Extract from the online
catalog
STEP-PS/1AC/12DC/1
Order No.: 2868538
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2868538
DIN rail power supply unit 12 V DC/1 A, primary switched-mode, 1phase
Product notes
WEEE/RoHS-compliant since:
10/02/2009
Commercial data
GTIN (EAN)
4046356519960
sales group
H013
Pack
1 pcs.
Weight/Piece
0.0907 KG
Catalog page information
Page 285 (NTK-2010)
http://
www.download.phoenixcontact.com
Please note that the data given
here has been taken from the
online catalog. For comprehensive
information and data, please refer
to the user documentation. The
General Terms and Conditions of
Use apply to Internet downloads.
Product description
STEP POWER power supply units – for building automation
The new STEP POWER generation of compact power supply units is particularly suitable for installation distributors
and flat control panels thanks to its design. The power supply units are available with 24 V DC output voltage in various
performance classes and widths and with the special voltages 5, 12, 15 and 48 V DC. Their high degree of efficiency and
the low standby losses make for high power efficiency.
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 1 / 5
Jul 9, 2010
STEP-PS/1AC/12DC/1 Order No.: 2868538
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2868538
Technical data
Input data
Nominal input voltage
100 V AC ... 240 V AC
AC input voltage range
85 V AC ... 264 V AC
DC input voltage range
95 V DC ... 250 V DC
AC frequency range
45 Hz ... 65 Hz
DC frequency range
0 Hz
Current consumption
Approx. 0.26 A (120 V AC)
Approx. 0.13 A (230 V AC)
Inrush surge current
< 15 A (typical)
Power failure bypass
> 15 ms (120 V AC)
> 90 ms (230 V AC)
Input fuse
1.25 A (slow-blow, internal)
Permissible backup fuse
B6
B10
B16
Output data
Nominal output voltage
12 V DC ±1%
Output current
1 A (-25°C ... 55°C)
1.1 A (-25 °C ... 40 °C permanent)
1.8 A (maximum output current)
Derating
From +55°C to 70°C: 2.5% per Kelvin
55 °C ... 70 °C 2.5%/K
Connection in parallel
Yes, for redundancy and increased capacity
Connection in series
Yes
Control deviation
< 1 % (change in load, static 10% ... 90%)
< 2 % (change in load, dynamic 10% ... 90%)
< 0.1 % (change in input voltage ±10%)
Residual ripple
< 10 mVPP (20 MHz)
Peak switching voltages nominal load
< 10 mVPP (20 MHz)
Maximum power dissipation idling
< 0.4 W
Power loss nominal load max.
< 2.8 W
General data
Width
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
18 mm
Page 2 / 5
Jul 9, 2010
STEP-PS/1AC/12DC/1 Order No.: 2868538
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2868538
Height
90 mm
Depth
61 mm
Weight
0.1 kg
Efficiency
> 83 % (for 230 V AC and nominal values)
Insulation voltage input/output
4 kV AC (type test)
2 kV AC (routine test)
Degree of protection
IP20
Class of protection
II
MTBF
> 500 000 h in acc. with IEC 61709 (SN 29500)
Ambient temperature (operation)
-25 °C ... 70 °C (> 55° C derating)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Max. permissible relative humidity (operation)
95 % (at 25 °C, no condensation)
Mounting position
Horizontal DIN rail NS 35, EN 60715
Assembly instructions
Can be aligned: Horizontal 0 cm, vertical 3 cm
Electromagnetic compatibility
Conformance with EMC directive 2004/108/EC
Immunity to interference
EN 61000-6-2:2005
Low Voltage Directive
Conformance with LV directive 2006/95/EC
Standard – Electrical equipment of machines
EN 60204
Standard - Safety of transformers
IEC 61558-2-17
Standard - Electrical safety
IEC 60950/VDE 0805 (SELV)
Standard – Electronic equipment for use in
electrical power installations and their assembly
into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage
IEC 60950 (SELV) and EN 60204 (PELV)
Standard - Safe isolation
DIN VDE 0100-410
DIN VDE 0106-1010
Standard – Protection against electric shock
DIN 57100-410
Standard – Protection against shock currents,
basic requirements for protective separation in
electrical equipment
DIN VDE 0106-101
Standard – Limitation of mains harmonic currents
EN 61000-3-2
UL approvals
UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950
NEC Class 2 as per UL 1310
Connection data, input
Type of connection
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Screw connection
Page 3 / 5
Jul 9, 2010
STEP-PS/1AC/12DC/1 Order No.: 2868538
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2868538
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
24
Conductor cross section AWG/kcmil max
12
Stripping length
6.5 mm
Screw thread
M3
Connection data, output
Type of connection
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
24
Conductor cross section AWG/kcmil max
12
Stripping length
6.5 mm
Signaling
Output name
LED status indicator
Status display
"DC OK" LED green
Note on status display
UOUT > 10.8 V: LED on
Certificates / Approvals
Certifications applied for:
UL Listed / CUL Listed / UL
Diagrams/Drawings
Block diagram
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 4 / 5
Jul 9, 2010
STEP-PS/1AC/12DC/1 Order No.: 2868538
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2868538
Address
PHOENIX CONTACT Inc., USA
586 Fulling Mill Road
Middletown, PA 17057,USA
Phone (800) 888-7388
Fax (717) 944-1625
http://www.phoenixcon.com
© 2010 Phoenix Contact
Technical modifications reserved;
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 5 / 5
Jul 9, 2010
很抱歉,暂时无法提供与“2868538”相匹配的价格&库存,您可以联系我们找货
免费人工找货