
the necessary safety precautions against
electrostatic discharge (ESD) according to
EN 61340-5-1 and IEC 61340-5-1.
passive
4.2 - 4.2
CH1
+
4.1
4.1
3.2
active
active
GND
+24V
1.2
rg
,G
82
5B
MA
2.2
2.1berg
lom
2.1
MA
,G
+
+
T
5.2
4.2
-
R
PW
2
HHT
1.1
–
–
IN
4.2
4.1 5.2
5.1
Zone 2
Basic circuit diagram
Input (intrinsically safe)
HHT
2
3
4
3.2
OU
5.1
HHT
HHT
1
3.1
4.1
IN
4.2
4.1 5.2
5.1
Bild 1
2.2
[EX ia]
HHT
-
R
2.1
+
4.2
PW
D
[EX ia]
+
+
4.1
-
1.2
MACX MCR-EX-SL-RPSS-2I-2I
5.2
GN
1.1
+
-
5.1
IZE
D
3.2
Bild 2
HHT
x.
Va
lue
s
CH
CH 1 4
.1
Zo 2 - 5 |4.2
ne .1
U2.1 Div |5.2
O , 2
V .
I O OC.2=
,I
2
P SC = 5,2 3.1
O ,
93 V 3
P
.2
O
m
=
58 A
se
7
em
mW
OU
an
T
ua
l
Zone 0,1,2
Zone 20,21,22
1.2
1.1 2.2
2.1 3.2
3.1
CH 1
D
1.1 2.2
2.1 3.2
+2 .1
43V
HHT
GN
1.2
HHT
4V
1.1
CH 1
+2
+
-
3
IZE
D
HHT
x.
Va
lue
s
CH
CH 1 4
.1
Zo 2 5 |4.2
ne .1|5
Div .2
U
O ,
V .
I O OC =
,I
2
P SC = 5,2
O ,
93 V
P
O
m
=
58 A
se
7
em
mW
an
ua
l
D IN WH
. 2 [Ex
ZO EN E
ia
0
NE NE
Ma mA ]
RG
2
4 ..
3.1
CH 2
CH 2
D IN WH
. 2 [Ex
ZO EN E
ia
0
NE NE
Ma mA ]
RG
2
4 ..
+
m
am
b
+
m
am
b
+
4
+
GND +24V
2.2
C
C
Su
Re erman
Re erman
O X
Or X M
U pp
U pp
d.- 3.2 CR
ly peate y wrd.- MCR
ly peate y ww
n =
n =
-E
r
w3.1No
Ou 24 VDCVolt r Poww.pNo.: -EX
O 24 VD Vo
ag Pow .phoe.: 28 X-S
t
we hoe 28 -SL 4 utp C (-2lt
(-2 ag
4 .. pu
er
L
r S nix 65
-RU ... 20 ut 0%/+2e:
.
t 0%/+2e:
53 -RP
Su nixc6
c
U 20m
3
P mA
up on 8
5%
5%
82
pp onta
SS
A
=
)
)
ply tac 2 T S= S
25
T 253
ly
-2IHA t.co -20-32VI-A2
HA ct.co
-20 V A
2IRT mWA ° ... + C,I 12
RT m
WA ° ... C, 12
SP
+
5
6
R
/ DD RNIN 60°C 5V DC
/D
DO NIN 0°C/- V DC
/-4
O
u
ua
G
4°
N
NO G
°
a
...
...
lC
AN l O
AN
T
+1
+1
CThS
D IN
D IN SE
40
40
ha
EP
a
°F
°F
P
nn
AR
Inp STA ARA
Inp STAnn
el
LL eAl TE
LL TE
ut
u
.2
t
1
E
E
MACX MCR-EX-SL-RPSS-2I-2I-SP
be
1.2
2.1
-
1.2
1.1
32
lom
2.2 2.2
CH2
2.1
Power
5B
+
passive
1
82
-
HHT
HHT
32
3.1
HHT
Structure
Su
3.2
CH1
3.1
5.2 - 5.2
CH2
+
5.1
5.1
1.1
PLC / DCS
AI
Channel 1: connection of 2-wire transmitters or 2-wire
measuring transducers at terminals 4.1 (+) and 4.2 (-)
Channel 2: connection of 2-wire transmitters or 2-wire
measuring transducers at terminals 5.1 (+) and 5.2 (-)
HART communicators (HHT) can be connected as shown in
the basic circuit diagram. Test sockets (diameter 2.3 mm)
have been integrated for this purpose.
