0
登录后你可以
  • 下载海量资料
  • 学习在线课程
  • 观看技术视频
  • 写文章/发帖/加入社区
创作中心
发布
  • 发文章

  • 发资料

  • 发帖

  • 提问

  • 发视频

创作活动
2878735

2878735

  • 厂商:

    PHOENIX(菲尼克斯)

  • 封装:

    -

  • 描述:

    I/OMODULE2ANALOG2ANALOG24V

  • 数据手册
  • 价格&库存
2878735 数据手册
IB IL SGI 2/F ... D 1 CH SGI 2/F TR Inline terminal with two fast analog input channels for connecting strain gauges 2 CH 4x AUTOMATION Data sheet 7210_en_02 1 © PHOENIX CONTACT - 11/2008 Function description The terminal is designed for use within an Inline station. This terminal is a fast two-channel input module used to connect load cells, force transducers, mass pressure transducers, and similar devices based on strain gauges. The strain gauges can be connected using 6 or 4-wire technology. The strain gauge output signals are measured in each bus cycle and updated in the process data (bussynchronous process data update). The terminal is designed for control system applications with increased speed requirements. Features – – – – – – – Two inputs for the strain gauges Sensor supply voltage provided by the terminal, no external power supply required Connection of strain gauges in 6 and 4-wire technology Communication via either process data or parameter channel (PCP) Channels are configured independently of one another using the bus system Bus-synchronous process data update Diagnostic indicators There are two options for data exchange: – Via process data (both inputs in one bus cycle) – Via PCP (both inputs in the "Analog Values" PCP object) The measuring values are represented by standardized 16-bit values. A short circuit in the strain gauge supply at one of the two channels also prevents measured data acquisition at the other channel for the duration of the short circuit. This data sheet only is valid in connection with the IL SYS INST UM E user manual (see "Documentation" on page 3). Make sure you always use the latest documentation. It can be downloaded at www.download.phoenixcontact.com. This data sheet is valid for all products listed on the following page. IB IL SGI 2/F ... Table of contents 1 2 3 4 Function description ................................................................................................................... 1 Ordering data.............................................................................................................................. 3 Technical data ............................................................................................................................ 4 Local diagnostic and status indicators and terminal point assignment....................................... 7 4.1 4.2 4.3 5 6 7 8 9 Local diagnostic and status indicators ........................................................................................................... 7 Function identification .................................................................................................................................... 7 Terminal point assignment ............................................................................................................................. 7 Internal circuit diagram ............................................................................................................... 8 Electrical isolation....................................................................................................................... 9 Installation instructions ............................................................................................................... 9 Connection notes................................................................................................................................................... 9 Connection examples ................................................................................................................10 9.1 9.2 9.3 9.4 6-wire connection (a strain gauge load cell per channel) ............................................................................ 10 6-wire connection (several strain gauge load cells per channel) ................................................................ 11 4-wire connection ......................................................................................................................................... 12 Permissible characteristics according to the jumper supply......................................................................... 