ILB PB AI4 AO2
Order No.: 2878874
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2878874
Inline Block IO analog input/output module, PROFIBUS, inputs: 0-20
mA, 4-20 mA, ±20 mA, 0-5 V, ±5 V,0-10 V, ±10 V, Pt 100, Pt 1000, Ni
1000..., outputs: 0-5 V, ±5 V, 0-10 V, ±10V, 0-20 mA, ±20 mA, 4-20
mA, 2, 3, 4-conductor connection
Product notes
WEEE/RoHS-compliant since:
10/28/2008
Commercial data
GTIN (EAN)
4
046356
075114
Note
Made-to-order
sales group
K441
Pack
1 pcs.
Customs tariff
85389091
Catalog page information
Page 327 (AX-2009)
http://
www.download.phoenixcontact.com
Please note that the data given
here has been taken from the
online catalog. For comprehensive
information and data, please refer
to the user documentation. The
General Terms and Conditions of
Use apply to Internet downloads.
Product description
The multifunctional, analog Inline Block I/O modules can be used universally. The four inputs either offer the difference
measured between analog current / voltage signals or the option of connecting resistance thermometers (RTDs).
Furthermore, the current or voltage actuators can be connected at the two outputs. In addition, all channels are equipped
with shield connections as a standard and are provided with the 2, 3 or 4-conductor system. The analog signals are
made available with a resolution of 16 bits.
The connectors can be labeled using hinged labeling fields. The fields have insert cards that can be labeled individually
to suit the application. Additionally, there is the proven ZBFM-6... Zack marker strip for labeling the terminal points.
PHOENIX CONTACT Deutschland GmbH
http://www.phoenixcontact.de
Page 1 / 6
Feb 8, 2011
ILB PB AI4 AO2 Order No.: 2878874
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2878874
Technical data
General data
Width
156 mm
Height
136.8 mm
Depth
57 mm
Weight
465 g
Mounting type
DIN rail
Ambient temperature (operation)
-25 °C ... 60 °C
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
10 % ... 85 % (no condensation)
Permissible humidity (storage/transport)
10 % ... 95 % (no condensation)
Air pressure (operation)
80 kPa ... 108 kPa (up to 2000 m above sea level)
Air pressure (storage/transport)
66 kPa ... 108 kPa (up to 3500 m above mean sea level)
Degree of protection
IP20
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
Mechanical tests
Vibration resistance in acc. with IEC 60068-2-6 5 g
Shock test in acc. with IEC 60068-2-27 30 g
Interface
Fieldbus system
PROFIBUS-DP
Name
Inline local bus
Type of connection
D-SUB-9 female connector
Transmission speed
9,6 kBit/s ... 12 MBit/s
Transmission physics
Copper
Inline potential routing
Communications power UL
24 V DC
Power supply at UL
max. 8 A
Current consumption from UL
Typ. 100 mA
max. 150 mA (AO-I nominal load)
Power supply at US
max. 8 A
Current consumption from US
max. 220 mA (Maximum full load)
Analog inputs
Number of inputs
max. 4 (2 differential inputs, voltage or current can be chosen
separately)
Type of connection
Spring-cage connection
PHOENIX CONTACT Deutschland GmbH
http://www.phoenixcontact.de
Page 2 / 6
Feb 8, 2011
ILB PB AI4 AO2 Order No.: 2878874
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2878874
Connection method
2, 3, 4-wire (shielded)
Input name
Analog inputs
A/D conversion time
Typ. 180 µs
Resolution A/D
16 bit
Limit frequency (3 dB)
120 Hz (default for 4.5 ms filter)
450 Hz (for 1.1 ms filter)
Data formats
IB IL
Measured value resolution
16 bits (15 bits + sign)
Current input signal
0 mA ... 20 mA
4 mA ... 20 mA
-20 mA ... 20 mA
Input resistance current input
