https://www.phoenixcontact.com/us/products/2882585
Surge protection device - S-PT-EX(I)-24DC-3/4" - 2882585
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Surge protection in the IP67 screw-on module for measuring sensors in intrinsically safe circuits, direct mounting
with 3/4" NPT outer thread, cable gland for the signal cable, two-stage protective circuit. HART-compatible.
Product Features
■
Arresters in hexagonal pipe with various outer threads
Key Commercial Data
Packing unit
1 pc
Weight per Piece (excluding packing)
440.0 g
Custom tariff number
85363010
Country of origin
Germany
Technical data
Dimensions
Height
34 mm
Width
34 mm
Depth
148 mm
Ambient conditions
Ambient temperature (operation)
-40 °C ... 50 °C
Degree of protection
IP67
General
Housing material
Zinc die-cast
Flammability rating according to UL 94
V-0
Color
silver
03/13/2016 Page 1 / 6
https://www.phoenixcontact.com/us/products/2882585
Surge protection device - S-PT-EX(I)-24DC-3/4" - 2882585
Technical data
General
Standards for cearances and creepage distances
IEC 60664-1
EN 60079-0
EN 60079-11
Mounting type
ct screw connection
Type
Screw-in module
Number of positions
3
Direction of action
Line-Line & Line-Earth Ground
Protective circuit
IEC test classification
C1
C2
C3
D1
Nominal voltage UN
24 V DC
Maximum continuous voltage UC
30 V DC
21 V AC
Maximum continuous voltage UC (wire-wire)
30 V DC
21 V AC
Nominal current IN
350 mA (50 °C)
Operating effective current IC at UC
≤ 10 µA
Residual current IPE
≤ 2 µA
Nominal discharge current In (8/20) µs (Core-Core)
10 kA
Nominal discharge current In (8/20) µs (Core-Earth)
10 kA
Nominal discharge current In (8/20) µs (Shield-Earth)
10 kA (optional)
Max. discharge current Imax (8/20) µs maximum (Core-Core)
10 kA
Max. discharge current Imax (8/20) µs maximum (Core-Earth)
10 kA
Max. discharge current Imax (8/20) µs maximum (Shield-Earth)
10 kA
Nominal pulse current Ian (10/1000) µs (Core-Core)
30 A
Nominal pulse current Ian (10/1000) µs (Core-Earth)
100 A
Nominal pulse current Ian (10/1000) µs (Shield-Earth)
100 A
Impulse discharge current (10/350)˽µs, peak value limp
1 kA
Output voltage limitation at 1 kV/µs (Core-Core) spike
≤ 50 V
Output voltage limitation at 1 kV/µs (Core-Earth) spike
≤ 1.4 kV (Direct grounding)
Output voltage limitation at 1 kV/µs (Shield-Earth) spike
≤ 600 V (optional)
Output voltage limitation at 1 kV/µs (Core-Core) static
≤ 50 V
Output voltage limitation at 1 kV/µs (Core-Earth) static
≤ 1.4 kV (Direct grounding)
Residual voltage at In (conductor-conductor)
≤ 50 V
03/13/2016 Page 2 / 6
https://www.phoenixcontact.com/us/products/2882585
Surge protection device - S-PT-EX(I)-24DC-3/4" - 2882585
Technical data
Protective circuit
Residual voltage with Ian (10/1000)µs (conductor-conductor)
≤ 50 V
Voltage protection level Up (core-core)
≤ 55 V (C2 -5 kA)
≤ 50 V (C1 - 250 A)
≤ 50 V (C3 - 25 A)
≤ 80 V (D1 - 1 kA)
Voltage protection level Up (core-ground)
≤ 1.4 kV (C2 -5 kA, direct grounding)
≤ 1.4 kV (C1 - 500 A)
≤ 1.4 kV (C3 - 100 A)
≤ 1.4 kV (D1 - 1 kA)
Voltage protection level Up (shield-ground)
≤ 650 V (C2 -5 kA optional)
Response time tA (Core-Core)
≤ 1 ns
Response time tA (Core-Earth)
≤ 100 ns
Response time tA (Shield-Earth)
≤ 100 ns
Input attenuation aE, sym.
