MACX MCR-S-MUX HART multiplexer Data sheet 103246_en_01 1 © PHOENIX CONTACT - 2012-05-03 Description The MACX MCR-S-MUX HART multiplexer is used for the digital connection of up to 32 HART-capable field devices to a PC. HART field devices are connected in point-to-point mode via a HART connection board and communicate with the HART multiplexer via the HART protocol. These HART signals are superimposed on the analog standardized signals (4 ... 20 mA) of the process variables. Conformance The MACX MCR-S-MUX HART multiplexer meets the following standards and directives: – Directive 94/9/EC – EN 61326 – VDE 0110 – HART Field Communication Protocol Rev. 6.0 The HART multiplexer communicates with a connected PC via an RS-485 bus. The configuration and diagnostics of the connected HART field devices are implemented by the HART/OPC server or standard software tools, such as Cornerstone, AMS (Version 6.2 or later), PDM, PRM, FieldCare or PACTware. WARNING: Risk of electric shock Observe the safety notes on page 4. Make sure you always use the latest documentation. It can be downloaded at www.phoenixcontact.net/catalog. MACX MCR-S-MUX 2 Table of contents 1 Description.................................................................................................................................. 1 2 Table of contents ........................................................................................................................ 2 3 Ordering data.............................................................................................................................. 3 4 Technical data ............................................................................................................................ 3 5 Block diagram............................................................................................................................. 4 6 Safety notes................................................................................................................................ 4 7 Structure ..................................................................................................................................... 5 8 Power supply .............................................................................................................................. 5 9 Installation .................................................................................................................................. 5 10 Settings....................................................................................................................................... 6 10.1 10.2 RS-485 address ............................................................................................................................................. 6 Number of channels/transmission speed ....................................................................................................... 6 11 Startup ....................................................................................................................................................................... 7 11.1 11.2 11.3 Starting the HART multiplexer ........................................................................................................................ 7 LED indicators on startup ............................................................................................................................... 7 Communication with field devices .................................................................................................................. 7 12 Operating states ......................................................................................................................... 7 13 Connection examples ................................................................................................................. 8 13.1 13.2 13.3 13.4 Example 1 - HART multiplexer with connection board and interface converter .............................................. 