Structure
Plug-in COMBICON screw or spring-cage terminal
block with integrated test socket
Green “PWR” LED, power supply
Snap-on foot for DIN rail mounting
Connection option for DIN rail connector
Always adhere to the safety regulations (1.2.
Intrinsic safety).
Output
–
–
Channel 1: active output (terminals 3.1 (+) and 3.2 (-))
for connecting passive analog input cards
Channel 2: active output (terminals 2.1 (+) and 2.2 (-))
for connecting passive analog input cards
HART communicators (HHT) can be connected as shown in
the basic circuit diagram. Test sockets (diameter 2.3 mm)
have been integrated for this purpose.
105571_en_00
PHOENIX CONTACT
6
MACX MCR-EX-SL-RPSS-2I-2I
6.3
Dimensions
6.4
116 (SP)
112,5
99
Assembly
WARNING: Explosion hazard
12,5
7
If the device has been used in non-intrinsically
safe circuits, it must not be used again in intrinsically safe circuits.
114,5
The device must be clearly marked as non-intrinsically safe.
Bild 3
105571_en_00
Dimensions
EN / UL 61010-1:
• Provide for a switch/circuit-breaker in the
vicinity of a device that is marked as disconnect device for this device.
• Provide overcurrent protection (I ≤ 16 A)
within the installation.
• To protect the device against mechanical
or electrical damage, install it in a suitable
housing with appropriate degree of protection as per IEC 60529.
• During maintenance work, disconnect the
device from all effective power sources.
• If the device is not used as described in
the documentation, the intended protection can be negatively affected.
• Thanks to its housing, the device has basic insulation to the neighboring devices,
for 300 Veff. If several devices are installed next to each other, this has to be taken into account, and additional
insulation has to be installed if necessary!
If the neighboring device is equipped with
basic insulation, no additional insulation
is necessary.
• The voltages present at the input, output,
and supply are extra-low voltages (ELV).
Depending on the application, hazardous
voltage (> 30 V) to ground may occur.
Safe electrical isolation between inputs
and outputs and between the inputs and
the supply exists for such cases.
PHOENIX CONTACT
7
MACX MCR-EX-SL-RPSS-2I-2I
A
B
C
6.5
•
•
•
Connecting the cables
Screw terminal blocks: fit the litz wires with ferrules, permitted conductor cross section: 0.2 mm² to 2.5 mm²
Spring-cage terminal blocks: fit the litz wires with ferrules, permitted conductor cross section: 0.2 mm² to
1.5 mm²
Install intrinsically safe and non-intrinsically safe cables
separately
Screw Connection
AWG 24-14
2
0,2-2,5 mm
MACX MCR-...
A
Bild 4
Mounting and removing
7 mm
•
•
•
•
•
Mount the device on a 35 mm DIN rail according to
DIN EN 60715.
When using the DIN rail connector, first insert it in the 35
mm DIN rail according to EN 60715 (A - C).
DIN rails with a height of 7.5 mm or more can be used.
The DIN rail connector is used to bridge the power supply and communication.
The snap-in direction of the device and DIN rail connector must be observed: snap-on foot on the bottom and
plug on the left.
Install the module in a suitable housing to meet the requirements for the protection class.
Before startup, check that the device is operating and
wired correctly, in particular with regard to the wiring
and marking of the intrinsically safe circuits.
B
Bild 5
•
•
0,5-0,6 Nm
5-7 lb In
Screw connection
Insert the wire into the corresponding connection terminal block.
Use a screwdriver to tighten the screw in the opening
above the connection terminal block.
Tightening torque: 0.6 Nm
Spring-cage connection:
AWG 24-16
2
0,2-1,5 mm
MACX MCR-...-SP
A
B
8 mm
A
Bild 6
•
105571_en_00
Spring-cage connection
Insert the wire into the corresponding connection terminal block.
PHOENIX CONTACT
8
MACX MCR-EX-SL-RPSS-2I-2I
6.6
Power supply
7
Comparison of the safety data
NOTE
Never connect the supply voltage directly to
the DIN rail connector. It is not permitted to
draw power from the DIN rail connector or
from individual modules.
The supply voltage can be supplied via terminal points 1.1
and 1.2 or via the DIN rail connector.
