IB IL SGI 2/F ...
D
1
CH
SGI 2/F
TR
Inline terminal with two fast analog input channels
for connecting strain gauges
2
CH
4x
AUTOMATION
Data sheet
7210_en_02
1
© PHOENIX CONTACT - 11/2008
Function description
The terminal is designed for use within an Inline station.
This terminal is a fast two-channel input module used to
connect load cells, force transducers, mass pressure
transducers, and similar devices based on strain gauges.
The strain gauges can be connected using 6 or 4-wire
technology. The strain gauge output signals are measured
in each bus cycle and updated in the process data (bussynchronous process data update). The terminal is
designed for control system applications with increased
speed requirements.
Features
–
–
–
–
–
–
–
Two inputs for the strain gauges
Sensor supply voltage provided by the terminal, no
external power supply required
Connection of strain gauges in 6 and 4-wire technology
Communication via either process data or parameter
channel (PCP)
Channels are configured independently of one another
using the bus system
Bus-synchronous process data update
Diagnostic indicators
There are two options for data exchange:
– Via process data (both inputs in one bus cycle)
– Via PCP (both inputs in the "Analog Values" PCP
object)
The measuring values are represented by standardized
16-bit values.
A short circuit in the strain gauge supply at one of the two channels also prevents measured data acquisition
at the other channel for the duration of the short circuit.
This data sheet only is valid in connection with the IL SYS INST UM E user manual (see "Documentation" on
page 3).
Make sure you always use the latest documentation.
It can be downloaded at www.download.phoenixcontact.com.
This data sheet is valid for all products listed on the following page.
IB IL SGI 2/F ...
Table of contents
1
2
3
4
Function description ................................................................................................................... 1
Ordering data.............................................................................................................................. 3
Technical data ............................................................................................................................ 4
Local diagnostic and status indicators and terminal point assignment....................................... 7
4.1
4.2
4.3
5
6
7
8
9
Local diagnostic and status indicators ........................................................................................................... 7
Function identification .................................................................................................................................... 7
Terminal point assignment ............................................................................................................................. 7
Internal circuit diagram ............................................................................................................... 8
Electrical isolation....................................................................................................................... 9
Installation instructions ............................................................................................................... 9
Connection notes................................................................................................................................................... 9
Connection examples ................................................................................................................10
9.1
9.2
9.3
9.4
6-wire connection (a strain gauge load cell per channel) ............................................................................ 10
6-wire connection (several strain gauge load cells per channel) ................................................................ 11
4-wire connection ......................................................................................................................................... 12
Permissible characteristics according to the jumper supply......................................................................... 13
10 Programming data/configuration data .......................................................................................13
11 Process data..............................................................................................................................13
12 OUT process data words...........................................................................................................14
12.1
12.2
12.3
Output word OUT1 (control word) ................................................................................................................ 14
Output word OUT2 and OUT3 (parameter word)......................................................................................... 15
Parameters for configuration........................................................................................................................ 15
13 IN process data words...............................................................................................................16
13.1
13.2
Input word IN1 (status word) ........................................................................................................................ 16
Input words IN2 and IN3 .............................................................................................................................. 16
14 PCP communication ..................................................................................................................18
14.1
14.2
Object dictionary .......................................................................................................................................... 18
Object description ........................................................................................................................................ 19
15 Startup/measuring jumper detuning ..........................................................................................21
16 Configuration and analog values ...............................................................................................21
7210_en_02
PHOENIX CONTACT
2
IB IL SGI 2/F ...
2
Ordering data
Products
Description
Type
Order No.
Pcs./Pkt.
Inline terminal with two analog input channels for connecting strain gauges,
without accessories,
transmission speed of 500 kbps
IB IL SGI 2/F
2878434
1
Inline terminal with two analog input channels for connecting strain gauges;
complete with accessories (connectors and labeling fields),
transmission speed of 500 kbps
IB IL SGI 2/F-PAC
2878638
1
Inline terminal with two analog input channels for connecting strain gauges,
without accessories,
transmission speed of 2 Mbps
IB IL SGI 2/F 2MBD
2878531
1
Inline terminal with two analog input channels for connecting strain gauges;
complete with accessories (connectors and labeling fields),
transmission speed of 2 Mbit/s
IB IL SGI 2/F-2MBD-PAC 2878735
1
You need two connectors with shield connection and two standard connectors for the IB IL SGI 2/F and IB IL SGI 2/F 2MBD terminals.
Accessories
Description
Type
Order No.
Inline shield connector for analog Inline terminals, without color print
IB IL SCN-6 SHIELD
2726353
Pcs./Pkt.