Typ. 107 Ω
Voltage input signal
-5 V ... 5 V
0 V ... 10 V
-10 V ... 10 V
Input resistance of voltage input
Typ. 276 kΩ
Number of inputs
4 (differential inputs, voltage)
Type of protection
Overload protection, short-circuit protection of sensor supply
Open circuit response
Goes to 0 V
Voltage input signal
0 V ... 5 V
-5 V ... 5 V
0 V ... 10 V
-10 V ... 10 V
Number of inputs
4 (differential inputs, current)
Type of protection
Electronic short-circuit protection
Open circuit response
Going to 0 mA; open-circuit detection from 4 mA ... 20 mA
Current input signal
0 mA ... 20 mA
4 mA ... 20 mA
-20 mA ... 20 mA
Input resistance current input
Typ. 107 Ω
Number of inputs
4
Input name
Analog RTD inputs
Sensor types (RTD) that can be used
Pt100, Pt500, Pt1000, Ni100, Ni1000, Ni1000 L&G
Linear resistance measuring range
0 Ω ... 3200 Ω
0 Ω ... 9500 Ω
Protective circuit
PHOENIX CONTACT Deutschland GmbH
http://www.phoenixcontact.de
Overload protection, short-circuit protection of sensor supply
Page 3 / 6
Feb 8, 2011
ILB PB AI4 AO2 Order No.: 2878874
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2878874
Analog outputs
Number of outputs
2
Type of connection
Spring-cage connection
Connection method
2-wire (shielded)
Output name
Analog outputs
D/A conversion time
Typ. 70 µs
D/A resolution
16 Bit
Type of protection
Short-circuit protection of outputs
Data formats
IB IL
Measured value representation
16 bits (15 bits + sign bit)
Process data update
17 ms
Current output signal
0 mA ... 20 mA
4 mA ... 20 mA
-20 mA ... 20 mA
Load/output load current output
to 500 Ω
Voltage output signal
0 V ... 5 V
-5 V ... 5 V
0 V ... 10 V
-10 V ... 10 V
Load/output load voltage output
> 2 kΩ
Certificates / Approvals
Certification
CUL, UL
Accessories
Item
Designation
Description
CLIPFIX 35-5
Snap-on end bracket, for NS 35/7.5 or NS 35/15 DIN rail, can be
fitted with Zack strip ZB 5 and ZBF 5, terminal strip marker KLM
2 and KLM, parking facility for FBS...5, FBS...6, KSS 5, KSS 6,
width: 5,15 mm, color: gray
Assembly
3022276
PHOENIX CONTACT Deutschland GmbH
http://www.phoenixcontact.de
Page 4 / 6
Feb 8, 2011
ILB PB AI4 AO2 Order No.: 2878874
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2878874
Marking
0809492
ESL 62X10
Insert strip for laser printer, lettering field: 62 x 10 mm
2727501
IB IL FIELD 2
Labeling field, width: 12.2 mm
0808778
ZBF 6:SO/CMS
Zack strip, flat, 10-section, divisible, special printing, marking
according to customer requirements
0803618
ZBFM 6/WH:UNBEDRUCKT
Zack marker sheet, flat, unprinted: 100-section, 10 strips à 10
markers, sufficient for 100 terminal blocks, for all terminal blocks,
pitch 6.2 mm, labeling with M-PEN or CMS system, color: white
0803650
ZBFM 6:SO/CMS
Special printing, Zack marker sheet, flat, 100-section, divisible,
marking according to customer requirements
2740245
IB IL SCN 6-SHIELD-TWIN
Inline shield connector
2726353
IB IL SCN-6 SHIELD
Inline shield connector
2726337
IB IL SCN-8
Connector, for digital 1, 2 or 8-channel Inline terminals
Plug/Adapter
Diagrams/Drawings
Connection diagram
Dimensioned drawing
PHOENIX CONTACT Deutschland GmbH
http://www.phoenixcontact.de
Page 5 / 6
Feb 8, 2011
ILB PB AI4 AO2 Order No.: 2878874
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2878874
Address
PHOENIX CONTACT Deutschland GmbH
Flachsmarktstr. 8
32825 Blomberg,Germany
Phone +49 5235 3 12000
Fax +49 5235 3 41200
http://www.phoenixcontact.de
© 2011 Phoenix Contact
Technical modifications reserved;
PHOENIX CONTACT Deutschland GmbH
http://www.phoenixcontact.de
Page 6 / 6
Feb 8, 2011