13 10 Programming data/configuration data .......................................................................................13 11 Process data..............................................................................................................................13 12 OUT process data words...........................................................................................................14 12.1 12.2 12.3 Output word OUT1 (control word) ................................................................................................................ 14 Output word OUT2 and OUT3 (parameter word)......................................................................................... 15 Parameters for configuration........................................................................................................................ 15 13 IN process data words...............................................................................................................16 13.1 13.2 Input word IN1 (status word) ........................................................................................................................ 16 Input words IN2 and IN3 .............................................................................................................................. 16 14 PCP communication ..................................................................................................................18 14.1 14.2 Object dictionary .......................................................................................................................................... 18 Object description ........................................................................................................................................ 19 15 Startup/measuring jumper detuning ..........................................................................................21 16 Configuration and analog values ...............................................................................................21 7210_en_02 PHOENIX CONTACT 2 IB IL SGI 2/F ... 2 Ordering data Products Description Type Order No. Pcs./Pkt. Inline terminal with two analog input channels for connecting strain gauges, without accessories, transmission speed of 500 kbps IB IL SGI 2/F 2878434 1 Inline terminal with two analog input channels for connecting strain gauges; complete with accessories (connectors and labeling fields), transmission speed of 500 kbps IB IL SGI 2/F-PAC 2878638 1 Inline terminal with two analog input channels for connecting strain gauges, without accessories, transmission speed of 2 Mbps IB IL SGI 2/F 2MBD 2878531 1 Inline terminal with two analog input channels for connecting strain gauges; complete with accessories (connectors and labeling fields), transmission speed of 2 Mbit/s IB IL SGI 2/F-2MBD-PAC 2878735 1 You need two connectors with shield connection and two standard connectors for the IB IL SGI 2/F and IB IL SGI 2/F 2MBD terminals. Accessories Description Type Order No. Inline shield connector for analog Inline terminals, without color print IB IL SCN-6 SHIELD 2726353 Pcs./Pkt. 5 Connector for digital single-channel, two-channel or 8-channel Inline terminals IB IL SCN-8 2726337 10 Shield connection clamp for applying the shield on busbars, 8 mm diameter SK8 3025163 10 Shield connection clamp for applying the shield on busbars, 14 mm diameter SK14 3025176 10 Shield connection clamp for applying the shield on busbars, 20 mm diameter SK20 3025189 10 Shield connection clamp for applying the shield on busbars, 35 mm diameter SK35 3026463 10 Support for assembly on DIN rails for 10 mm x 3 mm busbars AB-SK 3025341 10 Support for mounting on the NS 35/7,5 DIN rail, for 10 mm x 3 mm busbars AB-SK 65 3026489 10 Support for direct mounting with contact to the mounting surface AB-SK/E 3026476 10 PEN conductor busbar, 3 mm x 10 mm, length: 1000 mm NLS-CU 3/10 0402174 1 Power terminal, cross section: 0.5 - 4 mm², width: 7 mm Color: Gray AK 4 0404017 50 Power terminal, cross section: 0.5 - 4 mm², width: 7 mm, Color: Green/yellow AK G GNYE 0421029 50 Power terminal, cross section: 0.5 - 4 mm², width: 7 mm, Color: Black AKG 4 BK 0421032 50 Description Type Order No. Pcs./Pkt. "Automation terminals of the Inline product range" user manual IL SYS INST UM E 2698737 1 Documentation 7210_en_02 PHOENIX CONTACT 3 IB IL SGI 2/F ... 