Power Supply Unit, Primary Switched, Narrow Design
MINI-PS-48-60DC/24DC/1
• Extra narrow design with widths of 22.5 mm,
45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.)
• Global use due to a wide-range input
• A high level of operational safety in complex
global networks
• Reliable startup of heavy loads due to
POWER BOOST
The reliability of a power supply unit determines the
availability of individual components in a system and
whether complex systems can function safely.
The globalization of markets increases the demands
placed on the power supply unit. A wide-range input
and a high level of availability are required. These
requirements are met by MINI POWER.
1. Short Description
MINI POWER is the extra narrow power supply unit,
which is available in widths of 22.5 mm, 45 mm, and
67.5 mm (0.886, 1.772, and 2.657 in.).
In addition to a 24 V version with output currents of
1 A , 2 A, and 4 A, special voltages are also available
with 5 V/3 A, +/-15 V/1 A, and 10 - 15 V/2 A for
connection to single-phase AC networks or to two
external conductors in three-phase networks with
nominal voltages of 100 - 240 V AC. Two DC/DC
converters convert low direct voltages into an
adjustable and regulated 24 V output voltage.
With the DIN rail bus connector, the MINI-SYS-PS
can be connected in parallel to supply other modules in
the same system with a regulated 24 V DC voltage.
Reliable startup of heavy loads is ensured by a
power reserve of up to 100% – the POWER BOOST.
The high level of operational safety is also ensured in
complex global networks. MINI POWER also operates
in applications where static voltage dips, transient
power supply failures or phase failure are common.
Powerful capacitors ensure mains buffering of more
than 20 ms at full load.
2. Area of Application
MINI POWER can be used globally due to the
consistent provision of a wide-range input.
In this way, your entire system can be tested at any
production location in the world and can be delivered to
any location in the world without faulty switching of the
input voltage. This reduces storage costs and logistical
effort.
An international approval package including
UL 60950 for IT equipment and UL 508 for industrial
control equipment enables the device to be used
globally.
Headquarters: © Phoenix Contact GmbH & Co. KG • Flachsmarktstraße 8 • 32825 Blomberg • Germany
Phone +49 - 52 35 - 30 0 • Fax +49 - 52 35 - 34 12 00 • www.phoenixcontact.com
Local Contact: www.phoenixcontact.com/salesnetwork
Power Supply Unit, Primary Switched, Narrow Design – MINI-PS-48-60DC/24DC/1
3. Technical Data
114.5 mm
(4.508 in.)
N C
N C
O K
99 mm
(3.898 in.)
D C
22.5 mm
(0.886 in.)
MINI-PS-48-60DC/24DC/1
DC/DC Converter
7 mm (0.28 in.)
Input
Output
Signal
Solid
Stranded
[mm2]
AWG
0.2 - 2.5
0.2 - 2.5
0.2 - 2.5
Uu
Torque
[Nm]
[Ib in]
0.2 - 2.5 25 - 14 0.5 - 0.6 4.4 - 5.3
0.2 - 2.5 25 - 14 0.5 - 0.6 4.4 - 5.3
0.2 - 2.5 24 - 14 0.5 - 0.6 4.4 - 5.3
Description
Type
Order No.
Power supply,
primary switched, narrow design
MINI-PS-48-60DC/24DC/1
28 66 27 1
Technical Data
Input Data 1
Nominal input voltage
Input voltage range (current consumption)
Current consumption (for nominal values)
Inrush current limiting
Mains buffering for a nominal load (typical)
Switch-on time after applying the mains voltage
Transient surge protection
Input fuse, internal
48 - 60 V DC (wide-range input)
36 - 75 V DC
0.6 (at 48 V DC), 0.5 (at 60 V DC)
< 15 A, typical
15 ms (at 48 V DC), 20 ms (device protection) (at 60 V DC)
< 0.5 s
Varistor
T 3.15 AL 250 V (3.15 A)
Output Data 2
Nominal output voltage UN/tolerance
Setting range for the output voltage
Output current during convection cooling
and nominal values
POWER BOOST IBOOST (typical t < 2 min.,
-25°C to 60°C [-13°F to +140°F])
Nominal output current
IN -25°C to +60°C (-13°F to +140°F)
Derating
Short-circuit current limit
Startup of capacitive loads
System deviation on:
24 V DC/±1%
22.5 - 28.5 V DC
1.5 A (UOUT = 24 V)
1 A (UOUT = 24 V)
Maximum power dissipation
Level of efficiency (typical)
Response time UOUT (10% - 90%)
Residual ripple/switching peaks (20 MHz)
Can be connected in parallel
Internal surge protection
Resistance to return supply
From +60°C (+140°F), 2.5% per Kelvin
6A
Unlimited
< 1%, typical
< 3%, typical
< 0.1%, typical
1.2 W/5 W
> 85% (at 60 V DC and at nominal values)
< 30 ms, typical
< 100 mVpp (for nominal values)
To increase redundancy and power
Yes, limited to 35 V DC, approximately
35 V DC
Signal Output Data
DC OK (active) (Uout > 21.5 V DC = high signal)
LED (Uout > 21.5 V DC = LED permanently on)
+24 V signal/20 mA, maximum
Green LED
Static load change 10 - 90%
Dynamic load change 10 - 90%
Input voltage change ±10%
No load/nominal load
PHOENIX CONTACT page 2 of 8
Pcs.