5
Connector for digital single-channel, two-channel or 8-channel Inline terminals
IB IL SCN-8
2726337
10
Shield connection clamp for applying the shield on busbars,
8 mm diameter
SK8
3025163
10
Shield connection clamp for applying the shield on busbars,
14 mm diameter
SK14
3025176
10
Shield connection clamp for applying the shield on busbars,
20 mm diameter
SK20
3025189
10
Shield connection clamp for applying the shield on busbars,
35 mm diameter
SK35
3026463
10
Support for assembly on DIN rails
for 10 mm x 3 mm busbars
AB-SK
3025341
10
Support for mounting on the NS 35/7,5 DIN rail,
for 10 mm x 3 mm busbars
AB-SK 65
3026489
10
Support for direct mounting with contact to the mounting surface
AB-SK/E
3026476
10
PEN conductor busbar,
3 mm x 10 mm, length: 1000 mm
NLS-CU 3/10
0402174
1
Power terminal, cross section: 0.5 - 4 mm², width: 7 mm
Color: Gray
AK 4
0404017
50
Power terminal, cross section: 0.5 - 4 mm², width: 7 mm,
Color: Green/yellow
AK G GNYE
0421029
50
Power terminal, cross section: 0.5 - 4 mm², width: 7 mm,
Color: Black
AKG 4 BK
0421032
50
Description
Type
Order No.
Pcs./Pkt.
"Automation terminals of the Inline product range" user manual
IL SYS INST UM E
2698737
1
Documentation
7210_en_02
PHOENIX CONTACT
3
IB IL SGI 2/F ...
3
Technical data
General data
Housing dimensions (width x height x depth)
48.8 mm x 120 mm x 71.5 mm
Weight
125 g without connectors; 190 g with connectors
Operating mode
Process data mode with 3 words/1 PCP word
Strain gauge connection method
6 and 4-wire technology
Ambient temperature (operation)
-25°C to +55 °C
Ambient temperature (storage/transport)
-25°C to +85 °C
Permissible humidity (operation/storage/transport)
10% to 95% according to DIN EN 61131-2
Permissible air pressure (operation/storage/transport)
70 kPa to 106 kPa (up to 3000 m above sea level)
Degree of protection
IP20 according to IEC 60529
Class of protection
Class 3 in acc. with VDE 0106, IEC 60536
Connection data for Inline connectors
Connection method
Spring-cage terminal
Conductor cross-section
0.2 mm2 to 1.5 mm2 (solid or stranded), 24 - 16 AWG
Interface
Local bus
Data routing
Transmission speed
IB IL SGI 2/F (-PAC)
500 kbps
IB IL SGI 2/F 2MBD (-PAC)
2 Mbps
Power consumption
500 kbps
2 Mbps
Communications power UL
7.5 V
7.5 V
Current consumption from UL
75 mA, typical
100 mA, typical
I/O supply voltage UANA
24 V DC
24 V DC
Current consumption at UANA
Without strain gauge
8 mA, typical
8 mA, typical
With maximum load of 60 Ω
32 mA (at UV = 5 V), typical
32 mA (at UV = 5 V), typical
0.755 W, typical
0.942 W, typical
Total power consumption
Supply of the module electronics and I/O through the bus coupler/power terminal
Connection method
Potential routing
Outputs
Number
2 voltage outputs (UV = 3.3 V, UV = 5 V)
Total impedance of the Inline terminal
> 58.3 Ω (typical)
Maximum current at UV = 3.3 V
Imax = 55 mA (typical)
Maximum current at UV = 5 V
Imax = 85 mA (typical)
7210_en_02
PHOENIX CONTACT
4
IB IL SGI 2/F ...
Analog inputs
Number
Two input channels for strain gauges
(four voltage inputs)
Connection of signals
6 or 4-wire, twisted pair shielded cable
Voltage inputs
Jumper difference Ud
Two, can be configured by selecting the characteristic and the jumper supply
Jumper voltage U0
3.3 V ± 0.5 V or 5 V ± 0.5 V
Characteristics
Unipolar
+1 mV/V, +2 mV/V, +3 mV/V, +4 mV/V
Bipolar
±1 mV/V, ±2 mV/V, ±3 mV/V, ±4 mV/V
Measured value representation
15 bits + sign bit
Process data update
Once every bus cycle (bus synchronous)
Bus cycle time
≥ 1 ms
Jumper difference input limit frequency
1.6 kHz (typical)
Tolerances at TA = 25 °C
Nominal characteristic value
Relative deviation in % related to the measuring range
final value
Typical
Maximum
Unipolar 1 mV/V, 2 mV/V, 3 mV/V, 4 mV/V
±0.1%
±0.3%
Bipolar ±1 mV/V, ±2 mV/V, ±3 mV/V, ±4 mV/V
±0.2%
±0.6%
The typical values contain the typical offset error, gain error and linearity error in the respective configuration related to the positive measuring range up to
100% of the nominal characteristic value. This data is valid for nominal operation (preferred mounting position, US = 24 V) with16-sample average value filter.