3 Technical data General data Housing dimensions (width x height x depth) 48.8 mm x 120 mm x 71.5 mm Weight 125 g without connectors; 190 g with connectors Operating mode Process data mode with 3 words/1 PCP word Strain gauge connection method 6 and 4-wire technology Ambient temperature (operation) -25°C to +55 °C Ambient temperature (storage/transport) -25°C to +85 °C Permissible humidity (operation/storage/transport) 10% to 95% according to DIN EN 61131-2 Permissible air pressure (operation/storage/transport) 70 kPa to 106 kPa (up to 3000 m above sea level) Degree of protection IP20 according to IEC 60529 Class of protection Class 3 in acc. with VDE 0106, IEC 60536 Connection data for Inline connectors Connection method Spring-cage terminal Conductor cross-section 0.2 mm2 to 1.5 mm2 (solid or stranded), 24 - 16 AWG Interface Local bus Data routing Transmission speed IB IL SGI 2/F (-PAC) 500 kbps IB IL SGI 2/F 2MBD (-PAC) 2 Mbps Power consumption 500 kbps 2 Mbps Communications power UL 7.5 V 7.5 V Current consumption from UL 75 mA, typical 100 mA, typical I/O supply voltage UANA 24 V DC 24 V DC Current consumption at UANA Without strain gauge 8 mA, typical 8 mA, typical With maximum load of 60 Ω 32 mA (at UV = 5 V), typical 32 mA (at UV = 5 V), typical 0.755 W, typical 0.942 W, typical Total power consumption Supply of the module electronics and I/O through the bus coupler/power terminal Connection method Potential routing Outputs Number 2 voltage outputs (UV = 3.3 V, UV = 5 V) Total impedance of the Inline terminal > 58.3 Ω (typical) Maximum current at UV = 3.3 V Imax = 55 mA (typical) Maximum current at UV = 5 V Imax = 85 mA (typical) 7210_en_02 PHOENIX CONTACT 4 IB IL SGI 2/F ... Analog inputs Number Two input channels for strain gauges (four voltage inputs) Connection of signals 6 or 4-wire, twisted pair shielded cable Voltage inputs Jumper difference Ud Two, can be configured by selecting the characteristic and the jumper supply Jumper voltage U0 3.3 V ± 0.5 V or 5 V ± 0.5 V Characteristics Unipolar +1 mV/V, +2 mV/V, +3 mV/V, +4 mV/V Bipolar ±1 mV/V, ±2 mV/V, ±3 mV/V, ±4 mV/V Measured value representation 15 bits + sign bit Process data update Once every bus cycle (bus synchronous) Bus cycle time ≥ 1 ms Jumper difference input limit frequency 1.6 kHz (typical) Tolerances at TA = 25 °C Nominal characteristic value Relative deviation in % related to the measuring range final value Typical Maximum Unipolar 1 mV/V, 2 mV/V, 3 mV/V, 4 mV/V ±0.1% ±0.3% Bipolar ±1 mV/V, ±2 mV/V, ±3 mV/V, ±4 mV/V ±0.2% ±0.6% The typical values contain the typical offset error, gain error and linearity error in the respective configuration related to the positive measuring range up to 100% of the nominal characteristic value. This data is valid for nominal operation (preferred mounting position, US = 24 V) with16-sample average value filter. The maximum tolerance values represent the worst case measurement inaccuracy. Besides the maximum offset error, the gain error and the linearity error, the maximum tolerance values also comprise the longtime drift as well as the maximum tolerances of the test and calibration equipment. Please also observe the values for temperature drift and the tolerances influenced by EMI. This data is valid for at least twelve months. Additional tolerances influenced by electromagnetic fields Type of electromagnetic interference Relative deviation in % related to the measuring range final value Electromagnetic fields, field strength 10 V/m in acc. with EN 61000-4-3 < ±0.7% Conducted interference, Class 3 (10 V test voltage) according to EN 61000-4-6 < ±0.2% Fast transients (burst) up to an interference voltage of ±2.2 kV according to EN 61000-4-4 < ±0.3% You can minimize the interference by connecting the sensor cable shield to the DIN rail in front of the terminal via a shield connection clamp (see "Accessories" on page 3). Temperature and drift response (TA = 25°C to 55°C) Relative drift in ppm/K related to the measuring range final value Typical Maximum Unipolar 1 mV/V, 2 mV/V, 3 mV/V, 4 mV/V 15 ppm/K 50 ppm/K Bipolar ±1 mV/V, ±2 mV/V, ±3 mV/V, ±4 mV/V 500 ppm/K 980 ppm/K The typical values contain the typical offset value and gain value in the respective configuration in the temperature range from -25°C up to +55°C related to the positive measuring range up to 100% of the nominal characteristic value. This data is valid for nominal operation (preferred mounting position, US = 24 V) with16-sample average value filter. The maximum tolerance values represent the worst case measurement inaccuracy. Besides the maximum offset drift and gain drift, they also comprise the longtime drift as well as the maximum tolerances of the test and calibration equipment in the temperature range from -25°C up to +55°C. 7210_en_02 PHOENIX CONTACT 5 IB IL SGI 2/F ... Protective equipment Short-circuit protection Yes Electrical isolation Common potentials 24 V main voltage UM, 24 V segment voltage US, and GND have the same potential. FE is a separate potential area. Separate potentials in the terminal Test