ILB IB 24 DI16-DSUB
Inline Block IO Module
for INTERBUS With 16 Digital Inputs;
Bus Connection via D-SUB Connectors
AUTOMATIONWORX
Data Sheet
7118_en_02
© PHOENIX CONTACT - 03/2007
Description
The ILB IB 24 DI16-DSUB module is designed for use
within an INTERBUS network. It is used to acquire digital
signals.
INTERBUS Features
–
–
–
Remote bus connection via D-SUB connector
500 kbps transmission speed
Diagnostic and status indicators
Input Features
–
–
–
–
–
Connections for 16 digital sensors
Connection of sensors in 2 and 3-wire technology
Maximum permissible load current per sensor: 125 mA
Maximum permissible load current from the sensor
supply: 2.0 A
Diagnostic and status indicators
Please refer to the "Mounting and Removing Inline Block IO Modules" application note (see "Ordering Data"
on page 2).
Make sure you always use the latest documentation.
It can be downloaded at www.download.phoenixcontact.com.
A conversion table is available on the Internet at
www.download.phoenixcontact.com/general/7000_en_00.pdf.
ILB IB 24 DI16-DSUB
Ordering Data
Product
Description
Type
Order No.
Pcs./Pkt.
ILB IB 24 DI16-DSUB
2878421
1
Accessories: Connectors
Description
Type
Order No.
Pcs./Pkt.
D-SUB connector (female connector), solder connection
SUBCON 9/F-SH
2761499
1
D-SUB connector (male connector), solder connection
SUBCON 9/M-SH
2761509
1
Accessories: Connectors as Replacement Item
Description
Type
Order No.
Pcs./Pkt.
Connector for the supply (4-pos. MINI COMBICON)
FK-MCP 1,5/5-STF-3,81
1851258
50
Connector for the supply (5-pos. MINI COMBICON)
FK-MCP 1,5/6-STF-3,81
1851261
50
Connector for digital 4-channel or 16-channel Inline input terminals, with color
print
IB IL SCN-12-ICP
2727611
10
Inline Block IO module for INTERBUS
with 16 digital inputs; bus connection via D-SUB connectors
Accessories: Other
Description
Type
Order No.
Pcs./Pkt.
CLIPFIX 35-5
3022276
50
Documentation
Description
Type
Order No.
Pcs./Pkt.
"Mounting and Removing Inline Block IO Modules" application note
AH ILB INSTALLATION
9014931
1
1
Recommended end clamp; placed both to the right and left of the module to
secure it on the DIN rail
"INTERBUS Addressing" data sheet
DB GB IBS SYS ADDRESS
9000990
"Addressing of 16-Channel ILB Modules" application note
AH ILB 24 DI/DO 16 ADDRESS
9014962
1
"General Introduction to the INTERBUS System" user manual
IBS SYS INTRO G4 UM E
2745211
1
"Configuring and Installing INTERBUS" user manual
IBS SYS PRO INST UM E
2743802
1
7118_en_02
PHOENIX CONTACT
2
ILB IB 24 DI16-DSUB
Technical Data
General Data
Housing dimensions with connectors (width x height x depth)
95 mm x 55 mm x 141 mm
Weight
254 g (with connectors)
Operating mode
Process data mode with 1 word
Transmission speed
500 kbps
Connection method for sensors
2 and 3-wire technology
Housing Dimensions
95
141
120
55
7118B003
Figure 1
Housing dimensions of the module (dimensions in mm)
Ambient Conditions
Regulations
Developed according to VDE 0160/EN 50178/IEC 62103, UL 508
Ambient temperature (operation)
-25°C to +60°C
Ambient temperature (storage/transport)
-25°C to +85°C
Humidity (operation/storage/transport)
10% to 95%, according to EN 61131-2
Air pressure (operation)
80 kPa to 108 kPa (up to 2000 m above sea level)
Air pressure (storage/transport)
66 kPa to 108 kPa (up to 3500 m above sea level)
Degree of protection according to IEC 60529
IP20
Class of protection
Class 3 according to VDE 0106/IEC 60536
Air and creepage distances
According to DIN VDE 0110/IEC 60664, IEC 60664A,
DIN VDE 0160/EN 50178/IEC 62103
Housing material
Plastic, PVC-free, PBT, self-extinguishing (V0)
Pollution degree according to
EN 60664-1/IEC 60664-1, EN 61131-2/IEC 61131-2
2; condensation not permitted during operation
