Primary-switched STEP POWER power supply for DIN rail mounting, input: 1-phase, output: 15 V DC/4 A
Product Description
STEP POWER power supplies for installation distributors
The STEP POWER power supply range was developed especially for building automation. The low idling losses and high degree of efficiency ensure
maximum energy efficiency. They allow flexible use and can be snapped onto the DIN rail or screwed onto an even surface.
Why buy this product
Flexible mounting by simply snapping onto the DIN rail or screwing onto a level surface
Reliable power supply thanks to high MTBF (mean time between failures) of more than 500,000 hours and U/I characteristic curve
Energy savings thanks to maximum energy efficiency and incredibly low idling losses
Key Commercial Data
Packing unit
1 STK
GTIN
GTIN
4046356308540
Weight per Piece (excluding packing)
300.000 g
Custom tariff number
85044030
Country of origin
Poland
Technical data
Dimensions
Width
72 mm
Height
90 mm
Depth
61 mm
01/11/2018 Page 1 / 7
https://www.phoenixcontact.com/us/products/2868619
Power supply unit - STEP-PS/ 1AC/15DC/4 - 2868619
Technical data
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 70 °C (> 55° C derating : 2.5%/K)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Max. permissible relative humidity (operation)
≤ 95 % (at 25 °C, non-condensing)
Climatic class
3K3 (in acc. with EN 60721)
Degree of pollution
2
Input data
Nominal input voltage range
100 V AC ... 240 V AC
Input voltage range
85 V AC ... 264 V AC
95 V DC ... 250 V DC
AC frequency range
45 Hz ... 65 Hz
Frequency range DC
0 Hz
Current consumption
0.8 A (120 V AC)
0.5 A (230 V AC)
Nominal power consumption
68.5 W
Inrush surge current
< 15 A (typical)
Mains buffering
> 27 ms (120 V AC)
> 120 ms (230 V AC)
Input fuse
3.15 A (slow-blow, internal)
Choice of suitable circuit breakers
6 A ... 16 A (Characteristics B, C, D, K)
Type of protection
Transient surge protection
Protective circuit/component
Varistor
Output data
Nominal output voltage
15 V DC ±1 %
Setting range of the output voltage (USet)
10 V DC ... 16.5 V DC (> 15 V DC, constant capacity restricted)
Nominal output current (IN)
4 A (-25 °C ... 55 °C)
4.4 A (-25°C ... 40°C permanent )
Output current Imax
9A
Derating
55 °C ... 70 °C (2.5%/K)
Connection in parallel
Yes, for redundancy and increased capacity
Connection in series
yes
Feedback resistance
≤ 25 V DC
Circuit breaker against surge voltage at output by invasive foreign matter
< 25 V DC
Control deviation
< 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
01/11/2018 Page 2 / 7
https://www.phoenixcontact.com/us/products/2868619
Power supply unit - STEP-PS/ 1AC/15DC/4 - 2868619
Technical data
Output data
Residual ripple
< 55 mVPP (20 MHz)
Output power
60 W
Typical response time
< 0.5 s
Peak switching voltages nominal load
< 10 mVPP (20 MHz)
Maximum power dissipation in no-load condition
< 0.5 W
Power loss nominal load max.
8.6 W
General
Net weight
0.27 kg
Operating voltage display
Green LED
Efficiency
> 87 % (for 230 V AC and nominal values)
Insulation voltage input/output
4 kV AC (type test)
3.75 kV AC (routine test)
Insulation voltage input / PE
3.5 kV AC (type test)
2 kV AC (routine test)
Insulation voltage output / PE
500 V DC (routine test)
Protection class
II (in closed control cabinet)
Degree of protection
IP20
> 1134000 h (40 °C)
Mounting position
horizontal DIN rail NS 35, EN 60715
Assembly instructions
Alignable: 0 mm horizontally, 30 mm vertically
Connection data, input
Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Stripping length
6.5 mm
Screw thread
M3
Connection data, output
Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
01/11/2018 Page 3 / 7
https://www.phoenixcontact.com/us/products/2868619
Power supply unit - STEP-PS/ 1AC/15DC/4 - 2868619
Technical data
Connection data, output
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Stripping length
6.5 mm
Screw thread
M3
Standards and Regulations
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Noise immunity
EN 61000-6-2:2005
Connection in acc. with standard
CUL
Standards/regulations
EN 61000-4-2
Contact discharge
4 kV (Test Level 2)
Standards/regulations
EN 61000-4-3
Frequency range
80 MHz ... 1 GHz
Test field strength
10 V/m
Frequency range
1.4 GHz ... 2 GHz
Test field strength
3 V/m
Standards/regulations
EN 61000-4-4
Comments
Criterion B
Standards/regulations
EN 61000-4-5
EN 61000-6-3
EN 61000-4-6
Frequency range
0.15 MHz ... 80 MHz
Voltage
10 V (Test Level 3)
Standards/regulations
EN 61000-4-11
Low Voltage Directive
Conformance with LV directive 2006/95/EC
Standard - Safety of transformers
EN 61558-2-16
Standard - Electrical safety
IEC 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations
and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage
IEC 60950-1 (SELV) and EN 60204-1 (PELV)
Standard - Safe isolation
DIN VDE 0100-410
Standard – Protection against shock currents, basic requirements for
protective separation in electrical equipment
EN 50178
Standard – Limitation of mains harmonic currents
EN 61000-3-2
Shipbuilding approval
DNV GL (EMC B) ABS, NK
UL approvals
UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous
Location)
01/11/2018 Page 4 / 7
https://www.phoenixcontact.com/us/products/2868619
Power supply unit - STEP-PS/ 1AC/15DC/4 - 2868619
Technical data
Standards and Regulations
Shock
18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation)
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.