distance Test voltage 7.5 V supply (bus logic)/ ±5 V analog supply (analog I/O) 600 V AC, 50 Hz, 1 min 7.5 V supply (bus logic) / functional earth ground 600 V AC, 50 Hz, 1 min ±5 V analog supply (analog I/O)/functional earth ground 600 V AC, 50 Hz, 1 min Error messages to the higher-level control or computer system Failure of the internal I/O voltage supply Yes, I/O error message sent to the bus terminal Failure of or insufficient communications power UL Yes, I/O error message sent to the bus terminal Error messages via process data Peripheral fault/user error Yes (see page 17) Approvals For the latest approvals, please visit www.download.phoenixcontact.com. 7210_en_02 PHOENIX CONTACT 6 IB IL SGI 2/F ... 4 Local diagnostic and status indicators and terminal point assignment 4.3 D SGI 2/F TR CH1 CH2 D 1 CH 1 CH 2 SGI 2/F TR 1 2 1.1 1 1 2.1 1.2 2 2 2.2 1.3 3 3 2.3 1.4 4 4 2.4 1, 3 2 1.1 1 1 2.1 1.2 2 2 2.2 1.3 3 3 2.3 1.4 4 4 2.4 2, 4 7210A002 Figure 1 4.1 Des. D TR CH1 CH2 4.2 Terminal with an appropriate connector Local diagnostic and status indicators Color Green Green Green ON: OFF: Meaning Diagnostics PCP active Diagnostic indicator of channel 1 Channel 1 OK Channel 1 not connected or not supplied or open circuit Green Diagnostic indicator of channel 2 ON: Channel 2 OK OFF: Channel 2 not connected or not supplied or open circuit Terminal point assignment Terminal Signal points Connectors 1 and 3 1.1 +UV 2.1 GNDUv 1.2 +U0 2.2 -U0 1.3 +Ud 2.3 -Ud 1.4, 2.4 FE Connectors 2 and 4 1.1 5V 2.1 3.3 V 1.2, 2.2 +UV 1.3, 2.3 1.4, 2.4 – FE Assignment Jumper supply UV Jumper voltage U0 Jumper difference Ud Shielding Optional voltages to supply the jumper Routing of the selected supply voltage to the "Jumper supply UV" connection on connector 1 or 3 Not used Shielding Connect the terminal point of the selected voltage for the jumper supply to terminal point +UV on connector 2 (or 4). Terminal points +UV on slot 2 (or 4) are connected internally to terminal point +UV on slot 1 (or 3) (see Figure 2). Therefore, the selected voltage at +UV is available on slot 1 (or 3) (see also "Connection examples" on page 10). Function identification Green 2 Mbps: White stripe in the vicinity of the D LED 7210_en_02 PHOENIX CONTACT 7 IB IL SGI 2/F ... 5 Internal circuit diagram Local bus OPC SRE 1 UL+ UANA UL- Level Adaptation 3V/5V 24 V REF +5 V µC AGND Supervisor MUX +3,3 V AGND AGND +24 V (US) +24 V (UM) 7210B003 Figure 2 Internal circuit diagram Key: OPC S R E 1 Level Adaptation 3V/5V S u p e r v is o r Protocol chip Analog/digital converter Register expansion R E F Reference voltage Level adaptation M U X Multiplexer Hardware monitoring Amplifier x x x µ C Microcontroller X X X DC/DC converter with electrical isolation Optocoupler Other symbols used are explained in the IL SYS INST UM E user manual. 7210_en_02 PHOENIX CONTACT 8 IB IL SGI 2/F ... 6 Electrical isolation 8 Connection notes Connecting the strain gauges Connect the strain gauges using shielded twisted pair cables. Shield connection Only connect the shielding at one point, preferably to the terminal. If the shield is securely connected to the sensor, insulate the shield on the terminal side. Figure 3 7 Electrical isolation of the individual function areas Installation instructions Unused channels For unused channels, follow the instructions for parameterization (see notes on bit 15 on page 15). High current flowing through potential jumpers UM and US leads to a temperature rise in the potential jumpers and inside the terminal. Observe the following instructions to keep the current flowing through the potential jumpers of the analog terminals as low as possible: Create a separate main circuit for the analog terminals If this is not possible in your application and if you are using analog terminals in a main circuit together with other terminals, place the analog terminals after all the other terminals at the end of the main circuit. 7210_en_02 PHOENIX CONTACT 9 IB IL SGI 2/F ... 9 Connection examples The IB IL SGI 2/F terminal can measure both unipolar and bipolar jumper differences. Observe the polarity when connecting +Ud and -Ud. If the analog terminal expects unipolar jumper differences, the signal excursion may be negative in the worstcase scenario. The measured value would therefore always be 0. In this case, adapt the signal excursion to the input voltage range by switching cables +Ud and -Ud. If the analog terminal is set to a bipolar jumper difference, the signal excursion may be mixed up in the sign bit in the worst-case scenario. In this case, adapt the signal excursion to the input voltage range again by switching cables +Ud and -Ud. Connections +U0 and -U0 are led back to a unipolar input. If the cables are mixed up, the terminal indicates a configuration error. 