https://www.phoenixcontact.com/us/products/2897211
Bus coupler - IL DN BK DI8 DO4-PAC - 2897211
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
DeviceNet™ bus coupler, 8 inputs, 24 V DC, 4 outputs, 24 V DC, 500 mA, complete with I/O connectors
Product Description
The bus coupler for the DeviceNet™ has 4 digital outputs and 8 digital inputs. This package contains all the necessary Inline connectors for connecting
the supply and the I/Os.
For project planning, the corresponding EDS (device master data) file for the product is provided in the download center.
The Inline terminals can be labeled using pull-out labeling fields. The fields have insert cards that can be labeled individually to suit the application.
Additionally, there is the ZBFM-6... Zack marker strip for labeling the terminal points.
Product Features
■
■
■
■
■
DeviceNet™ connection using TWIN-COMBICON plug
62 terminals can be connected
Automatic speed detection of the system bus
Address can be set via DIP switches or software
Slave function in DeviceNet™ network
Key Commercial Data
Packing unit
1 pc
Weight per Piece (excluding packing)
352.4 g
Custom tariff number
85176200
Country of origin
Germany
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
80 mm
Height
119.8 mm
03/14/2016 Page 1 / 6
https://www.phoenixcontact.com/us/products/2897211
Bus coupler - IL DN BK DI8 DO4-PAC - 2897211
Technical data
Dimensions
Depth
71.5 mm
Note on dimensions
Specfications with connectors
Ambient conditions
Ambient temperature (operation)
-25 °C ... 55 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Permissible humidity (operation)
10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)
10 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection
IP20
General
Mounting type
DIN rail
Net weight
320 g
Note on weight specifications
with connectors
Diagnostics messages
Short-circuit / overload of the digital outputs Yes
Sensor supply failure Yes
Failure of the actuator supply Yes
Interfaces
Fieldbus system
DeviceNet™
Designation
DeviceNet™
Connection method
TWIN COMBICON
Transmission speed
500 kBit/s, 250 kBit/s, 125 kBit/s (Can be set via DIP switch or
programmed)
Number of positions
10
Fieldbus system
Lokalbus
Designation
Inline local bus
Connection method
Inline data jumper
Transmission speed
500 kBit/s / 2 MBit/s (Automatic detection, no combined system)
System limits of the bus coupler
Number of supported devices
max. 63 (per station)
Number of local bus devices that can be connected
max. 61 (on board I/Os are two devices)
Number of devices with parameter channel
max. 8
Number of supported branch terminals with remote bus branch
0
Power supply for module electronics
Connection method
Spring-cage connection
03/14/2016 Page 2 / 6
https://www.phoenixcontact.com/us/products/2897211
Bus coupler - IL DN BK DI8 DO4-PAC - 2897211
Technical data
Power supply for module electronics
Designation
Bus coupler supply UBC; Communications power UL (7.5 V) and the analog
supply UANA (24 V) are generated from the bus coupler supply.