8 Example 2 - HART multiplexer with connection board and FL COMSERVER .............................................. 10 Example 3 - Several HART multiplexers with connection board and FL COMSERVER ............................... 12 Example 4 - HART multiplexer with motherboard and interface converter or FL COMSERVER .................. 13 14 Repair and maintenance............................................................................................................15 103246_en_01 PHOENIX CONTACT 2 MACX MCR-S-MUX 3 Ordering data HART multiplexer Description Type Order No. Pcs. / Pkt. HART multiplexer, 32-channel, including two 14-wire flat-ribbon cables MACX MCR-S-MUX 2865599 1 Accessories Description Type Order No. Pcs. / Pkt. The HART transfer board is used to operate the MACX MCR-S-MUX HART multiplexer. The signals from the HART-capable signal converters are applied to the terminal strip of the transfer board where they are then transmitted to the multiplexer via an FLK. MACX MCR-S-MUX-TB 2308124 1 Interface converter, for conversion from RS-232 to RS-422 and RS-485, with electrical isolation, 2 channels, DIN-rail mountable PSM-ME-RS232/RS485-P 2744416 1 Repeater, for electrical isolation and increasing the range in RS-485 2-wire bus systems, 3-way isolation, DIN-rail mountable (required if there are more than 32 multiplexers on one interface) PSM-ME-RS485/RS485-P 2744429 1 Ex-i motherboard for accommodating 16 x PI-Ex supply, input or output isolating amplifier modules. With interface for connecting to HART multiplexer and D-SUB pin strip for connecting the analog signals to the control system level. PI-EX-MB-S/16-01-2/D-SUB 2865214 1 FL COMSERVER BASIC..., serial devices server to convert a serial RS-232/ 422/485 interface to Ethernet, supports TCP, UDP applications, incl. CD-ROM with Com Port Redirector Software and user documentation (PDF). FL COMSERVER BASIC 232/422/ 485 2313478 1 Only use original accessories and original replacement parts from Phoenix Contact. 4 Technical data Field device interface (HART) Channels 16 or 32; can be set via a switch Connection method Flat-ribbon cable, 14-pos. (included) Signal HART FSK HART specification HART Field Communication Protocol Rev. 6.0 (backwards compatible up to Rev. 4.0); FSK Physical Layer Specification (Rev. 8.1) Data transmission indicator 2 yellow "Tx" and "Rx" LEDs: "HART" Error indicator Red "ERR" LED (flashes in the event of an error on the HART bus) RS-485 interface Connection method 9-pos. D-SUB socket Signal RS-485 Data flow control/protocols Compatible with OPC HART server, AMS, PDM, and PRM Number of HART multiplexers per bus segment 31, maximum Address setting 0 ... 127; via rotary switch on the front Data rate 9600/19200/38400/57600 [bps]; via rotary switch on the front Transmission length ≤ 1200 m Indicator 2 yellow "Tx" and "Rx" LEDs: "RS-485" General data Supply voltage range 20 V DC ... 30 V DC Nominal supply voltage 24 V DC Current consumption 55 mA Power consumption 1.35 W Operating voltage indicator Green "PWR" LED Undervoltage monitoring Yes (no faulty module/output states) 103246_en_01 PHOENIX CONTACT 3 MACX MCR-S-MUX General data [...] Electrical isolation of HART signal/RS-485 350 V AC Electrical isolation of HART signals from one another 100 V DC (capacitive) Electrical isolation of HART signal/supply 350 V AC Electrical isolation of RS-485/supply 350 V AC Error monitoring Processor error: "PWR" LED flashes; HART communication error: "ERR" LED flashes Width x height x length 35.2 x 99 x 114.5 mm Ambient conditions Ambient temperature (operation) -20°C ... 60°C Ambient temperature (storage/transport) -40°C ... 80°C Humidity ≤ 95% (no condensation) Conformance/approvals Conformance 5 CE-compliant Block diagram Safe area E.g., PSM-ME-RS232/RS485-P A+5V GND B+ RS-485 Trans. 