9.1 6-wire connection (several strain gauge load cells per channel) Connector Channel RL Strain gauge 1 R R +UV +U0 +Ud Ud U0 UV 4 3 2 1 2 1 11 11 11 1 2 22 22 22 2 3 33 33 33 3 -Ud -U0 GNDUv FE R 1 4 44 44 44 4 RL Strain gauge 2 +UV +U0 +Ud -Ud -U0 GNDUv FE R R R R UV U0 Ud R RL RL 7210D005 Figure 4 Connection of strain gauges in 6-wire technology RL: Cable resistance Channel 1: Connect the strain gauge to connector 1 using 6-wire technology. At connector 2 select the jumper supply level. The terminal provides supply voltages of 5 V and 3.3 V. Connections +UV of connector 1 and +UV of connector 2 are connected internally. At connector 2, connect either 5 V or 3.3 V to +UV. This supplies the 6-wire connection of channel 1 with power. Channel 2: Connect the strain gauge to connector 3 using 6-wire technology. At connector 4 select the jumper supply level. The terminal provides supply voltages of 5 V and 3.3 V. Connections +UV of connector 3 and +UV of connector 4 are connected internally. At connector 4, insert a jumper to connect either 5 V or 3.3 V to +UV. This supplies the 6-wire connection of channel 2 with power. Channels 1 and 2 can be supplied with different supply voltages (5 V or 3.3 V). 7210_en_02 PHOENIX CONTACT 10 IB IL SGI 2/F ... 9.2 6-wire connection (several strain gauge load cells per channel) Connector Channel RL Strain gauge 1 R R +UV +U0 +Ud Ud U0 UV 2 1 1 11 11 2 22 22 3 33 33 4 44 44 -Ud -U0 GNDUv FE R 1 R RL RL Strain gauge 2 r R R Ud U0 UV Distribution R R RL RL Strain gauge n R R Ud U0 UV R R 7210A008 RL Figure 5 Connection of several strain gauges in 6-wire technology RL: Cable resistance In this operating mode you may connect several strain gauge load cells in parallel to connector 1 (channel 1) and/or connector 3 (channel 2), depending on the impedance of the strain gauge used. Please note, that the total impedance of the wired Inline terminal (channel 1 and channel 2) must not be lower than 58.3 Ω (typically). 7210_en_02 PHOENIX CONTACT 11 IB IL SGI 2/F ... Channel 1: Connect the required number of strain gauges in parallel to connector 1 using 6-wire technology. At connector 2 select the jumper supply level. The terminal provides supply voltages of 5 V and 3.3 V. Connections +UV of connector 1 and +UV of connector 2 are connected internally. At connector 2, connect either 5 V or 3.3 V to +UV. This supplies the 6-wire connection of channel 1 with power. Channel 2: Connect the required number of strain gauges to connector 3 using 6-wire technology. At connector 4 select the jumper supply level. The terminal provides supply voltages of 5 V and 3.3 V. Connections +UV of connector 3 and +UV of connector 4 are connected internally. At connector 4, insert a jumper to connect either 5 V or 3.3 V to +UV. This supplies the 6-wire connection of channel 2 with power. Channels 1 and 2 can be supplied with different supply voltages (5 V or 3.3 V). 9.3 4-wire termination Connector 1 Channel Strain gauge 1 R RL R 4 3 2 1 2 1 11 11 11 1 2 22 22 22 2 +UV +Ud Ud UV +UV 3 33 33 33 -Ud R 3 4 44 44 44 Strain gauge 2 R R R R +Ud -Ud GNDUv FE RL UV Ud GNDUv 4 FE R RL RL 7210D006 Figure 6 Connection of strain gauges in 4-wire technology (channel 1 and channel 2) RL: Cable resistance Channel 1/channel 2: Strain gauges can also be connected to the terminal in 4-wire technology. In this case, connect connections +UV to +U0 and GNDUv to -U0 (magnified in the diagram for channel 2) at the connector for the relevant channel (connector 2 and/or 3). There is no temperature and long-term drift compensation for the connecting cable in 4-wire technology. 7210_en_02 PHOENIX CONTACT 12 IB IL SGI 2/F ... 9.4 Permissible characteristics according to the jumper supply The table below indicates which characteristic can be configured for which jumper supply. Characteristic +1 mV/V ±1 mV/V +2 mV/V ±2 mV/V +3 mV/V ±3 mV/V +4 mV/V ±4 mV/V 10 UV = 3.3 V Yes Yes Yes Yes Yes Yes Yes Yes Programming data/configuration data Local bus (INTERBUS)) ID code Length code Process data channel Input address area Output address area Parameter channel (PCP) Register length (bus) 11 UV = 5 V Yes Yes Yes Yes Yes No Yes No Other bus systems DFhex (223dec) 03hex 48 bits 3 words 3 words 1 word 4 words For the programming/configuration data of other bus systems, please refer to the corresponding electronic device data sheet (e.g., GSD, EDS). Process data The terminal occupies three process data words and one PCP word. Figure 7 7210_en_02 Order of the process data words PHOENIX CONTACT 13 IB IL SGI 2/F ... 