The maximum tolerance values represent the worst case measurement inaccuracy. Besides the maximum offset error, the gain error and the linearity error,
the maximum tolerance values also comprise the longtime drift as well as the maximum tolerances of the test and calibration equipment.
Please also observe the values for temperature drift and the tolerances influenced by EMI.
This data is valid for at least twelve months.
Additional tolerances influenced by electromagnetic fields
Type of electromagnetic interference
Relative deviation in % related to the measuring range
final value
Electromagnetic fields, field strength 10 V/m in acc. with EN 61000-4-3
< ±0.7%
Conducted interference, Class 3 (10 V test voltage)
according to EN 61000-4-6
< ±0.2%
Fast transients (burst) up to an interference voltage of ±2.2 kV
according to EN 61000-4-4
< ±0.3%
You can minimize the interference by connecting the sensor cable shield to the DIN rail in front of the terminal via a shield connection clamp
(see "Accessories" on page 3).
Temperature and drift response (TA = 25°C to 55°C)
Relative drift in ppm/K related to the measuring range
final value
Typical
Maximum
Unipolar 1 mV/V, 2 mV/V, 3 mV/V, 4 mV/V
15 ppm/K
50 ppm/K
Bipolar ±1 mV/V, ±2 mV/V, ±3 mV/V, ±4 mV/V
500 ppm/K
980 ppm/K
The typical values contain the typical offset value and gain value in the respective configuration in the temperature range from -25°C up to +55°C related to
the positive measuring range up to 100% of the nominal characteristic value. This data is valid for nominal operation (preferred mounting position, US = 24 V)
with16-sample average value filter.
The maximum tolerance values represent the worst case measurement inaccuracy. Besides the maximum offset drift and gain drift, they also comprise the
longtime drift as well as the maximum tolerances of the test and calibration equipment in the temperature range from -25°C up to +55°C.
7210_en_02
PHOENIX CONTACT
5
IB IL SGI 2/F ...
Protective equipment
Short-circuit protection
Yes
Electrical isolation
Common potentials
24 V main voltage UM, 24 V segment voltage US, and GND have the same potential. FE is a separate potential area.
Separate potentials in the terminal
Test distance
Test voltage
7.5 V supply (bus logic)/
±5 V analog supply (analog I/O)
600 V AC, 50 Hz, 1 min
7.5 V supply (bus logic) / functional earth ground
600 V AC, 50 Hz, 1 min
±5 V analog supply (analog I/O)/functional earth ground
600 V AC, 50 Hz, 1 min
Error messages to the higher-level control or computer system
Failure of the internal I/O voltage supply
Yes, I/O error message sent to the bus terminal
Failure of or insufficient communications power UL
Yes, I/O error message sent to the bus terminal
Error messages via process data
Peripheral fault/user error
Yes (see page 17)
Approvals
For the latest approvals, please visit www.download.phoenixcontact.com.
7210_en_02
PHOENIX CONTACT
6
IB IL SGI 2/F ...
4
Local diagnostic and status indicators and terminal point assignment
4.3
D
SGI 2/F
TR
CH1
CH2
D
1
CH
1
CH
2
SGI 2/F
TR
1
2
1.1
1
1
2.1
1.2
2
2
2.2
1.3
3
3
2.3
1.4
4
4
2.4
1, 3
2
1.1
1
1
2.1
1.2
2
2
2.2
1.3
3
3
2.3
1.4
4
4
2.4
2, 4
7210A002
Figure 1
4.1
Des.
D
TR
CH1
CH2
4.2
Terminal with an appropriate connector
Local diagnostic and status indicators
Color
Green
Green
Green
ON:
OFF:
Meaning
Diagnostics
PCP active
Diagnostic indicator of channel 1
Channel 1 OK
Channel 1 not connected or not supplied
or open circuit
Green Diagnostic indicator of channel 2
ON: Channel 2 OK
OFF: Channel 2 not connected or not supplied
or open circuit
Terminal point assignment
Terminal
Signal
points
Connectors 1 and 3
1.1
+UV
2.1
GNDUv
1.2
+U0
2.2
-U0
1.3
+Ud
2.3
-Ud
1.4, 2.4
FE
Connectors 2 and 4
1.1
5V
2.1
3.3 V
1.2, 2.2
+UV
1.3, 2.3
1.4, 2.4
–
FE
Assignment
Jumper supply UV
Jumper voltage U0
Jumper difference Ud
Shielding
Optional voltages to supply the
jumper
Routing of the selected supply
voltage to the "Jumper supply UV"
connection on connector 1 or 3
Not used
Shielding
Connect the terminal point of the selected
voltage for the jumper supply to terminal point
+UV on connector 2 (or 4). Terminal points +UV
on slot 2 (or 4) are connected internally to
terminal point +UV on slot 1 (or 3) (see
Figure 2). Therefore, the selected voltage at
+UV is available on slot 1 (or 3) (see also
"Connection examples" on page 10).