8 6 5 3 X2 RS-485 RS-232 PC 24 V 24 V 5V control 6 data 5V HART connection board X1 HART CH 1...32 FSK modem FLK 14 connector µC Safety notes WARNING: Risk of electric shock Please observe the following notes during installation and operation: – Observe all national assembly and installation regulations (e.g., EN 60079-14), national safety and accident prevention regulations, generally recognized technical regulations, as well as the safety notes in the operating instructions. – Install the HART multiplexer outside potentially explosive areas. – Use the module for its intended purpose, i.e., only for its approved application (see page 1). – Incorrect or improper use or failure to observe the notes in the operating instructions invalidates the warranty. – Modifications and changes to the module are not permitted. – The module must only be installed and operated when in an undamaged, dry, and clean state. 103246_en_01 PHOENIX CONTACT 4 MACX MCR-S-MUX 7 Structure 1 2 3 4 5 6 7 9 1 HA 5V 3 oa 24 V X2 rd HA RT X1 234 01 ADDRESS 234 01 56 56 01 µC MACX MCR-S-MUX CH 16 Seri al N o. X XXX 6 9k k2 19 k4 38 7k6 5 1 10 6 0 10 789 m 4 5 56 789 FS K mo de 8 9 3 9 CH FL .1.. K 1 X1 .32 4C on ne cto r 5V RS 4 Tra 85 ns . erb 234 5 oth control RS485 6 A+5 V GND B+ 8 24 V X2 MA Or CX M d.- C N R ltip o.: 2 -S-M 8 6 UX lex HA 5 er RT 59 M Mu data RT PC 789 www.interface.phoenixcontact.com 2 FLK connection D-SUB connection "PWR" LED, power "ERR" LED, error "HART-Tx"/"HART-Rx" LEDs, data transmission Rotary switch for RS-485 address Rotary switch for number of channels and transmission speed "RS485-Tx"/"RS485-Rx" LEDs Universal snap-on foot for EN DIN rails CH 32 A k2 19 k6 9 k2 19 k4 38 k6 57 A 6 9k 7 8 XXX X 8 Power supply The HART multiplexer is supplied with power by the HART connection board, e.g.,MACX MCR-S-MUX-TB, which is connected via the 14-pos. flat-ribbon cable. 9 Installation WARNING: Danger if installed incorrectly C Install the HART multiplexer outside potentially explosive areas. B D A 103246_en_01 The assignment of the connection terminal blocks is shown in the block diagram. The module can be snapped onto all 35 mm DIN rails according to EN 60715. • Push the module onto the DIN rail from below (A). Push the module from the front toward the mounting surface until it engages with a click (B). • Pull the base latch up using a screwdriver, needle-nose pliers or similar (C). Pull the top edge of the module away from the mounting surface and pull the module diagonally downward away from the DIN rail (D). PHOENIX CONTACT 5 MACX MCR-S-MUX 10 Settings 10.1 RS-485 address Each HART multiplexer that is installed is assigned an address. This is set directly on the front of the multiplexer. Please note that the setting is not indicated by the slot for the screwdriver, but by a small slot on the edge of the rotary switch. 23 78 1 1 = Units 10 = Tens 100 = Hundreds 901 ADDRESS 23 78 456 10 901 78 456 100 16 CH = 16 channels 16 CH 32 CH 9k6 19k2 19k2 A 9k6 19k2 38k4 57k6 9k6 A Figure 2 9k6 19k2 38k4 57k6 = = = = 9.6 kbps 19.2 kbps 38.4 kbps 57.6 kbps 32 CH = 32 channels 19k2 9k6 19k2 38k4 57k6 9k6 A = = = = = = 19.2 kbps *) 9.6 kbps 19.2 kbps 38.4 kbps 57.6 kbps 9.6 kbps *) Rotary switch Example: 16 channels, 9600 bps 901 Figure 1 Number of channels/transmission speed The number of channels and transmission speed are set in the same way. 38k4 57k6 456 23 10.2 Rotary switches Example: Address 103 *) Select these settings ("19k2 A", "9k6 A") when connecting the HART multiplexer to PRM (ARCOM protocol). Select the "9k6" setting when operating the HART multiplexer with AMS (Version 6.2). Settings are only applied after a software reset or module restart. 103246_en_01 PHOENIX CONTACT 6 MACX MCR-S-MUX 11 Startup 12 11.1 Starting the HART multiplexer LED indicators • • Connect the flat-ribbon cable (supplied as standard with the module) to the HART connection board, e.g., MACX MCR-S-MUX-TB. Connect the HART connection board, e.g., MACX MCR-S-MUX-TB, to the 24 V DC supply voltage. The HART multiplexer scans all 32 channels (default setting) for connected HART field devices (CMD 0). 