Pkt.
1
Power Supply Unit, Primary Switched, Narrow Design – MINI-PS-48-60DC/24DC/1
General Data
Insulation voltage:
Input/output
Approval package
Electrical equipment of machines
Safety transformers for switched-mode power supply units
Electrical safety
(of IT equipment)
Industrial control equipment
1.5 kV AC (type test)/1 kV AC (routine test)
EN 60 204 (Surge Voltage Category III)
EN 61 558-2-17
EN 60950/VDE 0805
UL/C-UL Recognized UL 60 950 u
UL/C-UL Listed UL 508 U
LISTED
Electronic equipment for use in electrical
power installations
Safety extra-low voltage
EN 50 178/VDE 0160
PELV (EN 60 204)
SELV (EN 60 950)
VDE 0100-410
Safe isolation
Protection against electric shock,
basic requirements for safe isolation
in electrical equipment
Limitation of harmonic line currents
DIN VDE 0106-101
According to EN 61000-3-2
Mounting position
Can be mounted with spacing
- Vertically
- Horizontally
Degree of protection
Class of protection
MTBF
Housing version
Weight
Dimensions (W x H x D)
Climatic Data
Ambient temperature
Operation
Storage
Humidity
Vibration
Shock
Pollution degree
Climatic category
According to IEC 68-2-6
According to IEC 68-2-27
On horizontal NS 35 DIN rail according to EN 60715
With spacing of ≥ 5 cm (1.969 in.)
0 cm (0 in.)
IP20
ΙΙ, (in closed control cabinets)
> 500,000 h according to IEC 1709 (SN 29 500)
Polyamide PA, color green
0.2 kg, approximately
22.5 x 99 x 114.5 mm (0.886 x 9.898 x 4.508 in.)
-25°C to +70°C [-13°F to +158°F] (> +60°C [140°F] derating)
-40°C to +85°C [-40°F to +185°F]
Up to 95% at +25°C [77°F], no condensation
< 15 Hz, amplitude ±2.5 mm/15 Hz - 150 Hz, 2.3 g
30 g all space directions
2
(according to EN 50 178)
3K3 (according to EN 60 721)
c
Conformance With EMC Directive 89/336/EEC and
Low Voltage Directive 73/23/EEC
EMC (Electromagnetic Compatibility)
Noise Immunity According to EN 61000-6-2:
Electrostatic
discharge (ESD)
EN 61000-4-23)
Electromagnetic
HF field
EN 61000-4-32)
Fast transients
(burst)
EN 61000-4-43)
Surge current loads
(surge)
EN 61000-4-53)
Conducted
interference
EN 61000-4-62)
Voltage dips
EN 61000-4-113)
Housing
Contact discharge:
Air discharge:
Housing
Frequency:
Field strength:
Input:
Output:
Signal:
I/O/S:
Frequency:
U0:
Input:
Requirements
EN 61 000-6-2
MINI-PS-48-60DC/24DC/1
4 kV
8 kV
> Level 3
8 kV
8 kV
80 - 1000 MHz
10 V/m
Level 3
80 - 2000 MHz
10 V/m
2 kV
2 kV
1 kV
asymmetrical5)
asymmetrical5)
asymmetrical5)
2 kV (Level 3)
2 kV (Level 3)
1 kV (Level 2)
2 kV
1 kV
asymmetrical5)
symmetrical4)
4 kV (Level 3)
2 kV (Level 3)
asymmetrical5)
Level 3
0.15 - 80 MHz
10 V
0.15 - 80 MHz
10 V
30% reduction of the input voltage
for 0.5 periods
See Input Data:
Mains buffering
> 20 ms
Noise Emission According to EN 50081-2:
EN 55011
Class A6)
EN 55011 (EN 55022) Class B7)
Radio interference emission EN 55011
Class A6)
EN 55011 (EN 55022) Class B7)
Radio interference voltage
EN 55011 corresponds to CISPR11/EN 55022 corresponds to
CISPR22
EN 61000 corresponds to IEC 1000
2)
Criterion A: Normal operating characteristics within the specified
limits.
