IB IL 230 PWR IN/F-D (-PAC)
Inline power terminal, 230 V AC,
with fuse and diagnostics
AUTOMATION
Data sheet
7187_de_01
1
© PHOENIX CONTACT 2011-06-14
Description
This terminal is designed for use within an Inline station.
It enables input of the 230-V-AC-supply voltage into a 230-VAC area of an Inline station.
The end clamp (IB IL AC END) that is used for terminating the
230-V-AC area is supplied as standard.
The terminal is equipped with elements for protection against
surge voltage. The internal fuse protects the L phase.
The terminal is equipped with an LED for diagnostics and
occupies two input data bits, which are used to indicate the
presence of the supply voltage and the state of the fuse
Features
–
–
–
Supplying the L phase (230 V AC)
Diagnostic indicators
Protecting the L phase by an internal fuse
WARNING: dangerous contact voltage
Connecting and disconnecting the Inline terminals for the 230 V AC voltage range is only permitted when the
power supply is disconnected!
This data sheet is only valid in association with the IL SYS INST UM E user manual.
Make sure you always use the latest documentation.
It can be downloaded from the product at www.phoenixcontact.net/catalog.
IB IL 230 PWR IN/F-D (-PAC)
2
Table of contents
1
Description .............................................................................................................................. 1
2
Table of contents ..................................................................................................................... 2
3
Ordering data .......................................................................................................................... 3
4
Technical data ......................................................................................................................... 3
5
Internal circuit diagram ............................................................................................................ 5
6
Intended use............................................................................................................................ 6
7
Local diagnostic indicators ...................................................................................................... 6
8
Terminal point assignment....................................................................................................... 7
9
Connection example................................................................................................................ 7
10
Installation and startup............................................................................................................. 7
11
Process data............................................................................................................................ 8
7187_de_01
PHOENIX CONTACT
2
IB IL 230 PWR IN/F-D (-PAC)
3
Ordering data
Description
Type
Order No.
Pcs. / Pkt.
Inline power terminal, complete with accessories (connector and labeling
field), 230 V AC, with fuse and diagnostics
IB IL 230 PWR IN/F-D-PAC
2878971
1
Inline power terminal, without accessories, 230 V AC, with fuse and diagnostics
IB IL 230 PWR IN/F-D
2878081
1
Accessories
Type
Order No.
Pcs. / Pkt.
Connector set, for Inline input terminal blocks with AC voltage
( Plug/Adapter )
IB IL AC-PWR-IN-PLSET
2740180
1
10
Labeling field, width: 12.2 mm ( Marking )
IB IL FIELD 2
2727501
Insert strip for laser printer, lettering field: 62 x 10 mm ( Marking )
ESL 62X10
0809492
1
Replacement fuse ( Fuse )
SI 5X20 6,3 A T DIN 41662
2726104
10
Documentation
Type
Order No.
Pcs. / Pkt.
User manual, English, Automation terminals of the Inline product range
IL SYS INST UM E
-
-
4
Technical data
Dimensions (nominal sizes in mm)
140,5
71,5
119,8
Width
36.6 mm
Height
119.8 mm
Depth
71.5 mm
Wide power terminal block
24.4 mm
Wide end terminal block
12.2 mm
General data
Color
Gray
Weight
80 g
Mounting type
DIN rail
Ambient temperature (operation)
-25 °C ... 55 °C
Ambient temperature (storage/transport)
-25 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)
10 % ... 95 % (according to DIN EN 61131-2)
7187_de_01
PHOENIX CONTACT
3
IB IL 230 PWR IN/F-D (-PAC)
General data
Air pressure (operation)
70 kPa ... 106 kPa (up to 2000 m above mean sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above mean sea level)
Degree of protection
IP20
Protection class
I, IEC 61140, EN 61140, VDE 0140-1
Connection data
Name
Inline connectors
Connection method
Spring-cage connection
Conductor cross section solid / stranded
0.08 mm² ... 1.5 mm²
Conductor cross section [AWG]
28 ... 16
Interface
Interface
Inline local bus
Connection method
Inline data jumper
Power consumption
Main circuit supply UM
230 V AC (nominal value)
Peripherals voltage range
207 V AC ... 253 V AC (including all tolerances, including ripple)
Power supply at UM
8 A (nominal value)
Communications power UL
7.5 V DC (via voltage jumper)
Current consumption from UL
25 mA
Programming Data
ID code (hex)
BE
ID code (dec.)
190
Length code (hex)
C2
Length code (dec.)
194
Process data channel
2 Bit
Input address area
2 Bit
Output address area
0 Byte
Parameter channel (PCP)
0 Byte
Register length
2 Bit
For the programming data/configuration data of other bus systems, please refer to the corresponding electronic device data sheet (e.g., GSD,
EDS).
PROFIBUS telegram data
Required parameter data
1 Byte
Need for configuration data
4 Byte
Electrical isolation/isolation of the voltage areas
5 V supply, incoming remote bus/7.5 V supply (bus logics)
500 V AC , 50 Hz , 1 min
5 V supply, outgoing remote bus/7.5 V supply (bus logics)
500 V AC , 50 Hz , 1 min
7.5 V supply (bus logic) / peripheral range 230 V AC
2500 V AC , 50 Hz , 1 min
7.5 V supply (bus logic) / peripheral range 230 V AC (routine test)
1200 V AC , 50 Hz , 1 min
Peripheral range 230 V AC / PE
500 V AC , 50 Hz , 1 min
Output / Phase
500 V AC , 50 Hz , 1 min
Approvals
For the latest approvals, please visit www.phoenixcontact.net/catalog.