Supply voltage
24 V DC (via Inline connector)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Supply current
typ. 70 mA
Current consumption
max. 0.9 A (from UBK)
Power dissipation
max. 3.5 W (entire device)
Communications power UL
7.5 V DC
Current consumption
0.8 A
Power consumption
typ. 1.7 W
Inline potentials
Communications power UL
7.5 V DC ±5 %
Power supply at UL
max. 0.8 A DC
Main circuit supply UM
24 V DC
Supply voltage range UM
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply at UM
max. 8 A DC (Sum of UM + US)
Current consumption from UM
max. 8 A DC
Segment circuit supply US
24 V DC
Supply voltage range US
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply at US
max. 8 A DC (Sum of UM + US)
Current consumption from US
max. 8 A DC
I/O supply voltage UANA
24 V DC
Supply voltage range UANA
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply at UANA
max. 0.5 A DC
Digital inputs
Input name
Digital inputs
Description of the input
EN 61131-2 type 1
Connection method
Inline connector
3-conductor
Number of inputs
8
Typical response time
approx. 500 µs
Protective circuit
Protection against polarity reversal Suppressor diode
Input voltage
24 V DC
Input voltage range "0" signal
-30 V DC ... 5 V DC
Input voltage range "1" signal
15 V DC ... 30 V DC
Nominal input current at UIN
typ. 3 mA
03/14/2016 Page 3 / 6
https://www.phoenixcontact.com/us/products/2897211
Bus coupler - IL DN BK DI8 DO4-PAC - 2897211
Technical data
Digital inputs
Typical input current per channel
typ. 3 mA
Delay at signal change from 0 to 1
1.2 ms
Delay at signal change from 1 to 0
1.2 ms
Digital outputs
Output name
Digital outputs
Connection method
Inline connector
3-conductor
Number of outputs
4
Protective circuit
Short-circuit and overload protection Free running circuit
Output voltage
24 V DC -1 V (At nominal current)
Nominal output voltage
24 V DC
Maximum output current per channel
500 mA
Maximum output current per module / terminal block
2A
Maximum output current per module
2A
Nominal load, inductive
12 VA (1.2 H; 48 Ω)
Nominal load, lamp
12 W
Nominal load, ohmic
12 W
Standards and Regulations
Conformity with EMC directives
Noise immunity test in accordance with EN 61000-6-2 Electrostatic
discharge (ESD) EN 61000-4-2/IEC 61000-4-2 Criterion B, 6 kV contact
discharge, 8 kV air discharge
Noise immunity test in accordance with EN 61000-6-2 Electromagnetic
fields EN 61000-4-3/IEC 61000-4-3 Criterion A; Field intensity: 10 V/m
Noise immunity test in accordance with EN 61000-6-2 Fast transients
(burst) EN 61000-4-4/IEC 61000-4-4 Criterion A, all interfaces 1
kVCriterion B, all interfaces 2 kV
Noise immunity test in accordance with EN 61000-6-2 Transient
overvoltage (surge) EN 61000-4-5/IEC 61000-4-5 Criterion B, supply lines
DC: 0.5 kV/0.5 kV (symmetrical/asymmetrical), fieldbus cable shield 1 kV
Noise immunity test in accordance with EN 61000-6-2 Conducted
interference EN 61000-4-6/IEC 61000-4-6 Criterion A; Test voltage 10 V
Noise emission test as per EN 61000-6-4 EN 55011 Class A
Mechanical tests
Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g
Shock in acc. with EN 60068-2-27/IEC 60068-2-27 Operation: 25g, 11 ms
duration, semi-sinusoidal shock impulse
Connection in acc. with standard
CUL
Protection class
III, IEC 61140, EN 61140, VDE 0140-1
03/14/2016 Page 4 / 6
https://www.phoenixcontact.com/us/products/2897211
Bus coupler - IL DN BK DI8 DO4-PAC - 2897211
Classifications
eCl@ss
eCl@ss 4.0
27250203
eCl@ss 4.1
27250203
eCl@ss 5.0
27250203
eCl@ss 5.1
27242608
eCl@ss 6.0
27242608
eCl@ss 7.0
27242608
eCl@ss 8.0
27242604
eCl@ss 9.0
27242604
ETIM
ETIM 2.0
EC001434
ETIM 3.0
EC001604
ETIM 4.0
EC001604
ETIM 5.0
EC001599
UNSPSC
UNSPSC 6.01
43172015
UNSPSC 7.0901
43201404
UNSPSC 11
43172015
UNSPSC 12.01
43201404
UNSPSC 13.2
43201404
Approvals
Approvals
Approvals
UL Recognized / cUL Recognized / cULus Recognized
Ex Approvals
UL Listed / cUL Listed / cULus Listed
Approvals submitted
Approval details
03/14/2016 Page 5 / 6
https://www.phoenixcontact.com/us/products/2897211
Bus coupler - IL DN BK DI8 DO4-PAC - 2897211
Approvals
UL Recognized
cUL Recognized
cULus Recognized
Drawings
Connection diagram
Dimensional drawing
PWR DO4 DI4 DI4
1 2 3 4
119,8
IN6
+
US -
+24 V
+24 V
DeviceNet
TM
IN8
71,5
OUT2
+
UM
OUT3
+
UBK -
Phoenix Contact 2016 © - all rights reserved
http://www.phoenixcontact.com
03/14/2016 Page 6 / 6