Extract from the online
catalog
FLT-CP-PLUS-3C-350
Order No.: 2882653
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2882653
Pluggable lighting current arrester, in acc. with type 1/class I/B for 3phase power supply networks with combined PE and N (L1, L2, L3,
PEN) installed in one cable.
Product notes
WEEE/RoHS-compliant since:
05/09/2006
Commercial data
GTIN (EAN)
4
046356
098236
sales group
J010
Pack
1 pcs.
Customs tariff
85363010
Catalog page information
Page 16 (TT-2011)
http://
www.download.phoenixcontact.com
Please note that the data given
here has been taken from the
online catalog. For comprehensive
information and data, please refer
to the user documentation. The
General Terms and Conditions of
Use apply to Internet downloads.
Technical data
Standards
Housing material
PBT
Inflammability class acc. to UL 94
V0
Color
gray
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 1 / 6
Jul 26, 2011
FLT-CP-PLUS-3C-350 Order No.: 2882653
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2882653
Standards for air and creepage distances
EN 60664-1
IEC 60664-1: 1992-10
IEC 61643-11
Degree of protection
IP20
Mounting type
DIN rail: 35 mm
Design
DIN rail module, two-section, divisible
Number of positions
3
Ambient temperature (operation)
-40 °C ... 80 °C
Message: Surge protection fault
Optical, remote indicator contact
Direction of action
3L-N/PE
Width
106.90 mm
Height
70.00 mm
Length
95.80 mm
Pitch unit
6 Div.
Protective circuit
IEC category
I
T1
EN type
T1
Lightning protection class
I /100 kA (TN-C)
Nominal voltage UN
240 V AC (230/400 V AC ... 240/415 V AC)
Arrester rated voltage UC (L-PEN)
350 V AC
UT (TOV-proof)
415 V (5 s)
Nominal frequency fN
50 Hz (60 Hz)
Nominal load current IL
125 A (≤ 55°C)
Standby power consumption PC
≤ 4 mVA
Nominal discharge surge current In (8/20) µs (LPEN)
25 kA
75 kA (3L-PEN)
Lightning test current (10/350) µs, charge
37.5 As
Lightning test current (10/350) µs, specific energy
1.40 MJ/Ω
Lightning test current (10/350) µs, peak value limp
75 kA
Lightning test current (10/350) µs, charge
12.5 As
Lightning test current (10/350) µs, specific energy
160.00 kJ/Ω
Lightning test current (10/350) µs, peak value limp
25 kA (1L-PEN)
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 2 / 6
Jul 26, 2011
FLT-CP-PLUS-3C-350 Order No.: 2882653
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2882653
Impulse operate voltage at 6 kV (1.2/50)µs (LPEN)
≤ 1.5 kV
Protection level UP (L-PEN)
≤ 1.5 kV
Response time (L-N)
≤ 100 ns
Max. required backup fuse with branch wiring
315 A (gL/gG)
Max. required backup fuse with V-type through
wiring
125 A (gL/gG)
Recommended backup fuse maximum
160 A (gL/gG, 125 A with serial through wiring)
Short-circuit resistance IP with max. backup fuse
(effective)
50 kA
Follow current quenching capacity If (L-PE)
50 kA (264 V AC)
25 kA (350 V AC)
Connection, protective circuit
Connection method
Screw terminal blocks
Connection type IN
Biconnect screw terminal block
Connection type OUT
Biconnect screw terminal block
Connection method
Biconnect terminal block
Screw thread
M5
Tightening torque
4.5 Nm
Stripping length
18 mm
Conductor cross section stranded min.
2.5 mm²
Conductor cross section stranded max.
25 mm²
Conductor cross section solid min.
2.5 mm²
Conductor cross section solid max.
35 mm²
Conductor cross section AWG/kcmil min.
13
Conductor cross section AWG/kcmil max
2
Remote indicator contact
Connection name
Remote fault indicator contact
Switching function
PDT contact
Connection method
Plug-in/screw connection via COMBICON
Screw thread
M2
Tightening torque
0.25 Nm
Stripping length
7 mm
Conductor cross section stranded min.
0.14 mm²
Conductor cross section stranded max.
1.5 mm²
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 3 / 6
Jul 26, 2011
FLT-CP-PLUS-3C-350 Order No.: 2882653
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2882653
Conductor cross section solid min.
0.14 mm²
Conductor cross section solid max.
1.5 mm²
Conductor cross section AWG/kcmil min.
28
Conductor cross section AWG/kcmil max
16
Maximum operating voltage Umax. AC
250 V AC
Maximum operating voltage Umax DC
125 V DC
Max. operating current Imax
1 A AC (inductive)
1 A AC (ohmic)
30 mA DC (inductive)
200 mA DC (ohmic)
Standards
Standards/regulations
IEC 61643-1 2005
EN 61643-11 2002
EN 61643-11/A11 2007
UL 1449 ed. 2
Certificates / Approvals
Certification
CUL, GOST, UL
Accessories
Item
Designation
Description
FLT-CP-PLUS-350-ST
Type 1 / Class I / B arrester (lightning arrester) replacement plug
for paths L-N and L-PEN, can be combined with FLASHTRAB
compact series of products.
1051993
B-STIFT
Marker pen, for manual labeling of unprinted Zack strips, smearproof and waterproof, line thickness 0.5 mm
2749589
ZBN 18,LGS:ERDE
Marking labels, printed horizontally, strips with 5 labels, GND
(grounding symbol), color: White
General
2859913
Marking
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 4 / 6
Jul 26, 2011
FLT-CP-PLUS-3C-350 Order No.: 2882653
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2882653
2749576
ZBN 18,LGS:L1-N,ERDE
Marker labels, printed horizontally, strips with 5 labels, L1, L2, L3,
N, GND, color: white
0800763
ZBN 18:SO/CMS
Marker labels, 5-section, special printing, labeled according to
customer requirements (Please specify the required marking with
order), for terminal width: 17.5 mm, color: White
2809128
ZBN 18:UNBEDRUCKT
Unprinted marker labels, strips with 5 labels for individual labeling
with M-PEN or CMS system, for terminal block width: 17.5 mm,
color: White
Diagrams/Drawings
Dimensioned drawing
Circuit diagram
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 5 / 6
Jul 26, 2011
FLT-CP-PLUS-3C-350 Order No.: 2882653
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2882653
Address
PHOENIX CONTACT Inc., USA
586 Fulling Mill Road
Middletown, PA 17057,USA
Phone (800) 888-7388
Fax (717) 944-1625
http://www.phoenixcon.com
© 2011 Phoenix Contact
Technical modifications reserved;
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
Page 6 / 6
Jul 26, 2011