3)
Criterion B: Temporary adverse effects on the operating
characteristics, which the device corrects automatically.
4)
symmetrical:
5)
asymmetrical:
6)
Class A:
7)
Class B:
PHOENIX CONTACT page 3 of 8
Cable to cable
Cable to ground
Industrial applications
Industrial and domestic applications
Power Supply Unit, Primary Switched, Narrow Design – MINI-PS-48-60DC/24DC/1
4. Device View, Connections, and Control Elements
2
4
–
A
+ 1 +
V
24
–
+
C
– TD –
U
O
5
3
.5 5
22 8. C
2 D
V
C
D K
O
V
60 –
48 NC
C C
D N
IN +
1
C
D K
O
ER
OW
IP
N
MI
+
NC
–
48-60V
Range:
8
–25
- 25 … + 70 °C
- 13 … + 154 °F
(>+60°C/+140°F Derating)
INFORMATION
TECHNOLOGY
EQUIPMENT
u
Read installation instructions
before connecting to mains
www.interface.phoenixcontact.com
INDUSTRIAL
CONTROL
EQUIPMENT
43KA
TEMPERATURE
LISTED
U
APPROVALS
Order No.: 28 66 27 1
7
MINI-PS-48-60DC/24DC/1
24V DC
±1%
1A
6
Power Supply
OUTPUT
36-75V
0.8-0.4A
5
INPUT
DC:
NC
6
Figure 04
1 DC input:
36 - 75 V DC input voltage
(0.2 mm2 to 2.5 mm2 solid)
(0.2 mm2 to 2.5 mm2 stranded)
(25 - 14 AWG)
Internal fuse 3.15 A
5. Safety Notes and Warning
Instructions
2 DC output:
24 V DC output voltage (default),
can be set from 22.5 - 28.5 V DC using
potentiometer 4 (0.2 mm2 to 2.5 mm2 solid)
(0.2 mm2 to 2.5 mm2 stranded) (25 - 14 AWG)
The device is idling-proof and short-circuit-proof.
3 DC OK output active
4 Potentiometer 22.5 - 28.5 V DC
5 DC OK LED
6 Universal latching foot for EN DIN rails
To ensure that the device can be operated safely
and all functions can be used, please read these
instructions carefully.
Installation and startup must only be carried out by
qualified personnel. The relevant country-specific
regulations (e.g., VDE, DIN) must also be observed.
Before startup it is particularly important to ensure
that:
• All supply lines have sufficient fuse protection and
are the correct size.
• All output cables are the correct size for the maximum
device output current or have separate fuse
protection.
• Sufficient convection is ensured.
PHOENIX CONTACT page 4 of 8
Power Supply Unit, Primary Switched, Narrow Design – MINI-PS-48-60DC/24DC/1
6. Installation
6.1. Mounting
The power supply unit can be snapped onto all DIN
rails according to EN 60715. The device must be
mounted horizontally (input terminal blocks facing
downwards).
Installation Dimensions
5
6
To ensure sufficient convection, a
minimum spacing of 5 cm (1.969 in.) to
other modules is required above
and below the device.