11.2 Des. PWR Operating states Color Indicator Green Steady light: HART-Tx Yellow Lit HART-Rx alternately: RS485-Rx Yellow Lit RS485-Tx alternately: Supply voltage present, operation OK Communication with HART field devices OK Communication with the PC via the RS-485 interface OK LED indicators on startup (See also "Troubleshooting" on page 15) Des. PWR Color Indicator Green Steady light: Flashing: HART-Tx Yellow Flashing briefly: HART-Rx Yellow Flashing briefly: ERR 11.3 Red Flashing briefly: Supply voltage present, operation OK Module error; switch module off/on again Request to field device Confirmation from field device; communication OK No confirmation from field device Communication with field devices An RS-485 bus is not required for communication with field devices. Once scanning is complete, the HART multiplexer establishes communication with the HART field devices that are found. The "HART-Tx" and "HART-Rx" LEDs light up alternately. If no field devices are found when the HART multiplexer is started, both LEDs remain off. If modules are added later, they must be located and added using the PC software (e.g., in Cornerstone using "Learn" or "Add instrument"). HART communication is only possible if the control circuit resistance is between 230 Ω and 600 Ω. An additional resistor may be required. 250 Ω is sufficient in most cases. 103246_en_01 PHOENIX CONTACT 7 MACX MCR-S-MUX 13 Connection examples Various connection boards and transmission options are available for connecting the field devices to the HART multiplexer. – "Example 1 - HART multiplexer with connection board and interface converter" on page 8 "Example 2 - HART multiplexer with connection board and FL COMSERVER" on page 10 "Example 3 - Several HART multiplexer with connection board and FL COMSERVER" on page 12 "Example 4 - HART multiplexer with motherboard and interface converter or FL COMSERVER" on page 13 – If one board is not sufficient, the connection board can be extended with a second board. – – For a detailed description of the installation of the HART multiplexer and additional information, please refer to the user manual at www.phoenixcontact.net/catalog. 13.1 Example 1 - HART multiplexer with connection board and interface converter 1 17 16 32 ... 17 32 FLK 14 MACX MCR-S-MUX-TB or 17 1 2 1 US1 PC ... 20 ... 30 V DC 16 32 16 MACX MCR-S-MUX-TB FLK 14 X1 78 78 901 78 901 9 1 10 100 X2 456 MACX MCR-S-MUX 23 456 ADDRESS 23 456 32 CH 38k4 16 CH 19k2 A 9k6 19k2 57k6 9k6 A 9k6 19k2 38k4 57k6 23 901 MACX MCR-S-MUX RS-232 RS-485 Interface converter, RS-485 to RS-232 Figure 3 103246_en_01 MACX MCR-S-MUX HART multiplexer with MACX MCR-S-MUX-TB connection board and interface converter PHOENIX CONTACT 8 MACX MCR-S-MUX The following components are required: – Field device HART-capable Ex-certified, if necessary – Signal converter HART-penetrable Ex-certified, if necessary, for explosion protection through energy limitation (EX-i) of the circuit for the field device. For example, a repeater power supply that supplies the field device and forwards the process signal (4 ... 20 mA) with electrical isolation to a controller. – If required, a suitable terminal block in order to route the signal to the connection board. – HART connection board Here, a maximum of 16 channels are connected per board. An FLK plug can be used to extend this to 32 channels by adding a board. – HART multiplexer Accepts the HART signal, which was previously decoupled capacitively, and forwards it via an RS-485 interface. A maximum of 32 field devices in succession can therefore communicate bidirectionally via a HART multiplexer. The flat-ribbon cable for connection to the connection board is supplied as standard. – Interface converter, RS-485 to RS-232 – If necessary, a resistor for the signal cable A termination resistor may be required in the signal cable. According to the HART specification, a resistance value of between 230 and 600 Ω is required for the transmission of the HART signal. – Power supply The converter, connection board, signal converter, and, if necessary, the field device must be supplied with 24 V. Software The following may be required: – Standard software