Function identification
Green
2 Mbps: White stripe in the vicinity of the D LED
7210_en_02
PHOENIX CONTACT
7
IB IL SGI 2/F ...
5
Internal circuit diagram
Local bus
OPC
SRE 1
UL+
UANA
UL-
Level Adaptation 3V/5V
24 V
REF
+5 V
µC
AGND
Supervisor
MUX
+3,3 V
AGND
AGND
+24 V (US)
+24 V (UM)
7210B003
Figure 2
Internal circuit diagram
Key:
OPC
S R E
1
Level Adaptation 3V/5V
S u p e r v is o r
Protocol chip
Analog/digital converter
Register expansion
R E F
Reference voltage
Level adaptation
M U X
Multiplexer
Hardware monitoring
Amplifier
x x x
µ C
Microcontroller
X X X
DC/DC converter
with electrical isolation
Optocoupler
Other symbols used are explained in the
IL SYS INST UM E user manual.
7210_en_02
PHOENIX CONTACT
8
IB IL SGI 2/F ...
6
Electrical isolation
8
Connection notes
Connecting the strain gauges
Connect the strain gauges using shielded
twisted pair cables.
Shield connection
Only connect the shielding at one point,
preferably to the terminal. If the shield is
securely connected to the sensor, insulate the
shield on the terminal side.
Figure 3
7
Electrical isolation of the individual function
areas
Installation instructions
Unused channels
For unused channels, follow the instructions for
parameterization (see notes on bit 15 on page 15).
High current flowing through potential jumpers UM and US
leads to a temperature rise in the potential jumpers and
inside the terminal. Observe the following instructions to
keep the current flowing through the potential jumpers of
the analog terminals as low as possible:
Create a separate main circuit for the
analog terminals
If this is not possible in your application and if
you are using analog terminals in a main circuit
together with other terminals, place the analog
terminals after all the other terminals at the end
of the main circuit.
7210_en_02
PHOENIX CONTACT
9
IB IL SGI 2/F ...
9
Connection examples
The IB IL SGI 2/F terminal can measure both unipolar and bipolar jumper differences. Observe the polarity
when connecting +Ud and -Ud.
If the analog terminal expects unipolar jumper differences, the signal excursion may be negative in the worstcase scenario. The measured value would therefore always be 0. In this case, adapt the signal excursion to
the input voltage range by switching cables +Ud and -Ud.
If the analog terminal is set to a bipolar jumper difference, the signal excursion may be mixed up in the sign bit
in the worst-case scenario. In this case, adapt the signal excursion to the input voltage range again by switching
cables +Ud and -Ud.
Connections +U0 and -U0 are led back to a unipolar input. If the cables are mixed up, the terminal indicates a
configuration error.
9.1
6-wire connection (several strain gauge load cells per channel)
Connector
Channel
RL
Strain gauge 1
R
R
+UV
+U0
+Ud
Ud U0 UV
4
3
2
1
2
1
11
11
11
1
2
22
22
22
2
3
33
33
33
3
-Ud
-U0
GNDUv
FE
R
1
4
44
44
44
4
RL
Strain gauge 2
+UV
+U0
+Ud
-Ud
-U0
GNDUv
FE
R
R
R
R
UV U0 Ud
R
RL
RL
7210D005
Figure 4
Connection of strain gauges in 6-wire technology
RL: Cable resistance
Channel 1: Connect the strain gauge to connector 1 using 6-wire technology. At connector 2 select the jumper supply level.
The terminal provides supply voltages of 5 V and 3.3 V. Connections +UV of connector 1 and +UV of connector 2 are
connected internally. At connector 2, connect either 5 V or 3.3 V to +UV. This supplies the 6-wire connection of channel 1
with power.
Channel 2: Connect the strain gauge to connector 3 using 6-wire technology. At connector 4 select the jumper supply level.
