https://www.phoenixcontact.com/us/products/2868635
Power supply unit - STEP-PS/ 1AC/24DC/0.75 - 2868635
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Primary-switched STEP POWER power supply for DIN rail mounting, input: 1-phase, output: 24 V DC/0.75 A
Product Description
STEP POWER power supplies for distribution boards
The STEP POWER power supply range was developed especially for building automation. The low idling losses and high degree of efficiency ensure
maximum energy efficiency. They allow flexible use and can be snapped onto the DIN rail or screwed onto an even surface.
Your advantages
Flexible mounting by simply snapping onto the DIN rail or screwing onto a level surface
Reliable power supply thanks to high MTBF (mean time between failures) of more than 500,000 hours and U/I characteristic curve
Energy savings thanks to maximum energy efficiency and incredibly low idling losses
Key Commercial Data
Packing unit
1 pc
GTIN
GTIN
4046356165297
Weight per Piece (excluding packing)
151.600 g
Custom tariff number
85044030
Country of origin
Poland
Technical data
Dimensions
Width
36 mm
Height
90 mm
Depth
61 mm
12/22/2019 Page 1 / 9
https://www.phoenixcontact.com/us/products/2868635
Power supply unit - STEP-PS/ 1AC/24DC/0.75 - 2868635
Technical data
Ambient conditions
Degree of protection
IP20
Ambient temperature (operation)
-25 °C ... 70 °C (> 55° C derating : 2.5%/K)
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Max. permissible relative humidity (operation)
≤ 95 % (at 25 °C, non-condensing)
Climatic class
3K3 (in acc. with EN 60721)
Degree of pollution
2
Input data
Nominal input voltage range
100 V AC ... 240 V AC
Input voltage range
85 V AC ... 264 V AC
95 V DC ... 250 V DC
AC frequency range
45 Hz ... 65 Hz
Frequency range DC
0 Hz
Current consumption
0.3 A (120 V AC)
0.2 A (230 V AC)
Nominal power consumption
36.9 VA
Inrush current
< 15 A (typical)
Mains buffering time
typ. 15 ms (120 V AC)
typ. 70 ms (230 V AC)
Input fuse
1.25 A (slow-blow, internal)
Recommended breaker for input protection
6 A ... 16 A (Characteristics B, C, D, K)
Power factor (cos phi)
0.58
Type of protection
Transient surge protection
Protective circuit/component
Varistor
Output data
Nominal output voltage
24 V DC ±1 %
Nominal output current (IN)
0.75 A (-25 °C ... 55 °C)
0.83 A (-25°C ... 40°C permanent )
Output current Imax
1.4 A
Derating
55 °C ... 70 °C (2.5%/K)
Connection in parallel
Yes, for redundancy and increased capacity
Connection in series
yes
Feedback voltage resistance
≤ 35 V DC
Protection against overvoltage at the output (OVP)
< 35 V DC
Control deviation
< 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
12/22/2019 Page 2 / 9
https://www.phoenixcontact.com/us/products/2868635
Power supply unit - STEP-PS/ 1AC/24DC/0.75 - 2868635
Technical data
Output data
Residual ripple
< 75 mVPP (20 MHz)
Output power
18 W
Typical response time
< 0.5 s
Peak switching voltages nominal load
< 15 mVPP (20 MHz)
Maximum power dissipation in no-load condition
0.5 W
Power loss nominal load max.
3.6 W
General
Net weight
0.11 kg
Operating voltage display
Green LED
Efficiency
> 84 % (for 230 V AC and nominal values)
Insulation voltage input/output
4 kV AC (type test)
3.75 kV AC (routine test)
Protection class
II (in closed control cabinet)
Degree of protection
IP20
MTBF (IEC 61709, SN 29500)
> 926000 h (40 °C)
Mounting position
horizontal DIN rail NS 35, EN 60715
Assembly instructions
alignable: 0 mm horizontally, 30 mm vertically
Connection data, input
Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Stripping length
6.5 mm
Screw thread
M3
Connection data, output
Connection method
Screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
2.5 mm²
Conductor cross section AWG min.
24
Conductor cross section AWG max.
12
Stripping length
6.5 mm
12/22/2019 Page 3 / 9
https://www.phoenixcontact.com/us/products/2868635
Power supply unit - STEP-PS/ 1AC/24DC/0.75 - 2868635
Technical data
Connection data, output
Screw thread
M3
Standards
EMC requirements for noise immunity
EN 61000-6-1
EN 61000-6-2
EMC requirements for noise emission
EN 61000-6-3
EN 61000-6-4
Budgetary standard
IEC 60335-1
Standard - Safety of transformers
EN 61558-2-16
Standard - Electrical safety
IEC 60950-1/VDE 0805 (SELV)
Standard – Electronic equipment for use in electrical power installations
and their assembly into electrical power installations
EN 50178/VDE 0160 (PELV)
Standard – Safety extra-low voltage
IEC 60950-1 (SELV) and EN 60204-1 (PELV)
Standard - Safe isolation
DIN VDE 0100-410
Standard – Limitation of mains harmonic currents
EN 61000-3-2
Standard - Approval for medical use
IEC 60601-1, 2 x MOOP
Rail applications
EN 50121-4
Conformance/approvals
UL approvals
UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4
(Hazardous Location)
NEC Class 2 as per UL 1310
CSA
CSA-C22.2 No. 107.1-01
Shipbuilding approval
DNV GL (EMC B), ABS, LR, RINA, NK, BV
EMC data
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Low Voltage Directive
Conformance with LV directive 2006/95/EC
Electrostatic discharge
EN 61000-4-2
Contact discharge
6 kV (Test Level 3)
Discharge in air
8 kV (Test Level 3)
Electromagnetic HF field
EN 61000-4-3
Frequency range
80 MHz ... 3 GHz
Test field strength
10 V/m (Test Level 3)
Comments
Criterion A
Fast transients (burst)
EN 61000-4-4
Input
4 kV (Test Level 4 - asymmetrical)
Output
2 kV (Test Level 3 - asymmetrical)
12/22/2019 Page 4 / 9
https://www.phoenixcontact.com/us/products/2868635
Power supply unit - STEP-PS/ 1AC/24DC/0.75 - 2868635
Technical data
EMC data
Comments
Criterion A
Surge voltage load (surge)
EN 61000-4-5
Input
2 kV (Test Level 3 - symmetrical)
4 kV (Test Level 4 - asymmetrical)
Output
0.5 kV (Test Level 1 - symmetrical)
1 kV (Test Level 2 - asymmetrical)
Comments
Criterion A
Frequency range
10 kHz ... 80 MHz
Voltage
10 V (Test Level 3)
Comments
Criterion A
Voltage dips
EN 61000-4-11
Criterion A
Normal operating behavior within the specified limits.