tools, such as Cornerstone, AMS (Version 6.2 or later), PDM, PRM, FieldCare or PACTware – HART OPC server (HCF server - the program can be purchased from the HCF (HART Communication Foundation)) 103246_en_01 PHOENIX CONTACT 9 MACX MCR-S-MUX 13.2 Example 2 - HART multiplexer with connection board and FL COMSERVER The HART multiplexer organizes bidirectional data exchange between a maximum of 32 field devices and a separate PC or controller. HART connection boards 4...20 mA X2 456 1 Ethernet 901 456 78 ADDRESS 23 78 23 X1 10 901 23 456 78 100 32 17 32 1 16 1 16 MACX MCR-S-MUX 901 17 16 CH 32 CH 9k6 19k2 19k2 A 9k6 19k2 38k4 57k6 38k4 57k6 9k6 A HART multiplexer FL COMSERVER 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR 4.1 4.2 5.1 5.2 32 signal converters 4...20 mA 4 5 2 6 3 1 Figure 4 Temperature transducers MACX MCR-S-MUX HART multiplexer with MACX MCR-S-MUX-TB connection board and FL COMSERVER The following components are required: – Field device HART-capable Ex-certified, if necessary – Signal converter HART-penetrable Ex-certified, if necessary, for explosion protection through energy limitation (EX-i) of the circuit for the field device. For example, a repeater power supply that supplies the field device and forwards the process signal (4 ... 20 mA) with electrical isolation to a controller. – If required, a suitable terminal block in order to route the signal to the connection board. – HART connection board Here, a maximum of 16 channels are connected per board. An FLK plug can be used to extend this to 32 channels by adding a board. – HART multiplexer Accepts the HART signal, which was previously decoupled capacitively, and forwards it via an RS-485 interface. A maximum of 32 field devices in succession can therefore communicate bidirectionally via a HART multiplexer. The flat-ribbon cable for connection to the connection board is supplied as standard. 103246_en_01 – – – – FL COMSERVER Has an RJ45 interface for the Ethernet connection. Ethernet cable If necessary, a resistor for the signal cable A termination resistor may be required in the signal cable. According to the HART specification, a resistance value of between 230 and 600 Ω is required for the transmission of the HART signal. Power supply The converter, connection board, signal converter, and, if necessary, the field device must be supplied with 24 V. PHOENIX CONTACT 10 MACX MCR-S-MUX Software The following may be required: – CommPort Redirector (Version 2.2/3 in the example) The CommPort Redirector program, which is supplied as standard with the FL COMSERVER, provides a virtual COM port on the PC, because the HART OPC server expects a COM interface. Version 2.2/3 can be used up to Windows XP. Version 4.3 is available for Windows XP or later. – Browser for configuring the FL COMSERVER – Standard software tools, such as Cornerstone, AMS (Version 6.2 or later), PDM, PRM, FieldCare or PACTware – HART OPC server (HCF server - the program can be purchased from the HCF (HART Communication Foundation)) 103246_en_01 PHOENIX CONTACT 11 MACX MCR-S-MUX 13.3 Example 3 - Several HART multiplexer with connection board and FL COMSERVER Several HART multiplexer can be connected in parallel so that, in theory, up to 4000 channels can be visualized on a PC via the interface. PLC/IOs Ethernet up to 125 modules MACX MCR-S-MUX 32 17 32 1 16 1 16 32 CH 9k6 19k2 19k2 A 9k6 19k2 38k4 57k6 23 456 ADDRESS 23 1 456 10 456 23 23 17 16 CH 38k4 57k6 9k6 A 17 32 17 32 1 16 1 16 MACX MCR-S-MUX 23 23 901 901 16 MACX MCR-S-MUX 901 23 ADDRESS 23 901 901 23 23 ADDRESS 23 901 MACX MCR-S-MUX 901 32 1 901 17 16 38k4 57k6 9k6 A 78 32 1 19k2 A 9k6 19k2 X2 78 17 32 CH 9k6 19k2 38k4 57k6 100 78 16 16 CH 1 10 456 78 32 1 38k4 57k6 9k6 A X1 456 456 78 17 16 19k2 A 9k6 19k2 100 78 32 1 32 CH 9k6 19k2 X2 1 10 456 78 78 17 16 CH 38k4 57k6 X1 456 456 78 78 100 78 78 ADDRESS 23 X2 1 10 456 901 X1 456 456 901 X2 100 901 X1 901 HART connection board 16 CH 32 CH 9k6 19k2 19k2 A 9k6 19k2 38k4 57k6 38k4 57k6 9k6 A HART multiplexer FL COMSERVER 