The terminal provides supply voltages of 5 V and 3.3 V. Connections +UV of connector 3 and +UV of connector 4 are
connected internally. At connector 4, insert a jumper to connect either 5 V or 3.3 V to +UV. This supplies the 6-wire
connection of channel 2 with power.
Channels 1 and 2 can be supplied with different supply voltages (5 V or 3.3 V).
7210_en_02
PHOENIX CONTACT
10
IB IL SGI 2/F ...
9.2
6-wire connection (several strain gauge load cells per channel)
Connector
Channel
RL
Strain gauge 1
R
R
+UV
+U0
+Ud
Ud U0 UV
2
1
1
11
11
2
22
22
3
33
33
4
44
44
-Ud
-U0
GNDUv
FE
R
1
R
RL
RL
Strain
gauge 2
r
R
R
Ud U0 UV
Distribution
R
R
RL
RL
Strain gauge n
R
R
Ud U0 UV
R
R
7210A008
RL
Figure 5
Connection of several strain gauges in 6-wire technology
RL: Cable resistance
In this operating mode you may connect several strain gauge load cells in parallel to connector 1 (channel 1)
and/or connector 3 (channel 2), depending on the impedance of the strain gauge used.
Please note, that the total impedance of the wired Inline terminal (channel 1 and channel 2) must not be lower
than 58.3 Ω (typically).
7210_en_02
PHOENIX CONTACT
11
IB IL SGI 2/F ...
Channel 1: Connect the required number of strain gauges in parallel to connector 1 using 6-wire technology. At
connector 2 select the jumper supply level. The terminal provides supply voltages of 5 V and 3.3 V. Connections +UV of
connector 1 and +UV of connector 2 are connected internally. At connector 2, connect either 5 V or 3.3 V to +UV. This
supplies the 6-wire connection of channel 1 with power.
Channel 2: Connect the required number of strain gauges to connector 3 using 6-wire technology. At connector 4 select
the jumper supply level. The terminal provides supply voltages of 5 V and 3.3 V. Connections +UV of connector 3 and +UV
of connector 4 are connected internally. At connector 4, insert a jumper to connect either 5 V or 3.3 V to +UV. This supplies
the 6-wire connection of channel 2 with power.
Channels 1 and 2 can be supplied with different supply voltages (5 V or 3.3 V).
9.3
4-wire termination
Connector
1
Channel
Strain gauge 1
R
RL
R
4
3
2
1
2
1
11
11
11
1
2
22
22
22
2
+UV
+Ud
Ud
UV
+UV
3
33
33
33
-Ud
R
3
4
44
44
44
Strain gauge 2
R
R
R
R
+Ud
-Ud
GNDUv
FE
RL
UV
Ud
GNDUv
4 FE
R
RL
RL
7210D006
Figure 6
Connection of strain gauges in 4-wire technology (channel 1 and channel 2)
RL: Cable resistance
Channel 1/channel 2: Strain gauges can also be connected to the terminal in 4-wire technology. In this case, connect
connections +UV to +U0 and GNDUv to -U0 (magnified in the diagram for channel 2) at the connector for the relevant
channel (connector 2 and/or 3).
There is no temperature and long-term drift compensation for the connecting cable in 4-wire technology.
7210_en_02
PHOENIX CONTACT
12
IB IL SGI 2/F ...
9.4
Permissible characteristics according to the jumper supply
The table below indicates which characteristic can be configured for which jumper supply.
Characteristic
+1 mV/V
±1 mV/V
+2 mV/V
±2 mV/V
+3 mV/V
±3 mV/V
+4 mV/V
±4 mV/V
10
UV = 3.3 V
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Programming data/configuration data
Local bus (INTERBUS))
ID code
Length code
Process data channel
Input address area
Output address area
Parameter channel (PCP)
Register length (bus)
11
UV = 5 V
Yes
Yes
Yes
Yes
Yes
No
Yes
No
Other bus systems
DFhex (223dec)
03hex
48 bits
3 words
3 words
1 word
4 words
For the programming/configuration data of
other bus systems, please refer to the
corresponding electronic device data sheet
(e.g., GSD, EDS).
Process data
The terminal occupies three process data words and one PCP word.
Figure 7
7210_en_02
Order of the process data words
PHOENIX CONTACT
13
IB IL SGI 2/F ...
12
OUT process data output words
Three OUT process data words are available.
Configure the terminal channels via the OUT process data words.
Where:
– Output word OUT1 contains the command
– Output word OUT2 contains the parameters for channel 1
– Output word OUT3 contains the parameters for channel 2
The following configurations are possible:
Configuration
Short designation
Selection of mean value generation (filtering)
Filter
Characteristic for calculating the gain (see "Startup/measuring jumper Characteristic
detuning" on page 21)
Default
16-sample mean value
±2 mV/V
Configuration errors are indicated in the status word. The configuration settings are stored in a volatile memory.