WARNING: Explosion hazard
Compare the safety data before connecting a
device located in the Ex i area to this device.
Provide proof of intrinsic safety according to standard IEC/
EN 60079-14 and other national standards and installation
specifications, if applicable.
Safety data
Supply via the MACX Analog Ex module
Where the total current consumption of the aligned modules
does not exceed 400 mA, the power can be supplied directly
at the connection terminal blocks of the module.
Up to 16 modules can be supplied depending on the current
consumption of the modules.
We recommend connecting a 630 mA fuse (normal-blow or
slow-blow) upstream.
Supply via power and error message module
Field devices
Ex repeater power supply
Ui, Ii, Pi, Li, Ci
Uo, Io, Po, Lo, Co
The values for Uo, Io, Po, Lo, Co can be found under “Safety
data according to ATEX” in the “Technical data” section.
Example for proof of intrinsic safety (simple circuit)
Ui Uo
Ii Io
Pi Po
The MACX MCR-PTB (Order No. 2865625) or the MACX
MCR-PTB-SP (Order No. 2924184) supply and error message module is used to provide the supply voltage to the DIN
rail connector.
Simple or redundant diode-decoupled power supply is possible.
Li + Lc Lo
Ci + Cc Co
Lc and Cc depend on the cables used.
Condition Li 1% of Lo or Ci 1% of Co
Depending on the current consumption of the modules, up
to 150 individual modules can be supplied by a supply that
is protected by a fuse.
The module has integrated error evaluation. An auxiliary
supply failure or fuse fault is indicated at a relay contact and
displayed via a flashing LED.
105571_en_00
PHOENIX CONTACT
9
MACX MCR-EX-SL-RPSS-2I-2I
8
Safety-related applications
8.1
Safety characteristic data
In SIL 2 applications, if the percentage of the device for the
entire safety chain is assumed to be a maximum of 10%, a
maintenance/test interval of 4 years can be achieved.
The following notes apply for the devices:
Designation
MACX MCR-EX-SL-RPSS-2I-2I
MACX MCR-EX-SL-RPSS-2I-2I-SP
Order No.
2865382
2924676
Single-channel version
In the case of the single-channel version, each of the two
channels can be used for a (different) safety function.
The following then applies for the safety function:
– Type A device (according to EN 61508-2)
– Safety integrity level (SIL) 2 and 3
– HFT 0
– MTTR 24 h
– Ambient temperature 40°C
Sensor
25 %
Device
21 mA).
The range from 3.6 ... 21 mA is considered the valid signal
range.
Output values outside this range are considered as the safe
state, which is detected by the subsequent controller.
The failure rates in FIT for each of the channels are as follows:
SU
316
SD
0
DU
55
DD
345
SFF
92.27%
DCD
86.25%
PFDavg values
T [PROOF]
PFDavg
1 year
2.52 10-4
4 years
9.79 10-4
5 years
1.22 10-3
Output values outside this range are considered as the safe
state, which is detected by the subsequent controller.
Safe failures in the device are therefore errors where the device sends output signals that deviate from the relevant input
signals by no more than 2%.
Dangerous failures are errors where the device does not follow a change in the input signal or deviates from the input signal by more than 2% and is not outside the range.
Errors that can be detected as dangerous failures are those
which send a signal outside the standard range (< 3.6 mA
and > 21 mA).
The failure rates in FIT for the entire device are as follows:
PFH = 5.53 * 10-8/h
The device is therefore suitable for SIL 3 applications.
105571_en_00
SU
549
SD
0
DU
92
DD
567
SFF
92.36%
DCD
86.04%
PHOENIX CONTACT
10
MACX MCR-EX-SL-RPSS-2I-2I
PFDavg values
T [PROOF]
PFDavg
8.3
1 year
0.91 10-4
5 years
4.15 10-4
10 years
8.27 10-4
Installation and startup
NOTE: Installation, operation, and maintenance may only be carried out by qualified
specialist personnel.
PFH = 1.99 * 10-8/h
When calculating the average probability of a dangerous failure on demand, errors with the same cause were taken into
consideration and a β or βD factor of 2% was determined.
The device is therefore suitable for SIL 3 applications.
In SIL 2 applications, if the percentage of the device for the
entire safety chain is assumed to be a maximum of 10%, a
maintenance/test interval of 10 years can be achieved.
Sensor
25 %
Device