Surge voltage class
II
7118_en_02
PHOENIX CONTACT
3
ILB IB 24 DI16-DSUB
Electrical Isolation/Isolation of the Voltage Areas
Test Distance
Test Voltage
Incoming remote bus / outgoing remote bus
500 V AC, 50 Hz, 1 min
Incoming remote bus / I/O
500 V AC, 50 Hz, 1 min
Incoming remote bus / functional earth ground
500 V AC, 50 Hz, 1 min
Outgoing remote bus / I/O
500 V AC, 50 Hz, 1 min
Outgoing remote bus / functional earth ground
500 V AC, 50 Hz, 1 min
I/O / functional earth ground
500 V AC, 50 Hz, 1 min
Mechanical Requirements
Vibration test, sinusoidal vibrations according to
EN 60068-2-6/IEC 60068-2-6
5g load, 2.5 hours in each space direction
Shock test according to EN 60068-2-27/IEC 60068-2-27
25g load for 11 ms, half sinusoidal wave,
3 shocks in each space direction and orientation
Broadband noise according to EN 60068-2-64/IEC 60068-2-64
0.78g load, 2.5 hours in each space direction
Conformance With EMC Directive 89/336/EEC
Noise Immunity Test According to EN 61000-6-2
Electrostatic discharge (ESD)
EN 61000-4-2
IEC 61000-4-2
Criterion B
Electromagnetic fields
EN 61000-4-3
IEC 61000-4-3
Criterion A
Fast transients (burst)
EN 61000-4-4/
IEC 61000-4-4
Criterion B
6 kV contact discharge
8 kV air discharge
Field strength: 10 V/m
Remote bus: 2 kV
Power supply: 2 kV
I/O cables: 2 kV
Criterion A
All interfaces: 1 kV
Surge voltage
EN 61000-4-5
IEC 61000-4-5
Criterion B
DC supply lines: ± 0.5 kV/± 1.0 kV (symmetrical/asymmetrical)
Signal lines: ± 0.5 kV/± 0.5 kV (symmetrical/asymmetrical)
Conducted interference
EN 61000-4-6
IEC 61000-4-6
Criterion A
Test voltage 10 V
Noise Emission Test According to EN 61000-6-4
Noise emission of housing
EN 55022
Class B (residential)
Interface: INTERBUS
Incoming remote bus
Copper cable (RS-422), connected via 9-pos. D-SUB connector; supply
electrically isolated; shielding connected with a capacitor to functional earth
ground
Outgoing remote bus
Copper cable (RS-422), connected via 9-pos. D-SUB connector; supply
electrically isolated; shielding directly connected to functional earth ground
Recommended cable lengths
See INTERBUS system data in the IBS SYS INTRO G4 UM E user manual
7118_en_02
PHOENIX CONTACT
4
ILB IB 24 DI16-DSUB
24 V Module Supply (Communications Power and Sensor Supply; UL and US)
Nominal value
24 V DC
Tolerance
-15%/+20% according to EN 61131-2
Ripple
±5% according to EN 61131-2
Permissible range
19.2 V DC to 30.0 V DC
Current consumption at UL
60 mA
Current consumption at US
4A
Safety equipment for communications power
Surge protection and protection against polarity reversal
Safety equipment for sensor supply
Surge, overload and short-circuit protection
Connection
Via MINI-COMBICON connector
Digital Inputs
Number
16
Connection method for sensors
2 and 3-wire technology
Input design
According to EN 61131-2 Type 1
Definition of switching thresholds
Maximum low-level voltage
ULmax < 5 V
Minimum high-level voltage
UHmin > 15 V
Common potentials
Sensor supply US, ground
Nominal input voltage UIN
24 V DC
Permissible range
-30 V < UIN < +30 V DC
Nominal input current for UIN
5 mA, typical
Current flow
Linear in the range 1 V < UIN < 30 V
Delay time
≤ 500 µs
Permissible cable length to the sensor
100 m
Use of AC sensors
AC sensors in the voltage range < UIN are limited in application
Power Dissipation
Formula to Calculate the Power Dissipation of the Electronics
2
n
PTOT = 1.44 W + IS x 0.06 W + S 0.12 W
i=1
Where
PTOT
IS
i
n
Total power dissipation of the module
Current from the sensor supply
Continuous index
Number of set inputs (n = 1 to 16)
Limitation of Simultaneity, Derating
No limitation of simultaneity, no derating
Approvals
For the latest approvals, please visit www.download.phoenixcontact.com.
