Primary-switched TRIO POWER power supply for DIN rail mounting, input: 1-phase, output: 24 V DC/2.5 A
Product Description
TRIO POWER power supplies with standard functionality
TRIO POWER is particularly suited to standard machine production, thanks to 1- and 3-phase versions up to 960 W. The wide-range input and the
international approval package enable worldwide use.
The robust metal housing, the high electric strength, and the wide temperature range ensure a high level of power supply reliability.
Your advantages
Use the third negative terminal block as a grounding terminal block and minimize installation costs
Maximum operational reliability thanks to high MTBF (mean time between failures) of more than 500,000 hours and high dielectric strength of up to
300 V AC
Rugged design with metal housing and wide temperature range from -25 to +70°C
Compensation of voltage drops by means of output voltage that can be adjusted on the front
Key Commercial Data
Packing unit
1 pc
GTIN
GTIN
4046356046626
Weight per Piece (excluding packing)
643.800 g
Custom tariff number
85044030
Country of origin
China
Technical data
Dimensions
Width
32 mm
12/22/2019 Page 1 / 9
https://www.phoenixcontact.com/us/products/2866268
Power supply unit - TRIO-PS/1AC/24DC/ 2.5 - 2866268
Technical data
Dimensions
Height
130 mm
Depth
115 mm
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 70 °C (> 55° C derating : 2.5%/K)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Max. permissible relative humidity (operation)
≤ 95 % (at 25 °C, non-condensing)
Climatic class
3K3 (in acc. with EN 60721)
Degree of pollution
2
Input data
Nominal input voltage range
100 V AC ... 240 V AC
Input voltage range
85 V AC ... 264 V AC (Derating < 90 V AC: 2,5 %/V)
Dielectric strength maximum
300 V AC
AC frequency range
45 Hz ... 65 Hz
Discharge current to PE
< 3.5 mA
Current consumption
0.95 A (120 V AC)
0.5 A (230 V AC)
Nominal power consumption
97 VA
Inrush current
< 15 A
Mains buffering time
> 20 ms (120 V AC)
> 100 ms (230 V AC)
Input fuse
2 A (slow-blow, internal)
Recommended breaker for input protection
6 A ... 16 A (Characteristics B, C, D, K)
Power factor (cos phi)
0.72
Type of protection
Transient surge protection
Protective circuit/component
Varistor
Output data
Nominal output voltage
24 V DC ±1 %
Setting range of the output voltage (USet)
22.5 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN)
2.5 A (UOUT = 24 V DC)
Derating
55 °C ... 70 °C (2.5%/K)
Connection in parallel
Yes, for redundancy and increased capacity
Connection in series
yes
Feedback voltage resistance
35 V DC
Protection against overvoltage at the output (OVP)
< 35 V DC
Max. capacitive load
unlimited
12/22/2019 Page 2 / 9
https://www.phoenixcontact.com/us/products/2866268
Power supply unit - TRIO-PS/1AC/24DC/ 2.5 - 2866268
Technical data
Output data
Active current limitation
Approx. 5 A (for short-circuit)
Control deviation
< 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple
< 30 mVPP
Output power
60 W
Typical response time
2054000 h
Mounting position
horizontal DIN rail NS 35, EN 60715
Assembly instructions
alignable: horizontally 0 mm, vertically 50 mm
Connection data, input
Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
14
Stripping length
9 mm
Screw thread
M2,5
Connection data, output
Connection method
Screw connection
12/22/2019 Page 3 / 9
https://www.phoenixcontact.com/us/products/2866268
Power supply unit - TRIO-PS/1AC/24DC/ 2.5 - 2866268
Technical data
Connection data, output
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
14
Stripping length
9 mm
Screw thread
M2,5
Signaling
Status display
"DC OK" LED green
Note on status display
UOUT > 21.5 V: LED lights up
