https://www.phoenixcontact.com/us/products/2866682
Power supply unit - QUINT-PS/1AC/48DC/10 - 2866682
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Primary-switched QUINT POWER power supply for DIN rail mounting with SFB (Selective Fuse Breaking)
Technology, input: 1-phase, output: 48 V DC/10 A
Product Description
QUINT POWER power supplies with maximum functionality
QUINT POWER circuit breakers magnetically and therefore quickly trip at six times the nominal current, for selective and therefore cost-effective system
protection. The high level of system availability is additionally ensured, thanks to preventive function monitoring, as it reports critical operating states
before errors occur.
Reliable starting of heavy loads takes place via the static power reserve POWER BOOST. Thanks to the adjustable voltage, all ranges between 5 V
DC ... 56 V DC are covered.
Product Features
■
■
■
Quick tripping of standard circuit breakers
Reliable starting of difficult loads
Preventive function monitoring
Key Commercial Data
Packing unit
1 pc
Weight per Piece (excluding packing)
2179.4 g
Custom tariff number
85044030
Country of origin
Thailand
Technical data
Dimensions
Width
90 mm
Height
130 mm
Depth
125 mm
Width with alternative assembly
122 mm
Height with alternative assembly
130 mm
04/12/2016 Page 1 / 7
https://www.phoenixcontact.com/us/products/2866682
Power supply unit - QUINT-PS/1AC/48DC/10 - 2866682
Technical data
Dimensions
Depth with alternative assembly
93 mm
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Max. permissible relative humidity (operation)
≤ 95 % (at 25 °C, non-condensing)
Noise immunity
EN 61000-6-2:2005
Maximum altitude
6000 m
Input data
Nominal input voltage range
100 V AC ... 240 V AC
Input voltage range
85 V AC ... 264 V AC
90 V DC ... 350 V DC (UL 508: ≤ 250 V DC)
Dielectric strength maximum
300 V AC
AC frequency range
45 Hz ... 65 Hz
Frequency range DC
0 Hz
Discharge current to PE
< 3.5 mA
Current consumption
5.1 A (120 V AC)
2.3 A (230 V AC)
4.8 A (110 V DC)
2.4 A (220 V DC)
Inrush surge current
< 20 A (typical)
Power failure bypass
> 20 ms (120 V AC)
> 20 ms (230 V AC)
Input fuse
12 A (slow-blow, internal)
Choice of suitable circuit breakers
10 A ... 16 A (AC: Characteristics B, C, D, K)
Type of protection
Transient surge protection
Protective circuit/component
Varistor
Output data
Nominal output voltage
48 V DC ±1 %
Setting range of the output voltage (USet)
30 V DC ... 56 V DC (> 48 V DC, constant capacity restricted)
Nominal output current (IN)
10 A (-25°C ... 60°C, UOUT = 48 V DC)
POWER BOOST (IBoost)
13 A (-25°C ... 40°C permanent, UOUT = 48 V DC )
Selective Fuse Breaking (ISFB)
60 A (12 ms)
Derating
60 °C ... 70 °C (2.5%/K)
Connection in parallel
Yes, for redundancy and increased capacity
Connection in series
Yes
04/12/2016 Page 2 / 7
https://www.phoenixcontact.com/us/products/2866682
Power supply unit - QUINT-PS/1AC/48DC/10 - 2866682
Technical data
Output data
Active current limitation
IBOOST = 13 A (for short-circuit), approximately
Control deviation
< 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple
< 80 mVPP (with nominal values)
Output power
480 W
Typical response time
93 % (for 230 V AC and nominal values)
Insulation voltage input/output
4 kV AC (type test)
2 kV AC (routine test)
Protection class
I
MTBF (IEC 61709, SN 29500)
> 900000 h (25 °C)
> 630000 h (40°C)
Mounting position
horizontal DIN rail NS 35, EN 60715
Assembly instructions
Alignable: 5 mm horizontally, 15 mm next to active components, 50 mm
vertically
Connection data, input
Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
6 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
4 mm²
Conductor cross section AWG min.