7118_en_02
PHOENIX CONTACT
5
ILB IB 24 DI16-DSUB
Internal Circuit Diagram
U L
B A
R C
Local Diagnostic and Status Indicators
R D
IN
B U S
E
1
1
1
2
O P C
8 x
8 x
U L
B A
R C
R D
I1
1
2
3
2
3
4
I2
2
3
4
I3
4
3
I4
4
5 V
2 4 V
D I1 ...8
U
U
L
D I9 ..1 6
U S
S
U L U S
IN T E R B U S
E
P W R
1 6 x
IN
Figure 3
7 1 1 8 A 0 0 5
Diagnostic and status indicators of the
ILB IB 24 DI16-DSUB module
7 1 1 8 B 0 0 2
Figure 2
Internal wiring of the terminal points
Designation
Color
Meaning
UL
Green
Communications power
RC
Green
Remote bus cable check
BA
Green
Bus active
RD
Yellow
Outgoing remote bus disabled
E
Red
US
Green
E
Red
Short circuit or overload of the
sensor supply
1 to 4
Yellow
Status indicators of the inputs
BUS
Key:
LED
OPC
Protocol chip (bus logic)
PWR
x x x
Power supply unit with electrical isolation
X X X
Undervoltage of the
sensor supply US
Sensor supply
IN
Optocoupler
Short-circuit-proof sensor supply
7118_en_02
PHOENIX CONTACT
6
ILB IB 24 DI16-DSUB
Connecting INTERBUS, the Supply, and
Sensors
1 .1
1 .
X 1
U L U S N C N C
1 .2
X 2
1
1 .3
0 V 0 V N C N C F E
1 .4
1
2
1 .1
2 .1
1 .2
2 .2
1 .3
2 .3
1 .4
2 .4
1 .5
2 .5
1 .5
1 .6
Terminal
Point
UL
US
NC
NC
2 .1
2 .2
2 .3
2 .4
2 .5
1 .6
2 .6
2 .6
5 -8
R E M O T E O U T
R E M O T E IN
IL B IB 2 4 D I1 6 -D S U B
d e r -N o .: 2 8 7 8 4
X 3
X 4
7 1 1 8 C 0 0 6
Figure 4
Terminal Point Assignment of the MINI-COMBICON
Connectors for the Connection of the Supply Voltages
(Connectors X1 and X2 in Figure 4 on page 7).
Terminal point assignment of the connectors
Terminal
Point
0V
0V
NC
NC
FE
Assignment
24 V communications power UL
24 V sensor supply US
Not used
Not used
Assignment
GND
GND
Not used
Not used
Functional earth ground
The terminal points for GND (0V) can have a
total current of 8 A per terminal point. The
maximum current carrying capacity of 8 A must
not be exceeded.
The supply points have the same ground
potential. All ground supplies on a module are
electrically connected with one another.
The communications power is also electrically
connected via all contacts. In this way it can
supply all potentials with just one supply
without the need for additional terminals, see
"Connection example" on page 9.
7118_en_02
PHOENIX CONTACT
7
ILB IB 24 DI16-DSUB
Terminal Point Assignment of the INTERBUS Connectors (Connectors X 3 and X4 in Figure 4 on page 7)
6
1
7
1
6
2
8
5
9
re
3
9
4
5
n o
re
re
A
B
D O
D O
D I
D I
s e rv e
G N D
t c o n
s e rv e
s e rv e
D O
D O
D I
D I
s e rv
G N D
t c o
s e rv
s e rv
re
d
n o
re
re
n .
d
d
6
1
7
2
3
n n .
e d
e d
1
6
8
e d
9
5
9
4
5
7 1 1 7 B 0 1 2
Figure 5
A
B
Assignment of the remote bus interfaces (DSUB connector)
Remote OUT (outgoing remote bus)
Remote IN (incoming remote bus)
Assignment Remark/Wire Color in the INTERBUS
Standard Cable
Receive
Green
DO
DO
Receive
Yellow
Transmit
Pink
DI
DI
Transmit
Gray
GND
Reference potential
Brown
Shield
Shield potential is connected with a
(incoming
capacitor to functional earth ground (FE) of
remote bus) the potential jumper.