If you change the configuration, the message "Measured value invalid" appears (diagnostic code 8004hex), until new
measured values are available.
12.1
Output word OUT1 (control word)
OUT1
Bit
15
14
13
12
11
10
9
Command code
Assignment
8
7
6
5
4
3
2
1
0
0
0
0
0
0
0
0
0
Bit 15 to bit 8 (command code):
0
0
Bit 15 to bit 8
0
0
0
0
0
0
OUT1
0000hex
0
0
0
1
0
0
0
C 1x00hex
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
0
0
0
0
1
0
0
0
0
1
0
0
1
1
0
0
1
0
1
0
3000hex
3100hex
3200hex
3300hex
3C00hex
0
1
0
0
0
0
0
0
4000hex
Command function
Read measured values
Read configuration channel-by-channel in IN2
(C = Channel number; 0 = Channel 1, 1 = Channel 2)
Read min. value; IN2: Min. value channel 1, IN3: Min. value channel 2
Read max. value; IN2: Max. value channel 1, IN3: Max. value channel 2
Delete minimum and maximum value of channel 1
Delete minimum and maximum value of channel 2
Read firmware version and module ID in IN2.
Configure device;
configuration for channel 1 in OUT2 and for channel 2 in OUT3
During the transient response (e.g., following a configuration command), the fluctuating measured values may
exceed the minimum and maximum values. Therefore, at the start of acquisition delete the minimum and
maximum values using command 3200hex and/or 3300hex.
One measurement is performed for each bus cycle.
7210_en_02
PHOENIX CONTACT
14
IB IL SGI 2/F ...
12.2
Output word OUT2 and OUT3 (parameter word)
For command 4000hex the parameters must be specified in OUT2 and OUT3. This parameter word is only evaluated for
this command.
OUT2 and OUT3
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
Assignment
1
0
0
0
0
0
0
Filter
0
0
0
0
0
Characteristic
Bit 15
1
0
The set bit ensures that the relevant channel is configured.
In the event that only one channel is used and there is no jumper supply at the other channel due to missing
wire jumpers, the configuration is acknowledged negatively in the status word. In this case, set bit 15 of the
configuration word of the unused channel to 0 to remedy the situation.
Filter
Selection of mean value generation. After every conversion, the measured value is saved in a mean value
memory via which the mean value is generated. The memory size can be selected with the filter option. E.g.,
for a 16-sample mean value, the mean value is generated using the last 16 measured values.
Character- Depending on the characteristic in relation to the available jumper supply, the terminal calculates the required
istic
gain for the configured input and thus has the best possible resolution in the unipolar and bipolar area.
If in the unipolar area the strain gauge is supplied with a load greater than 130% or a negative load, the
jumper detuning is outside the measuring range and an error is triggered.
If in the bipolar area the strain gauge is supplied with a load greater than 130% in the positive or negative
direction, the jumper detuning is outside the measuring range and an error is triggered.
If invalid parameters are specified in the parameter word, the command will not be executed. The command is
acknowledged in the input words with the error bit set.
12.3
Parameters for configuration
The values in bold are default settings.
Bit 15:
Code
dec
bin
0
0
1
1
Bit 3 to bit 0:
Configure
Channel is not configured
Channel is configured
Bit 8:
Code
dec
bin
0
0
1
1
7210_en_02
Filter
No mean value
16-sample mean value
Code
dec
bin
0
000
1
001
2
010
3
011
4
100
5
101
6
110
7
111
Characteristic
+1 mV/V
±1 mV/V
+2 mV/V
±2 mV/V
+3 mV/V
±3 mV/V
+4 mV/V
±4 mV/V
PHOENIX CONTACT
15
IB IL SGI 2/F ...
13
IN process data input words
13.1
Input word IN1 (status word)
Input word IN1 performs the task of a status word.
IN1
Bit
15
Assignment
EB
14
13
12
11
10
9
8
Mirroring of the command code
7
6
5
4
3
2
1
0
0
0
0
0
0
0
0
0
EB: Error bit
EB = 0
EB = 1
No error has occurred.
An error has occurred.
Mirroring of the command code:
A command code mirrored from the control word. Here, the MSB is suppressed.
The set error bit indicates an invalid configuration value for command 4000hex. Possible reasons:
– At least one of bits 3 - 7 or 9 - 14 is set
– The jumper voltage is not 3.3 V ± 0.5 V or 5 V ± 0.5 V.
– The characteristic value is 5 or 7 and the jumper voltage is 5 V ± 0.5 V.