18
Conductor cross section AWG max.
10
Stripping length
7 mm
Screw thread
M3
Connection data, output
Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
6 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
4 mm²
04/12/2016 Page 3 / 7
https://www.phoenixcontact.com/us/products/2866682
Power supply unit - QUINT-PS/1AC/48DC/10 - 2866682
Technical data
Connection data, output
Conductor cross section AWG min.
12
Conductor cross section AWG max.
10
Stripping length
7 mm
Screw thread
M3
Connection data for signaling
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
6 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
4 mm²
Conductor cross section AWG min.
18
Conductor cross section AWG max.
10
Screw thread
M3
Standards and Regulations
Electromagnetic compatibility
Conformance with EMC Directive 2004/108/EC
Shock
30g in each direction, according to IEC 60068-2-27
Noise emission
EN 55011 (EN 55022)
Noise immunity
EN 61000-6-2:2005
Connection in acc. with standard
CSA
Standards/regulations
EN 61000-4-3
EN 61000-4-4
EN 61000-4-6
Standard – Electrical equipment of machines
EN 60204-1
Standard - Electrical safety
IEC 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations
and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage
IEC 60950-1 (SELV) and EN 60204-1 (PELV)
Standard - Safe isolation
DIN VDE 0100-410
Standard – Protection against shock currents, basic requirements for
protective separation in electrical equipment
EN 50178
Standard – Limitation of mains harmonic currents
EN 61000-3-2
Standard - Equipment safety
BG (design tested)
Standard - Approval for medical use
IEC 60601-1, 2 x MOOP
UL approvals
UL Listed UL 508
UL/C-UL Recognized UL 60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous
Location)
Vibration (operation)
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
04/12/2016 Page 4 / 7
https://www.phoenixcontact.com/us/products/2866682
Power supply unit - QUINT-PS/1AC/48DC/10 - 2866682
Technical data
Standards and Regulations
Low Voltage Directive
Conformance with LV directive 2006/95/EC
Approval - requirement of the semiconductor industry with regard to mains
Semi F47-0706
voltage dips
Information technology equipment - safety (CB scheme)
CB Scheme
Rail applications
EN 50121-4
Classifications
eCl@ss
eCl@ss 4.0
27040702
eCl@ss 4.1
27040702
eCl@ss 5.0
27242213
eCl@ss 5.1
27242213
eCl@ss 6.0
27049002
eCl@ss 7.0
27049002
eCl@ss 8.0
27049002
eCl@ss 9.0
27040701
ETIM
ETIM 2.0
EC001039
ETIM 3.0
EC001039
ETIM 4.0
EC002540
ETIM 5.0
EC002540
UNSPSC
UNSPSC 6.01
30211502
UNSPSC 7.0901
39121004
UNSPSC 11
39121004
UNSPSC 12.01
39121004
UNSPSC 13.2
39121004
Approvals
Approvals
Approvals
CSA / UL Recognized / UL Listed / cUL Recognized / IECEE CB Scheme / SEMI F47 / EAC / EAC / cULus Recognized
04/12/2016 Page 5 / 7
https://www.phoenixcontact.com/us/products/2866682
Power supply unit - QUINT-PS/1AC/48DC/10 - 2866682
Approvals
Ex Approvals
UL Listed / cUL Listed / cULus Listed
Approvals submitted
Approval details
CSA
UL Recognized
UL Listed
cUL Recognized
IECEE CB Scheme
SEMI F47
EAC
EAC
cULus Recognized
04/12/2016 Page 6 / 7
https://www.phoenixcontact.com/us/products/2866682
Power supply unit - QUINT-PS/1AC/48DC/10 - 2866682
Drawings
Block diagram
L (+)
active
N (-)
PFC
DC OK
I < IN
13
14
Phoenix Contact 2016 © - all rights reserved
http://www.phoenixcontact.com
04/12/2016 Page 7 / 7