Criterion B
Temporary impairment to operational behavior that is corrected by the
device itself.
Environmental Product Compliance
REACh SVHC
Lead 7439-92-1
China RoHS
Environmentally Friendly Use Period = 25;
For details about hazardous substances go to tab “Downloads”, Category
“Manufacturer's declaration”
Drawings
Block diagram
Classifications
eCl@ss
eCl@ss 4.0
27040700
eCl@ss 4.1
27040700
eCl@ss 5.0
27242200
12/22/2019 Page 5 / 9
https://www.phoenixcontact.com/us/products/2868635
Power supply unit - STEP-PS/ 1AC/24DC/0.75 - 2868635
Classifications
eCl@ss
eCl@ss 5.1
27242200
eCl@ss 6.0
27049000
eCl@ss 7.0
27049002
eCl@ss 8.0
27049002
eCl@ss 9.0
27040701
ETIM
ETIM 2.0
EC001039
ETIM 3.0
EC001039
ETIM 4.0
EC002540
ETIM 5.0
EC002540
ETIM 6.0
EC002540
ETIM 7.0
EC002540
UNSPSC
UNSPSC 6.01
30211502
UNSPSC 7.0901
39121004
UNSPSC 11
39121004
UNSPSC 12.01
39121004
UNSPSC 13.2
39121004
UNSPSC 18.0
39121004
UNSPSC 19.0
39121004
UNSPSC 20.0
39121004
UNSPSC 21.0
39121004
Approvals
Approvals
Approvals
DNV GL / IECEE CB Scheme / BV / LR / NK / ABS / BSH / RINA / UL Listed / UL Recognized / cUL Recognized / IECEE CB Scheme / cUL Listed /
EAC / EAC / DNV GL / cULus Recognized / cULus Listed
Ex Approvals
UL Listed / cUL Listed / cULus Listed
Approval details
12/22/2019 Page 6 / 9
https://www.phoenixcontact.com/us/products/2868635
Power supply unit - STEP-PS/ 1AC/24DC/0.75 - 2868635
Approvals
DNV GL
https://approvalfinder.dnvgl.com/
TAE000014W
IECEE CB Scheme
http://www.iecee.org/
SI-4238
BV
http://www.veristar.com/portal/veristarinfo/generalinfo/
approved/approvedProducts/equipmentAndMaterials
21005-C0 BV
LR
http://www.lr.org/en
08/20069 E4
NK
http://www.classnk.or.jp/hp/en/
08A039
ABS
http://www.eagle.org/eagleExternalPortalWEB/
18-HG1797199_PDA
BSH
http://www.bsh.de/de/index.jsp
Nr. 581
RINA
http://www.rina.org/en
ELE038319XG
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 123528
UL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 214596
cUL Recognized
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 214596
12/22/2019 Page 7 / 9
https://www.phoenixcontact.com/us/products/2868635
Power supply unit - STEP-PS/ 1AC/24DC/0.75 - 2868635
Approvals
IECEE CB Scheme
http://www.iecee.org/
DK-27288-M1-UL
cUL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 123528
EAC
EAC-Zulassung
EAC
RU CDE.A*30.B.01082
DNV GL
https://approvalfinder.dnvgl.com/
TAA00001YD
cULus Recognized
cULus Listed
Accessories
Accessories
Device protection
Type 3 surge protection device - PLT-SEC-T3-230-FM-UT - 2907919
Type 2/3 surge protection, consisting of protective plug and base element with screw connection. For single-phase power
supply network with integrated status indicator and remote signaling. Nominal voltage 230 V AC/DC.
12/22/2019 Page 8 / 9
https://www.phoenixcontact.com/us/products/2868635
Power supply unit - STEP-PS/ 1AC/24DC/0.75 - 2868635
Accessories
Type 3 surge protection device - PLT-SEC-T3-24-FM-UT - 2907916
Type 3 surge protection, consisting of protective plug and base element, with integrated status indicator and remote
signaling for single-phase power supply networks. Nominal voltage 24 V AC/DC.
Phoenix Contact 2019 © - all rights reserved
http://www.phoenixcontact.com
12/22/2019 Page 9 / 9
很抱歉,暂时无法提供与“2868635”相匹配的价格&库存,您可以联系我们找货