7
8
C/1
/24D
0 °C
DC 1
+ 7
… 154 °F
8-60 27
- 25 … + ting)
S-4 66
ra
I-P : 28
- 13 De
°F
RE
MINer No. ply
TU
+140
RA
up
0°C/
Ord
MPE
(>+6
TE
er S
N
ow
TIO
P
MA GY
–25
OR LO
INFCHNO NT
UT
TE UIPME
P
T
EQ
OU
–
–
+
C
D K
O
MINI POWER
–
OU –
TD
C
+
D
24 OCK
V1
A
22
.5
28 VD.5
C
UT
INP
:
DC -60V
48 ge:
Ran
5V
36-70.4A
0.8-
C
D
24V
±1%
1A
S
AL
OV
PR
AP
U
TED
LIS
ww
IAL
TR
u
US L
ns
INDNTRO NT
ct io ns
COUIPME
st rum ai
EQ
n in
43KA
om
tio g to
al la tin
act.c
in st nn ec
cont
ad co
Refo re
enix
be
.pho
te
w.in
rfa
ce
DC
OK
IN
D
+ C 48
- 60
+
V
–
–
Figure 05
22.5 mm
(0.886 in.)
Installation depth: 106 mm [4.173 in.] (+ DIN rail)
106 mm (4.173 in.)
DC
+ OK
24V 1 A
MINI POWER
–
–
OUT DC
99 mm (3.898 in.)
199 mm (7.835 in.)
50 mm
(1.969 in.)
114.5 mm (4.508 in.)
22.528.5
VDC
DC
OK
50 mm
(1.969 in.)
IN DC 48 - 60 V
+ + –
–
Figure 06
Mounting:
Place the module with the DIN rail guideway on the
top edge of the DIN rail and then snap it downwards.
Mounting
Removal
Removal:
Release the snap-on catch using a screwdriver and
then detach the module from the bottom edge of the
DIN rail.
Figure 07
PHOENIX CONTACT page 5 of 8
Power Supply Unit, Primary Switched, Narrow Design – MINI-PS-48-60DC/24DC/1
6.2 Connecting Cable
The device is equipped with COMBICON connectors.
This reliable user-friendly connection method enables
quick device connection and visible isolation of the
electrical connection, if required.
Only operate connectors when the power is switched off.
The following cable cross sections can be connected:
1 Input:
2 Output:
3 Signal:
7 mm (0.28 in.)
Solid
[mm2]
0.2 - 2.5
0.2 - 2.5
0.2 - 2.5
Stranded
[mm2]
0.2 - 2.5
0.2 - 2.5
0.2 - 2.5
AWG
Torque
[Nm]
[Ib in]
25 - 14 0.5 - 0.6 4.4 - 5.3
25 - 14 0.5 - 0.6 4.4 - 5.3
25 - 14 0.5 - 0.6 4.4 - 5.3
For reliable and safe-to-touch
connections: Strip 7 mm (0.28 in.)
from the connector ends.
6.3. Input (1, Figure 9)
The 48 - 60 V DC connection is made using the "+" and "-" screw connections.
Protecting the Primary Side
The device must be installed according to the
specifications of EN 60 950.
Device protection is not required, as an internal fuse
is present.
2
3
4
–
A
+ 1 +
V
24
–
+
C
– TD –
U
O
1
ER
OW
P
NI
C
D K
O
.5 5
22 8. C
2 D
V
MI
C
D K
O
If the internal fuse is blown, this is most
probably due to a device fault.
In this case, the device should be
checked in the factory.
V
60 –
48 NC
C C
D N
IN +
+
NC
–
Power Supply
OUTPUT
8
TEMP
U
APPRO
Order No.: 28 66 27 1
7
24V DC
±1%
1A
6
MINI-PS-48-60DC/24DC/
36-75V
0.8-0.4A
48-60V
Range:
5
INPUT
DC:
NC
Figure 09
PHOENIX CONTACT page 6 of 8
Power Supply Unit, Primary Switched, Narrow Design – MINI-PS-48-60DC/24DC/1
6.4. Output (2, Figure 9)
The 24 V DC connection is made using the "+" and
"-" screw connections on the screw connection 2. The
output voltage set upon delivery is 24 V DC.
The output voltage can be adjusted from 22.5 to
28.5 V DC on the potentiometer 4.
Output 24V DC
Active Signal Output (3, Figure 10)
The 24 V DC signal is between the "DC OK" and "-"
connection terminal blocks and can be loaded with
20 mA maximum. This signal output indicates that the
output voltage has fallen below 21.5 V DC when "active
high" changes to "low".
The DC OK signal is isolated from the power output.
This ensures that a separate supply does not enter
from devices connected in parallel.
The 24 V DC signal can be connected directly to a
logic input for evaluation.
DC OK
Protecting the Secondary Side:
The device is electronically short-circuit-proof and
idling-proof. In the event of an error, the output voltage
is limited to a maximum of 35 V DC.