– The terminal has already been configured with PCP using the "Config Table" object.
13.2
Input words IN2 and IN3
The measured values, configuration or firmware version are transmitted to the controller board or the PC via process data
input words IN2 to IN3 according to the configuration.
For control word 3C00hex, IN2 provides the firmware version and the module ID.
Example: Firmware version 1.23:
IN2
Bit
Assignment
(hex)
Meaning
7210_en_02
15
14
13
1
12
11
10
9
8
2
Firmware version 1.23
7
6
5
3
4
3
2
1
0
1
Module ID
PHOENIX CONTACT
16
IB IL SGI 2/F ...
The measured values are available in IB IL format.
The measured value is represented in bits 14 to 0. An additional bit (bit 15) is available as a sign bit.
MSB
15 14
SB
MSB
LSB
SB
13
12
11
10
9
8
7
6
Analog value
5
4
3
2
1
LSB
0
Most significant bit
Least significant bit
Sign bit
This format supports extended diagnostics. Values >8000hex and 130.048
+ 130.048
+ 100.000
+ 1.000
+ 0.004
0.0
- 0.004
- 100.000
-130.048
< -130.048
–
Detuning for all unipolar
characteristics
[%]
> 130.048
+ 130.048
+ 100.000
+ 1.000
+ 0.004
0.0
–
–
–
–
–
To calculate the detuning as a percentage for other
measured values, please use the following formula:
Detuning = Process data value * 0.004 or
Detuning = Process data value/250
IB input word
[Hex]
IB input word
[dec]
8001
7F00
61A8
00FA
0001
0000
FFFF
9E58
8100
8080
8002
Overrange
32512
25000
250
1
0
-1
-25000
-32512
Underrange
Open circuit
Example:
Characteristic:
Process data value:
2m V/V
10000dec
Detuning = 10000/250 = 40%
40% of 2 mV/V = 0.8 mV/V
7210_en_02
PHOENIX CONTACT
17
IB IL SGI 2/F ...
14
PCP communication
For information on PCP communication, please refer to the IBS SYS PCP G4 UM E (Order No. 2745169) and
IBS PCP COMPACT UM E (Order No. 9015349) user manuals.
By default upon delivery, the terminal is configured according to the default settings on page 14. The terminal can be
configured using process data or PCP to suit your application.
In PCP mode, the terminal is configured with the "Config Table" object.
The programs IBS CMD (for standard controller boards) and IBS PC WORX (for Field Controllers [FC] and
Remote Field Controllers [RFC]) are available for the configuration and parameterization of your INTERBUS
system.
For additional information, please refer to the IBS CMD SWT G4 UM E user manual and the documentation for
the version of PC WorX used.
14.1
Object dictionary
Index
0080hex
0081hex
Data type
Array of Unsigned 16
Array of Unsigned 16
N
4
2
L
2
2
Meaning
Terminal configuration
Analog values of the
channels
N:
Number of elements
rd:
Read access permitted
L:
Length of an element in bytes
wr:
Write access permitted
7210_en_02
Object name
Config Table
Analog Values
Rights
rd/wr
rd
PHOENIX CONTACT
18
IB IL SGI 2/F ...
14.2
Object descriptions
Config Table object
Configure the terminal using this object.
Object description:
Object
Config Table
Access
Read, write
Data type
Array of Unsigned 16
Index
0080hex
Subindex
00hex
01hex
02hex
03hex
04hex
Write all elements
Configuration of channel 1
Configuration of channel 2
Reserved
Reserved
Length (bytes)
08hex02hex
Subindex 00hex
Subindex 01hex to 04hex
Data
Terminal configuration
4 x 2 bytes
Element value range
The "Configuration channel x" elements are structured as follows:
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Assignment
1
0
0
0
0
0
0
Filter
0
0
0
0
0
Characteristic
For the value ranges of the individual parameters, please refer to Section "Parameters for configuration" on page 15.
If an invalid configuration is specified, a negative confirmation is generated with error message 08hex, 00hex or xx30hex. The
low byte of the additional error code is 30hex (value is out of range), the high byte contains the number of the affected
element.
Example: Config Table is completely filled with data (subindex 00) and the entry for channel 2 is invalid. In this case, the
additional error code is equal to 0230hex.
7210_en_02
PHOENIX CONTACT
19
IB IL SGI 2/F ...
Analog Values object
The elements of this object contain the analog values of the channels in IB IL format.