7187_de_01
PHOENIX CONTACT
4
IB IL 230 PWR IN/F-D (-PAC)
5
Internal circuit diagram
IB IL AC END
IB IL 230 PWR IN/2-F-D-PAC
Local bus
OPC
D
UL+
UANA
UL-
E
L
L
N
Figure 1
Internal wiring of the terminal points
Key:
Optocoupler
LED
Protocol chip
(Bus logic including voltage conditioning)
OPC
Terminal point without metal contact
Terminal point without metal contact with
filler plugs
Explanation for other used symbols has been
provided in the IL SYS INST UM E user manual.
7187_de_01
PHOENIX CONTACT
5
IB IL 230 PWR IN/F-D (-PAC)
6
Intended use
The terminal is only to be used within an Inline station in
accordance with the specifications in the data sheet and
IL SYS INST UM E user manual. Phoenix Contact accepts no
liability when used for anything other than its intended purpose.
7
Local diagnostic indicators
B
A
L
D
E
D
Figure 2
Local diagnostic indicators
A
B
LED
D
E
L
L
E
Power terminal
End terminal
Color
Green
Red
Red off
Red off
Green
Green
OFF
Green ON
Meaning
Diagnostics (bus and logic voltage)
Fuse
Fuse OK
Fuse blown
Supply voltage 230 V AC
No supply voltage
Supply voltage is available
If there is no L phase or the fuse has blown or is
missing, an I/O error message is generated for
the higher-level control or computer system.
A blown or missing fuse is indicated via both
diagnostics displays. The LED E lights up and
the green LED D flashes at 2 Hz.
Function identification
Flashing white light
7187_de_01
PHOENIX CONTACT
6
IB IL 230 PWR IN/F-D (-PAC)
8
Terminal point assignment
B
9
Connection example
WARNING: dangerous contact voltage
3
Protect the 230 V AC supply via an external
fuse!
3
A
1
2
L
D
1
2
2.1
1.1
2.1
1.1
2.1
1.2
2.2
1.2
2.2
1.2
2.2
L
1.3
2.3
1.3
2.3
1.3
2.3
N
1.4
2.4
1.4
2.4
1.4
2.4
230 V AC
E
1.1
2.1
1.2
2.2
1.3
2.3
1.4
2.4
Figure 4
10
Figure 3
1.1
Terminal point assignment
Typical connection of the supply voltage
Installation and startup
Strictly observe the instructions in the data
sheet and the IL SYS INST UM E user manual
during installation and startup.
Installing the system
Terminal Designa- Assignment
point
tion
Power terminal (A)
Connector 1
All
Not used
Connector 2 (marked according to function)
1.1 / 2.1
Not used
1.2 / 2.2
L
Supply points for the phase of the L
supply;
Terminal points bridged internally
1.3 / 2.3
N
Neutral conductor connection; terminal points bridged internally
1.4
PE
Protective conductor connection; the
contact is connected directly to the
PE potential jumper. Ground the terminal via the PE connection! This ensures protective earth ground connection of all terminals within this
area when the 230 V AC area is correctly established.
2.4
Not used
End clamp (B)
Connector 3
All
Not used
7187_de_01
Install the system according to the requirements of EN 50178!
Only qualified personnel may work on low voltage area Inline
terminals.
Qualified personnel are people who, because of their education, experience and instruction and their knowledge of relevant standards, regulations, accident prevention and service
conditions, have been authorized by those responsible for the
safety of the plant, to carry out any required operations and
who are able to recognize and avoid any possible dangers.
(definitions for skilled workers according to
EN 50110-1:1996).
PHOENIX CONTACT
7
IB IL 230 PWR IN/F-D (-PAC)
WARNING: dangerous contact voltage
Please be aware of dangerous voltages when
working on circuits that do not meet SELV requirements.
Installing the Inline station
The maximum total current flowing through the potential
jumpers is 8 A.
WARNING:
Connecting and disconnecting the Inline terminals for the 230 V AC voltage range is only permitted when the power supply is disconnected!
Use the intended power connector for supplying the voltage.
The full current carrying capacity is ensured by
internal bridging of the terminal points (see
connection assignment).
When working on the terminals and wiring, always switch off the supply voltage and ensure
it cannot be switched on again.
Failure to observe these instructions can lead
to damage to health or even life-threatening
injuries.
WARNING: dangerous contact voltage in
the event of ground faults
(if for example, the FI switch is triggered or star
point is "exposed")
Only operate Inline terminals for 230 V AC voltage range in grounded AC voltage networks.
If it is necessary to establish another voltage range behind the
230 V AC area, terminate the 230 V area with an end clamp
and begin the new voltage area with a new power terminal.
Startup of an Inline station
An Inline station may only be put into operation when it is completely installed. That means:
– all terminals must be properly snapped in with their connectors.
– The station must be terminated with the end plate and the
two end clamps.
WARNING:multiple supplies are not permitted!
Observe the specifications in the
IL SYS INST UM E user manual on the low voltage area.
The supply voltage may only be connected to
the intended power terminal.
The connecting cables of all actuators and sensors may only be connected to the Inline AC
terminals.
11
Process data
Do not use external busbars for group potentials!
The input process data only maps the status of
the fuse and the main voltage.
(Byte.Bit) view
Assign- Phase L exists, fuse is OK
ment
Phase L exists, fuse has blown or is
missing
Phase L does not exist, fuse has blown
or is missing
0.1
1
0
0.0
1
1
0
0
For the assignment of the illustrated (byte.bit)
view to your INTERBUS control or computer
system, please refer to the
DB GB IBS SYS ADDRESS data sheet.
7187_de_01
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49-(0) 5235-3-00
PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300
www.phoenixcontact.com