4...20mA 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 4.1 4.2 5.1 5.2 1.1 1.2 2.1 2.2 3.1 3.2 PWR 4.1 4.2 5.1 5.2 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I up to 4000 signals MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR MACX MCR-EX-SL-RPSSI-I MACX MCR-EX-SL-RPSSI-I 1.1 1.2 2.1 2.2 3.1 3.2 PWR 4.1 4.2 5.1 5.2 up to 4000 signals Figure 5 103246_en_01 Several MACX MCR-S-MUX HART multiplexer with MACX MCR-S-MUX-TB connection board and FL COMSERVER PHOENIX CONTACT 12 MACX MCR-S-MUX 13.4 Example 4 - HART multiplexer with motherboard and interface converter or FL COMSERVER 2 1 UB1 ... 20 ... 30 V DC Ex area 2 UB2 20 ... 30 V DC Motherboard 2 or 37 Controller 16 FLK 14 1 ... Ex area Motherboard 1 or 37 PC 16 FLK 14 X1 901 78 78 901 78 103246_en_01 RS-232 9 1 10 100 HART multiplexer Figure 6 X2 456 23 456 ADDRESS 23 456 19k2 A 9k6 19k2 32 CH 38k4 57k6 9k6 A 9k6 19k2 38k4 57k6 16 CH 23 901 MACX MCR-S-MUX RS-485 Interface converter, RS-485 to RS-232 or FL COMSERVER MACX MCR-S-MUX HART multiplexer with two PI-EX-MB-S/16-01-2/D-SUB (2 x 16 channels) HART connection boards and PSM-ME-RS232/RS485-P interface converter or FL COMSERVER PHOENIX CONTACT 13 MACX MCR-S-MUX The following components are required: – Field device HART-capable Ex-certified, if necessary – Signal converter HART-penetrable Ex-certified, if necessary, for explosion protection through energy limitation (EX-i) of the circuit for the field device. For example, a repeater power supply that supplies the field device and forwards the process signal (4 ... 20 mA) with electrical isolation to a controller. – If required, a suitable terminal block in order to route the signal to the connection board. – HART connection board, PI-EX-MB-S/16-01-2/DSUB Here, a maximum of 16 channels are connected per board. An FLK plug can be used to extend this to 32 channels by adding a board. – HART multiplexer Accepts the HART signal, which was previously decoupled capacitively, and forwards it via an RS-485 interface. A maximum of 32 field devices in succession can therefore communicate bidirectionally via a HART multiplexer. The flat-ribbon cable for connection to the connection board is supplied as standard. – Interface converter, RS-485 to RS-232 or FL COMSERVER – Ethernet cable (for FL COMSERVER only) – If necessary, a resistor for the signal cable A termination resistor may be required in the signal cable. According to the HART specification, a resistance value of between 230 and 600 Ω is required for the transmission of the HART signal. – Power supply The converter, connection board, signal converter, and, if necessary, the field device must be supplied with 24 V. – Software, see "Software" on page 11 103246_en_01 PHOENIX CONTACT 14 MACX MCR-S-MUX 14 Repair and maintenance We recommend that you only allow us to repair our modules. In exceptional cases, repairs can also be made by another approved body. The modules are maintenance free. Troubleshooting Error detection "PWR" LED off Possible error cause Error removal Auxiliary voltage failure or module fuse faulty Check auxiliary voltage supply. "PWR" LED flashing Internal module error "ERR" LED flashes briefly No HART field device found "HART" LEDs off No HART field device found "RS485" LEDs off No RS-485 bus connected. RS-485 interface not active. If fuse is faulty, return the module for repair. Switch module off/on. If LED keeps flashing, return the module for repair. Connect HART field device and check connection. Connect HART field device and check connection. Connect RS-485 interface and check connection. If the approaches described prove unsuccessful, please contact our nearest sales center. For a quick response, make sure you have the following information to hand: – Type and serial number – Purchase data – Error description – Application (especially input/output circuit) 103246_en_01 PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: + 49 5235 3-00 www.phoenixcontact.com 15
2865599 价格&库存

很抱歉,暂时无法提供与“2865599”相匹配的价格&库存,您可以联系我们找货

免费人工找货