12 OUT process data output words Three OUT process data words are available. Configure the terminal channels via the OUT process data words. Where: – Output word OUT1 contains the command – Output word OUT2 contains the parameters for channel 1 – Output word OUT3 contains the parameters for channel 2 The following configurations are possible: Configuration Short designation Selection of mean value generation (filtering) Filter Characteristic for calculating the gain (see "Startup/measuring jumper Characteristic detuning" on page 21) Default 16-sample mean value ±2 mV/V Configuration errors are indicated in the status word. The configuration settings are stored in a volatile memory. If you change the configuration, the message "Measured value invalid" appears (diagnostic code 8004hex), until new measured values are available. 12.1 Output word OUT1 (control word) OUT1 Bit 15 14 13 12 11 10 9 Command code Assignment 8 7 6 5 4 3 2 1 0 0 0 0 0 0 0 0 0 Bit 15 to bit 8 (command code): 0 0 Bit 15 to bit 8 0 0 0 0 0 0 OUT1 0000hex 0 0 0 1 0 0 0 C 1x00hex 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 0 0 0 0 1 0 0 0 0 1 0 0 1 1 0 0 1 0 1 0 3000hex 3100hex 3200hex 3300hex 3C00hex 0 1 0 0 0 0 0 0 4000hex Command function Read measured values Read configuration channel-by-channel in IN2 (C = Channel number; 0 = Channel 1, 1 = Channel 2) Read min. value; IN2: Min. value channel 1, IN3: Min. value channel 2 Read max. value; IN2: Max. value channel 1, IN3: Max. value channel 2 Delete minimum and maximum value of channel 1 Delete minimum and maximum value of channel 2 Read firmware version and module ID in IN2. Configure device; configuration for channel 1 in OUT2 and for channel 2 in OUT3 During the transient response (e.g., following a configuration command), the fluctuating measured values may exceed the minimum and maximum values. Therefore, at the start of acquisition delete the minimum and maximum values using command 3200hex and/or 3300hex. One measurement is performed for each bus cycle. 7210_en_02 PHOENIX CONTACT 14 IB IL SGI 2/F ... 12.2 Output word OUT2 and OUT3 (parameter word) For command 4000hex the parameters must be specified in OUT2 and OUT3. This parameter word is only evaluated for this command. OUT2 and OUT3 Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 Assignment 1 0 0 0 0 0 0 Filter 0 0 0 0 0 Characteristic Bit 15 1 0 The set bit ensures that the relevant channel is configured. In the event that only one channel is used and there is no jumper supply at the other channel due to missing wire jumpers, the configuration is acknowledged negatively in the status word. In this case, set bit 15 of the configuration word of the unused channel to 0 to remedy the situation. Filter Selection of mean value generation. After every conversion, the measured value is saved in a mean value memory via which the mean value is generated. The memory size can be selected with the filter option. E.g., for a 16-sample mean value, the mean value is generated using the last 16 measured values. Character- Depending on the characteristic in relation to the available jumper supply, the terminal calculates the required istic gain for the configured input and thus has the best possible resolution in the unipolar and bipolar area. If in the unipolar area the strain gauge is supplied with a load greater than 130% or a negative load, the jumper detuning is outside the measuring range and an error is triggered. If in the bipolar area the strain gauge is supplied with a load greater than 130% in the positive or negative direction, the jumper detuning is outside the measuring range and an error is triggered. If invalid parameters are specified in the parameter word, the command will not be executed. The command is acknowledged in the input words with the error bit set. 12.3 Parameters for configuration The values in bold are default settings. Bit 15: Code dec bin 0 0 1 1 Bit 3 to bit 0: Configure Channel is not configured Channel is configured Bit 8: Code dec bin 0 0 1 1 7210_en_02 Filter No mean value 16-sample mean value Code dec bin 0 000 1 001 2 010 3 011 4 100 5 101 6 110 7 111 Characteristic +1 mV/V ±1 mV/V +2 mV/V ±2 mV/V +3 mV/V ±3 mV/V +4 mV/V ±4 mV/V PHOENIX CONTACT 15 IB IL SGI 2/F ... 