Information technology equipment - safety (CB scheme)
CB Scheme
Rail applications
EN 50121-4
Assembly instructions
Alignable: 0 mm horizontally, 30 mm vertically
Mounting position
horizontal DIN rail NS 35, EN 60715
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 25;
For details about hazardous substances go to tab “Downloads”, Category
“Manufacturer's declaration”
Drawings
Block diagram
L (+)
N (-)
Schematic diagram
+
+
–
–
Ou
12 tput
V
DC
5A
/5
12DC
1AC/ 3
-PS/ 6858
STEP o.: 28
r-N
Orde
T 0V
INPU 0-24
10 0Hz
-6
:
AC 50 0.65A
:
1.4
ltage
l Vo ~
iona 64V
erat 85-2 V
Op
50
95-2
T
PU
OUT V
12
5A
RE
TU
RA
MPE .+70°C
-25.. 58°F
.+1
-15..
F
131°
C/>+ /k)
5°
(>+5 :2,5% LS
ing
Derat ROVA ustrial
Indntrol nt
APP
:
DC
TE
-26
Co me
Equip
43KA
tion
ma y
Infor nolog
Tech ment
Equip
UL
D
TE
LIS
No.
nual
ma before ins t.com
Read813 g to ma ontac
9038ectin enixc
conn e.pho
erfac
w.int
ww
Classifications
eCl@ss
eCl@ss 4.0
27040702
eCl@ss 4.1
27040702
eCl@ss 5.0
27242213
eCl@ss 5.1
27242213
eCl@ss 6.0
27049002
eCl@ss 7.0
27049002
eCl@ss 8.0
27049002
eCl@ss 9.0
27040701
01/11/2018 Page 5 / 7
https://www.phoenixcontact.com/us/products/2868619
Power supply unit - STEP-PS/ 1AC/15DC/4 - 2868619
Classifications
ETIM
ETIM 2.0
EC001039
ETIM 3.0
EC001039
ETIM 4.0
EC002540
ETIM 5.0
EC002540
ETIM 6.0
EC002540
UNSPSC
UNSPSC 6.01
30211502
UNSPSC 7.0901
39121004
UNSPSC 11
39121004
UNSPSC 12.01
39121004
UNSPSC 13.2
39121004
Approvals
Approvals
Approvals
UL Recognized / UL Listed / cUL Recognized / cUL Listed / GL / NK / IECEE CB Scheme / EAC / EAC / ABS / cULus Recognized / cULus Listed
Ex Approvals
UL Listed / cUL Listed / cULus Listed
Approval details
UL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 214596
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 123528
cUL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 214596
01/11/2018 Page 6 / 7
https://www.phoenixcontact.com/us/products/2868619
Power supply unit - STEP-PS/ 1AC/15DC/4 - 2868619
Approvals
cUL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 123528
GL
http://exchange.dnv.com/tari/
59365-08 HH
NK
http://www.classnk.or.jp/hp/en/
09A024
IECEE CB Scheme
http://www.iecee.org/
DK-14416-M1
EAC
RU CDE.A*30.B.01082
EAC
EAC-Zulassung
http://www.eagle.org/eagleExternalPortalWEB/
08-HG383002-3-PDA
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
ABS
cULus Recognized
cULus Listed
Phoenix Contact 2018 © - all rights reserved
http://www.phoenixcontact.com