typ. 0.5 dB (≤ 1 MHz / 50 Ω)
typ. 0.2 dB (Up to 400 kHz, 150 Ω)
Cut-off frequency fg (3 dB), sym. in 50 Ohm system
typ. 6 MHz
Cut-off frequency fg (3 dB), sym. in 150 Ohm system
typ. 2.5 MHz
Resistance in series
2.2 Ω ±10 %
Surge protection fault message
None
Impulse durability (conductor-conductor)
C2 - 10 kV/5 kA
D1 - 1 kA
Impulse durability (conductor-ground)
C2 - 10 kV/5 kA
D1 - 1 kA
Impulse durability (shield-ground)
C2 - 10 kV / 5 kA
D1 - 1 kA
Alternating current carrying capacity (conductor-ground)
10 A - 1 s
Alternating current carrying capacity (shield-ground)
10 A - 1 s
Connection data
Connection name
Input/output
Connection method
Screw connection
Connection type IN
Screw terminal blocks
Connection type OUT
Connection line
Connection method
Screw connection
Screw thread
M3
Tightening torque
0.6 Nm
Stripping length
6 mm
Conductor cross section flexible min.
0.14 mm²
03/13/2016 Page 3 / 6
https://www.phoenixcontact.com/us/products/2882585
Surge protection device - S-PT-EX(I)-24DC-3/4" - 2882585
Technical data
Connection data
Conductor cross section flexible max.
1.5 mm²
Conductor cross section solid min.
0.14 mm²
Conductor cross section solid max.
1.5 mm²
Conductor cross section AWG min.
26
Conductor cross section AWG max.
16
Standards and Regulations
Standards/regulations
DIN EN 61643-21
EN 60079-0
EN 60079-11
EN 60079-26
General
Maximum inner capacitance Ci
2 nF
Maximum inner inductance Li
1 µH
Max. input current Ii
350 mA (T4,T5,T6/≤ 50°C)
Max. input voltage Ui
30 V
Maximum input power Pi
3W
Conformity / approvals
ATEX
˽ II 1G Ex ia IIC T4...T6 Ga
IECEx
Ex ia IIC T4...T6 Ga
Classifications
eCl@ss
eCl@ss 4.0
27140201
eCl@ss 4.1
27130801
eCl@ss 5.0
27130801
eCl@ss 5.1
27130801
eCl@ss 6.0
27130807
eCl@ss 7.0
27130807
eCl@ss 8.0
27130807
eCl@ss 9.0
27130807
ETIM
ETIM 2.0
EC000943
ETIM 3.0
EC000943
ETIM 4.0
EC000943
03/13/2016 Page 4 / 6
https://www.phoenixcontact.com/us/products/2882585
Surge protection device - S-PT-EX(I)-24DC-3/4" - 2882585
Classifications
ETIM
ETIM 5.0
EC000943
UNSPSC
UNSPSC 6.01
30212010
UNSPSC 7.0901
39121610
UNSPSC 11
39121610
UNSPSC 12.01
39121610
UNSPSC 13.2
39121620
Approvals
Approvals
Approvals
EAC / EAC
Ex Approvals
IECEx / ATEX / INMETRO
Approvals submitted
Approval details
EAC
EAC
Drawings
03/13/2016 Page 5 / 6
https://www.phoenixcontact.com/us/products/2882585
Surge protection device - S-PT-EX(I)-24DC-3/4" - 2882585
Dimensional drawing
Circuit diagram
1
BN
2
BL
136,5
IN
127,5
OUT
M20
33,5
30
106,5
BK
Phoenix Contact 2016 © - all rights reserved
http://www.phoenixcontact.com
03/13/2016 Page 6 / 6
很抱歉,暂时无法提供与“2882585”相匹配的价格&库存,您可以联系我们找货