13 IN process data input words 13.1 Input word IN1 (status word) Input word IN1 performs the task of a status word. IN1 Bit 15 Assignment EB 14 13 12 11 10 9 8 Mirroring of the command code 7 6 5 4 3 2 1 0 0 0 0 0 0 0 0 0 EB: Error bit EB = 0 EB = 1 No error has occurred. An error has occurred. Mirroring of the command code: A command code mirrored from the control word. Here, the MSB is suppressed. The set error bit indicates an invalid configuration value for command 4000hex. Possible reasons: – At least one of bits 3 - 7 or 9 - 14 is set – The jumper voltage is not 3.3 V ± 0.5 V or 5 V ± 0.5 V. – The characteristic value is 5 or 7 and the jumper voltage is 5 V ± 0.5 V. – The terminal has already been configured with PCP using the "Config Table" object. 13.2 Input words IN2 and IN3 The measured values, configuration or firmware version are transmitted to the controller board or the PC via process data input words IN2 to IN3 according to the configuration. For control word 3C00hex, IN2 provides the firmware version and the module ID. Example: Firmware version 1.23: IN2 Bit Assignment (hex) Meaning 7210_en_02 15 14 13 1 12 11 10 9 8 2 Firmware version 1.23 7 6 5 3 4 3 2 1 0 1 Module ID PHOENIX CONTACT 16 IB IL SGI 2/F ... The measured values are available in IB IL format. The measured value is represented in bits 14 to 0. An additional bit (bit 15) is available as a sign bit. MSB 15 14 SB MSB LSB SB 13 12 11 10 9 8 7 6 Analog value 5 4 3 2 1 LSB 0 Most significant bit Least significant bit Sign bit This format supports extended diagnostics. Values >8000hex and 130.048 + 130.048 + 100.000 + 1.000 + 0.004 0.0 - 0.004 - 100.000 -130.048 < -130.048 – Detuning for all unipolar characteristics [%] > 130.048 + 130.048 + 100.000 + 1.000 + 0.004 0.0 – – – – – To calculate the detuning as a percentage for other measured values, please use the following formula: Detuning = Process data value * 0.004 or Detuning = Process data value/250 IB input word [Hex] IB input word [dec] 8001 7F00 61A8 00FA 0001 0000 FFFF 9E58 8100 8080 8002 Overrange 32512 25000 250 1 0 -1 -25000 -32512 Underrange Open circuit Example: Characteristic: Process data value: 2m V/V 10000dec Detuning = 10000/250 = 40% 40% of 2 mV/V = 0.8 mV/V 7210_en_02 PHOENIX CONTACT 17 IB IL SGI 2/F ... 14 PCP communication For information on PCP communication, please refer to the IBS SYS PCP G4 UM E (Order No. 2745169) and IBS PCP COMPACT UM E (Order No. 9015349) user manuals. By default upon delivery, the terminal is configured according to the default settings on page 14. The terminal can be configured using process data or PCP to suit your application. In PCP mode, the terminal is configured with the "Config Table" object. The programs IBS CMD (for standard controller boards) and IBS PC WORX (for Field Controllers [FC] and Remote Field Controllers [RFC]) are available for the configuration and parameterization of your INTERBUS system. For additional information, please refer to the IBS CMD SWT G4 UM E user manual and the documentation for the version of PC WorX used. 14.1 Object dictionary Index 0080hex 0081hex Data type Array of Unsigned 16 Array of Unsigned 16 N 4 2 L 2 2 Meaning Terminal configuration Analog values of the channels N: Number of elements rd: Read access permitted L: Length of an element in bytes wr: Write access permitted 7210_en_02 Object name Config Table Analog Values Rights rd/wr rd PHOENIX CONTACT 18 IB IL SGI 2/F ... 14.2 Object descriptions Config Table object Configure the terminal using this object. Object description: Object Config Table Access Read, write Data type Array of Unsigned 16 Index 0080hex Subindex 00hex 01hex 02hex 03hex 04hex Write all elements Configuration of channel 1 Configuration of channel 2 Reserved Reserved Length (bytes) 08hex02hex Subindex 00hex Subindex 01hex to 04hex Data Terminal configuration 4 x 2 bytes Element value range The "Configuration channel x" elements are structured as follows: Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Assignment 1 0 0 0 0 0 0 Filter 0 0 0 0 0 Characteristic For the value ranges of the individual parameters, please refer to Section "Parameters for configuration" on page 15. If an invalid configuration is specified, a negative confirmation is generated with error message 08hex, 00hex or xx30hex. The low byte of the additional error code is 30hex (value is out of range), the high byte contains the number of the affected element. Example: Config Table is completely filled with data (subindex 00) and the entry for channel 2 is invalid. In this case, the additional error code is equal to 0230hex. 7210_en_02 PHOENIX CONTACT 19 IB IL SGI 2/F ... Analog Values object The elements of this object contain the analog values of the channels in IB IL format. Object description: Object Analog Values Access Read Data type Array of Unsigned 16 Index 0081hex Subindex 00hex 01hex 02hex Read all elements Analog value of channel 1 Analog value of channel 2 Length (bytes) 04hex02hex Subindex 00hex Subindex 01hex to 02hex Data Analog values of the channels 7210_en_02 2 x 2 bytes PHOENIX CONTACT 20 IB IL SGI 2/F ... 