Object description:
Object
Analog Values
Access
Read
Data type
Array of Unsigned 16
Index
0081hex
Subindex
00hex
01hex
02hex
Read all elements
Analog value of channel 1
Analog value of channel 2
Length (bytes)
04hex02hex
Subindex 00hex
Subindex 01hex to 02hex
Data
Analog values of the channels
7210_en_02
2 x 2 bytes
PHOENIX CONTACT
20
IB IL SGI 2/F ...
15
Startup/measuring jumper detuning
To start the terminal, proceed as follows:
•
Install the terminal within the Inline station. To do so, proceed as described in the package slip.
•
Connect the strain gauge in 6 or 4-wire technology (see "Connection examples" on page 10).
•
Connect the voltage to the Inline station.
•
On this power up the terminal is configured with the default values.
•
If you do not wish to operate the terminal with the default values, configure the terminal via process data
(see "OUT process data output words" on page 14) or PCP (see "PCP communication" on page 18).
•
Jumper detuning can now be measured.
Jumper detuning can only be measured if the corresponding input is configured. To configure the input, the
jumper supply UV must be present.
16
Configuration and analog values
Terminal configuration is only required if at least one of the channels is to be operated outside the default values (see
"Parameters for configuration" on page 15).
You can configure the terminal either using process data or using PCP and transmit the analog values accordingly.
If you have configured the terminal via PCP, the configuration can no longer be modified using the process data.
For easy terminal configuration a function block can be downloaded at www.phoenixcontact.com.
Example 1: Configuring the terminal via process data
A strain gauge pressure force transducer for control system applications is connected to channel 1. Its data sheet specifies
a characteristic of +2 mV/V at a nominal load of 500 N. The following configuration is thus selected for channel 1:
Characteristic:
Filter:
Configuration value OUT2:
Channel 1
+2 mV/V
No mean-value generation
8002hex
A tractive and pressure force transducer with the characteristic ±4 mV/V at a load of 1 kN is connected to channel 2. The
following configuration is thus selected for channel 2:
Characteristic:
Filter:
Configuration value OUT3:
Channel 2
±4 mV/V
16-sample mean-value generation
8107hex
If both channels are operated in the default configuration, configuration is not required. When a configuration
command is sent, however, both channels will always be configured. Therefore also enter the corresponding
parameterization for the channel that is to be operated in the default configuration. If a "0" is transmitted for
channel 1 in bit 15 (do not configure, see bit 15 on page 15), the channel does not provide any values in the
following.
7210_en_02
PHOENIX CONTACT
21
IB IL SGI 2/F ...
Step
1
2
3
4
5
Process data
OUT3 = 8107hex
OUT2 = 8003hex
OUT1 = 4000hex
Wait until IN1 = 4000hex
OUT1 = 0000hex
Wait until IN1 = 0000hex
Measured value channel 1 = IN2
Measured value channel 2 = IN3
If the measured value = 80xxhex, this corresponds to an
error message
Meaning
Specify configuration
Wait for confirmation
Requesting measured values
Wait for confirmation
Read measured values
Channel 1
Read measured value IN2:
Current jumper detuning:
5A78hex (= 23160dec)
= IN2 * 0.004% * characteristic
= 23160 * 0.004% * 2 mV/V
= 1.853 mV/V
= IN2 * 0.004% * nominal load
= 23160 * 0.004% * 500 N
= 463.2 N
Current load:
Channel 2
CBDEhex (= 52190dec); following evaluation of the MSB: -19422dec
= IN3 * 0.004% * characteristic
= -19422 * 0.004% * 4 mV/V
= -3.11 mV/V
= IN3 * 0.004% * nominal load
= -19422 * 0.004% * 1 kN
= -776.9 N
Read measured value IN3:
Current jumper detuning:
Current load:
Example 2: Minimum/maximum evaluation
The channel 1 and channel 2 pressure transducers are loaded and unloaded several times. Only the maximum load is of
interest during the entire process.
Step
1
2
3
4
5
6
7
8
Process data
OUT1 = 3200hex
Wait until IN1 = 3200hex
OUT1 = 3300hex
Wait until IN1 = 3300hex
OUT1 = 3100hex
Wait until IN1 = 3100hex
Maximum value of channel 1 = IN2
Maximum value of channel 2 = IN3
Meaning
Delete minimum and maximum values of channel 1
Wait for confirmation
Delete minimum and maximum values of channel 2
Wait for confirmation
Load and unload channel 1 and 2 pressure transducers
Read maximum values
Wait for confirmation
Read maximum value; to calculate the current jumper
detuning and the current load, see above.
If measured value = 80xxhex, then error message
© PHOENIX CONTACT 11/2008
7210_en_02
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
Phone: +49-(0) 5235-3-00 • Fax: +49-(0) 5235-3-4 12 00
www.phoenixcontact.com
22