Standards and Regulations
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Noise immunity
EN 61000-6-2:2005
Connection in acc. with standard
CUL
Standards/regulations
EN 61000-4-2
Contact discharge
4 kV (Test Level 2)
Standards/regulations
EN 61000-4-3
Frequency range
80 MHz ... 1 GHz
Test field strength
10 V/m
Frequency range
1.4 GHz ... 2 GHz
Test field strength
3 V/m
Standards/regulations
EN 61000-4-4
Comments
Criterion B
Standards/regulations
EN 61000-6-3
EN 61000-4-6
Frequency range
0.15 MHz ... 80 MHz
Voltage
10 V (Test Level 3)
Standards/regulations
EN 61000-4-11
Low Voltage Directive
Conformance with LV directive 2006/95/EC
Standard - Electrical safety
EN 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations
and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage
EN 60950-1 (SELV)
EN 60204 (PELV)
Standard - Safe isolation
DIN VDE 0100-410
12/22/2019 Page 4 / 9
https://www.phoenixcontact.com/us/products/2866268
Power supply unit - TRIO-PS/1AC/24DC/ 2.5 - 2866268
Technical data
Standards and Regulations
Standard – Protection against shock currents, basic requirements for
protective separation in electrical equipment
EN 50178
Standard – Limitation of mains harmonic currents
EN 61000-3-2
Shipbuilding approval
DNV GL (EMC A)
UL approvals
UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950-1
Shock
15g in all directions in acc. with IEC 60068-2-27
Vibration (operation)
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 25;
For details about hazardous substances go to tab “Downloads”, Category
“Manufacturer's declaration”
Drawings
12/22/2019 Page 5 / 9
https://www.phoenixcontact.com/us/products/2866268
Power supply unit - TRIO-PS/1AC/24DC/ 2.5 - 2866268
Dimensional drawing
12/22/2019 Page 6 / 9
https://www.phoenixcontact.com/us/products/2866268
Power supply unit - TRIO-PS/1AC/24DC/ 2.5 - 2866268
Block diagram
Classifications
eCl@ss
eCl@ss 4.0
27040700
eCl@ss 4.1
27040700
eCl@ss 5.0
27049000
eCl@ss 5.1
27049000
eCl@ss 6.0
27049000
eCl@ss 7.0
27049002
eCl@ss 8.0
27049002
eCl@ss 9.0
27040701
ETIM
ETIM 2.0
EC001039
ETIM 3.0
EC001039
ETIM 4.0
EC000599
ETIM 5.0
EC002540
ETIM 6.0
EC002540
ETIM 7.0
EC002540
UNSPSC
UNSPSC 6.01
30211502
UNSPSC 7.0901
39121004
UNSPSC 11
39121004
UNSPSC 12.01
39121004
UNSPSC 13.2
39121004
UNSPSC 18.0
39121004
UNSPSC 19.0
39121004
12/22/2019 Page 7 / 9
https://www.phoenixcontact.com/us/products/2866268
Power supply unit - TRIO-PS/1AC/24DC/ 2.5 - 2866268
Classifications
UNSPSC
UNSPSC 20.0
39121004
UNSPSC 21.0
39121004
Approvals
Approvals
Approvals
DNV GL / UL Listed / UL Recognized / cUL Recognized / cUL Listed / EAC / EAC / cULus Recognized / cULus Listed
Ex Approvals
Approval details
DNV GL
https://approvalfinder.dnvgl.com/
TAA00001AV
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 123528
UL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 211944
cUL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 211944
cUL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 123528
EAC
EAC-Zulassung
12/22/2019 Page 8 / 9
https://www.phoenixcontact.com/us/products/2866268
Power supply unit - TRIO-PS/1AC/24DC/ 2.5 - 2866268
Approvals
RU CDE.A*30.B.01082
cULus Recognized
cULus Listed
EAC
Accessories
Accessories
Device protection
Type 3 surge protection device - PLT-SEC-T3-230-FM-UT - 2907919
Type 2/3 surge protection, consisting of protective plug and base element with screw connection. For single-phase power
supply network with integrated status indicator and remote signaling. Nominal voltage 230 V AC/DC.
Type 3 surge protection device - PLT-SEC-T3-24-FM-UT - 2907916
Type 3 surge protection, consisting of protective plug and base element, with integrated status indicator and remote