Shield
Shield potential is directly connected to
(outgoing
functional earth ground (FE) of the potential
remote bus) jumper.
In order to assemble the connectors, proceed
as described in the IBS SYS PRO INST UM E
user manual.
Terminal Point Assignment of the Input Connectors (Connectors 5 to 8 in Figure 4 on page 7)
Terminal Point
Assignment
Connector 5
(I1)
Connector 6
(I2)
Connector 7
(I3)
Connector 8
(I4)
1.1, 2.1
1.1, 2.1
1.1, 2.1
1.1, 2.1
Signal input (IN)
1.2, 2.2
1.2, 2.2
1.2, 2.2
1.2, 2.2
Sensor supply for 2 and 3-wire termination
1.3, 2.3
1.3, 2.3
1.3, 2.3
1.3, 2.3
Ground contact (GND) for 3-wire termination
1.4, 2.4
1.4, 2.4
1.4, 2.4
1.4, 2.4
Signal input (IN)
1.5, 2.5
1.5, 2.5
1.5, 2.5
1.5, 2.5
Sensor supply for 2 and 3-wire termination
1.6, 2.6
1.6, 2.6
1.6, 2.6
1.6, 2.6
Ground contact (GND) for 3-wire termination
7118_en_02
PHOENIX CONTACT
8
ILB IB 24 DI16-DSUB
Connection Example
5
IN 1 4
F E
IN 1 5
+
8
+ 2 4 V
U
S
7
+ 2 4 V
U
6
L
7 1 1 8 A 0 1 0
Figure 6
Connection example
The numbers above the module illustration
identify the connector slots.
When connecting the sensors observe the
assignment of the terminal points to the
process data (see "Process Data" on page 10).
The module has an FE spring (metal clip) on
the bottom of the electronics base. This spring
creates an electrical connection to the DIN rail.
Use grounding terminals to connect the DIN
rail to protective earth ground. The module is
grounded when it is snapped onto the DIN rail.
To ensure reliable functional earth grounding
of the module even when the DIN rail is dirty or
the metal clip is damaged, Phoenix Contact
also recommends grounding the module via
one of the FE terminal points.
7118_en_02
PHOENIX CONTACT
9
ILB IB 24 DI16-DSUB
Programming Data
ID code
02hex (02dec)
Length code
01hex
Process data channel
16 bits
Input address area
1 word
Output address area
0 words
Parameter channel (PCP)
0 words
Register length (bus)
1 word
Process Data
For the assignment of the illustrated (byte.bit) view to your control or computer system, please refer to the
DB GB IBS SYS ADDRESS data sheet.
Please refer to the application note for addressing 16-channel ILB modules.
The documentation can be downloaded at www.download.phoenixcontact.com.
Assignment of the Terminal Points to the IN Process Data Word (Slots 5 to 8)
(Word.bit) view Word
Bit
(Byte.bit) view Byte
Bit
Module
Slot
Terminal point (signal)
Terminal point (+24 V)
Terminal point (GND)
Status indicator Slot
LED
15
7
14
13
12 11
Byte 0
4
3
10
9
Word 0
8
7
6
5
4
3
Byte 1
4
3
2
1
0
6
5
2
1
0
7
6
5
2
1
0
6 (I2)
5 (I1)
8 (I4)
7 (I3)
2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1
2.5 1.5 2.2 1.2 2.5 1.5 2.2 1.2 2.5 1.5 2.2 1.2 2.5 1.5 2.2 1.2
2.6 1.6 2.3 1.3 2.6 1.6 2.3 1.3 2.6 1.6 2.3 1.3 2.6 1.6 2.3 1.3
6
5
8
7
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
Diagnostics
Error Table With Diagnostic Data and Status Indicators
Error Type
Sensor voltage US too low
Diagnostic Data
I/O error message
Sensor supply short circuit
I/O error message
Status Indicators
US LED is OFF
E (PWR) LED is red
E (IN) LED of the sensor supply is red
© PHOENIX CONTACT 03/2007
7118_en_02
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
Phone: +49-(0) 5235-3-00 • Fax: +49-(0) 5235-3-4 12 00
www.phoenixcontact.com