15 Startup/measuring jumper detuning To start the terminal, proceed as follows: • Install the terminal within the Inline station. To do so, proceed as described in the package slip. • Connect the strain gauge in 6 or 4-wire technology (see "Connection examples" on page 10). • Connect the voltage to the Inline station. • On this power up the terminal is configured with the default values. • If you do not wish to operate the terminal with the default values, configure the terminal via process data (see "OUT process data output words" on page 14) or PCP (see "PCP communication" on page 18). • Jumper detuning can now be measured. Jumper detuning can only be measured if the corresponding input is configured. To configure the input, the jumper supply UV must be present. 16 Configuration and analog values Terminal configuration is only required if at least one of the channels is to be operated outside the default values (see "Parameters for configuration" on page 15). You can configure the terminal either using process data or using PCP and transmit the analog values accordingly. If you have configured the terminal via PCP, the configuration can no longer be modified using the process data. For easy terminal configuration a function block can be downloaded at www.phoenixcontact.com. Example 1: Configuring the terminal via process data A strain gauge pressure force transducer for control system applications is connected to channel 1. Its data sheet specifies a characteristic of +2 mV/V at a nominal load of 500 N. The following configuration is thus selected for channel 1: Characteristic: Filter: Configuration value OUT2: Channel 1 +2 mV/V No mean-value generation 8002hex A tractive and pressure force transducer with the characteristic ±4 mV/V at a load of 1 kN is connected to channel 2. The following configuration is thus selected for channel 2: Characteristic: Filter: Configuration value OUT3: Channel 2 ±4 mV/V 16-sample mean-value generation 8107hex If both channels are operated in the default configuration, configuration is not required. When a configuration command is sent, however, both channels will always be configured. Therefore also enter the corresponding parameterization for the channel that is to be operated in the default configuration. If a "0" is transmitted for channel 1 in bit 15 (do not configure, see bit 15 on page 15), the channel does not provide any values in the following. 7210_en_02 PHOENIX CONTACT 21 IB IL SGI 2/F ... Step 1 2 3 4 5 Process data OUT3 = 8107hex OUT2 = 8003hex OUT1 = 4000hex Wait until IN1 = 4000hex OUT1 = 0000hex Wait until IN1 = 0000hex Measured value channel 1 = IN2 Measured value channel 2 = IN3 If the measured value = 80xxhex, this corresponds to an error message Meaning Specify configuration Wait for confirmation Requesting measured values Wait for confirmation Read measured values Channel 1 Read measured value IN2: Current jumper detuning: 5A78hex (= 23160dec) = IN2 * 0.004% * characteristic = 23160 * 0.004% * 2 mV/V = 1.853 mV/V = IN2 * 0.004% * nominal load = 23160 * 0.004% * 500 N = 463.2 N Current load: Channel 2 CBDEhex (= 52190dec); following evaluation of the MSB: -19422dec = IN3 * 0.004% * characteristic = -19422 * 0.004% * 4 mV/V = -3.11 mV/V = IN3 * 0.004% * nominal load = -19422 * 0.004% * 1 kN = -776.9 N Read measured value IN3: Current jumper detuning: Current load: Example 2: Minimum/maximum evaluation The channel 1 and channel 2 pressure transducers are loaded and unloaded several times. Only the maximum load is of interest during the entire process. Step 1 2 3 4 5 6 7 8 Process data OUT1 = 3200hex Wait until IN1 = 3200hex OUT1 = 3300hex Wait until IN1 = 3300hex OUT1 = 3100hex Wait until IN1 = 3100hex Maximum value of channel 1 = IN2 Maximum value of channel 2 = IN3 Meaning Delete minimum and maximum values of channel 1 Wait for confirmation Delete minimum and maximum values of channel 2 Wait for confirmation Load and unload channel 1 and 2 pressure transducers Read maximum values Wait for confirmation Read maximum value; to calculate the current jumper detuning and the current load, see above. If measured value = 80xxhex, then error message © PHOENIX CONTACT 11/2008 7210_en_02 PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany Phone: +49-(0) 5235-3-00 • Fax: +49-(0) 5235-3-4 12 00 www.phoenixcontact.com 22
2878735 价格&库存

很抱歉,暂时无法提供与“2878735”相匹配的价格&库存,您可以联系我们找货

免费人工找货