https://www.phoenixcontact.com/us/products/2865586
Temperature measuring transducer - MACX MCR-EX-SL-TC-INC - 2865586
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Ex i temperature measuring transducer: Converts signals from thermocouples installed in Ex areas and mV
sources and transmits a 0/4-20 mA signal to a load in a safe area. Freely programmable, 3-way isolation
Product Features
■
■
■
■
■
■
■
■
Input for resistance thermometers and resistance-type sensors, [Ex ia] IIC
Power supply possible via DIN rail connector
Programming during operation with Ex measuring circuit connected and also voltage-free using IFS-USB-PROG-ADAPTER programming adapter
Installation in zone 2, protection type "n" (EN 60079-15) permitted
3-way electrical isolation
Status indicator for supply voltage, cable, sensor, and module errors
0 ... 20 mA or 4 ... 20 mA output
Configuration via software (FDT/DTM): sensor type, connection technology, measuring range, measuring unit, filter, alarm signal, and output
range
Key Commercial Data
Packing unit
1 pc
Weight per Piece (excluding packing)
120.0 g
Custom tariff number
85437090
Country of origin
Germany
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
04/11/2016 Page 1 / 7
https://www.phoenixcontact.com/us/products/2865586
Temperature measuring transducer - MACX MCR-EX-SL-TC-INC - 2865586
Technical data
Dimensions
Width
12.5 mm
Height
99 mm
Depth
114.5 mm
Ambient conditions
Ambient temperature (operation)
-20 °C ... 60 °C (Any mounting position)
Ambient temperature (storage/transport)
-40 °C ... 80 °C
Maximum altitude
≤ 2000 m
Permissible humidity (operation)
5 % ... 95 % (non-condensing)
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be minimal
deviations.
Degree of protection
IP20
Input data
Input
Intrinsically safe
Sensor types that can be used (TC)
E, J, K, N as per IEC / EN 60584, L as per DIN 43760
Temperature measuring range
-250 °C ... 1372 °C (Range depending on the sensor type)
Input signal range
-20 mV ... 70 mV
Measuring range span
Min. 50 K for thermocouples, 3 mV for mV sources
Output data
Signal output
Current output
Current output signal
0 mA ... 20 mA
4 mA ... 20 mA
Load/output load current output
≤ 500 Ω
Output ripple (current)
< 50 µAPP
Behavior in the event of a sensor error
As per NE 43 or can be freely defined
Power supply
Nominal supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (24 V DC -20%...+25%)
Max. current consumption
< 40 mA (24 V DC)
Power consumption