It should be ensured that all output cables are the
correct size for the maximum output current or have
separate fuse protection.
The cable cross sections in the secondary circuit
should be large enough to keep the voltage drops on
the cables as low as possible.
24 V DC
20 mA
UOUT = 24 V
UOUT
[V]
UN
Status 1
ON
Status 2
OFF
U = +24 V
(with reference to "-")
Normal operation of
the power supply unit
UOUT > 21.5 V
U=0V
(with reference to "-")
UOUT ≤ 21.5 V DC
• Secondary load
short circuit
or overload
• No mains voltage or
device fault
DC OK
Figure 10
Signaling
The active DC OK switching output and the DC OK
LED provide function monitoring.
Green
"DC OK" LED 5
Active DC OK
switching output 3
Meaning
+ – –
36 W
24
< 60°C
(140°F)
t < 2 min.
1
1.5
IN
IBOOST
IOUT
[A]
Figure 11
The U/I characteristic curve ensures that both heavy
capacitive loads and devices with DC/DC converters
can be supplied by MINI POWER in the input circuit
without any problems.
Connected fuses are reliably tripped. The selectivity
in your system configuration is ensured at all times.
7. Installation
7.1. Output Characteristic Curve
The device can supply a nominal output current of
1 A up to an ambient temperature of 60°C (140°F). At
temperatures up to 60°C (140°F), the POWER BOOST
provides a short-term output current of 1.5 A for a few
minutes.
In the event of heavier loads the working point
demonstrates the U/I characteristic curve shown in
Figure 11.
On an overload or short circuit, the entire output
current I BOOST is provided permanently at a reduced
output voltage.
Once the overload or short circuit has been removed,
the entire set secondary voltage is available again.
PHOENIX CONTACT page 7 of 8
Power Supply Unit, Primary Switched, Narrow Design – MINI-PS-48-60DC/24DC/1
UOUT = 24 V
1.0
0
0
20
40
60
Ambient temperature [°C]
Figure 12
7.3. Parallel Operation
Devices of the same type can be connected in
parallel to increase both redundancy and power. The
default setting does not have to be adjusted.
If the output voltage is adjusted, an even current
distribution can be ensured by precisely setting all
power supply units that are operated in parallel to the
same output voltage.
To ensure symmetrical current distribution we
recommend that all cable connections from the power
supply unit to the DIN rail are the same length and have
the same cross section.
Depending on the system, for parallel connection of
more than two power supply units a protective circuit
should be installed at each individual device output
(e.g., decoupling diode or DC fuse). This prevents high
return currents in the event of a secondary device fault.
7.4. Redundancy Operation
Redundant connections are designed for supplying
systems, which place particularly high requirements on
operational safety. If a fault occurs in the primary circuit
of the first power supply unit, the second device
automatically takes over the complete power supply
without interruption, and vice versa.
For this purpose, the power supply units to be
connected in parallel must be large enough that the
total current requirements of all loads can be fully met
by one power supply unit. External decoupling diodes
are required for 100% redundancy.
MINI
24 V/1 A + –
MINI
24 V/1 A + –
http://www.phoenixcontact.com
Output current [A]
7.2. Temperature Response
The device can supply a nominal output current of 1 A
up to an ambient temperature of 60°C (140°F). At
temperatures up to 60°C (140°F), the POWER BOOST
provides a short-term output current of 1.5 A for a few
minutes.
The output power must be decreased by 2.5% per
Kelvin temperature increase for ambient temperatures
above +60°C (140°F). At ambient temperatures above
+70°C (+158°F) or in the event of a thermal overload,
the device reduces the output power to protect itself
and returns to normal operation once it has cooled
down.
+
–
Σ= 1A
+ –
MINI
24 V/1 A + –
11/15/03
MINI
24 V/1 A + –
TNR:102053-00
Figure 13
+
–
Σ= 2A
+ –
Figure 14
PHOENIX CONTACT page 8 of 8
∀ PHOENIX CONTACT
7.5. Increasing Power
The output current can be increased to n x IN where
n is the number of devices connected in parallel.
Parallel connection for increasing power is used
when extending existing systems. A parallel
connection is recommended if the power supply unit
does not cover the current consumption of the most
powerful load. Otherwise, the loads should be divided
over independent individual devices.
A maximum of five devices can be connected in
parallel.