ILB S3 24 DI16 DIO16-2TX
1 2
1 2
E
1 2
E
1 2
Inline Block IO Module for
SERCOS III With 16 Digital Inputs and
16 Digital Inputs/Outputs
E
1 2
1
UA A2
U
1
US US2
K1
LN
T1
AC
S3
K2
LN
T2
UL
PW
3 4
IO
PW
1 2
3 4
IO
3 4
IO
1 2
3 4
IO
3 4
1 2
3 4
3 4
3 4
I4
I3
I2
I1
4
3
2
1
R2
R1
AC
AUTOMATIONWORX
Data Sheet
7606_en_00
© PHOENIX CONTACT - 09/2007
Description
The ILB S3 24 DI16 DIO16-2TX module is designed for use
within a SERCOS III network. It is used to acquire digital
input signals and output digital signals.
Features of SERCOS III
–
–
2 x Ethernet twisted pair according to 802.3u with
auto negotiation and auto crossing, connected via an
integrated managed 3-port switch (2 external ports,
1 internal port)
Transmission speed of 100 Mbps
Features of Inputs
–
–
–
–
Connections for 16 digital sensors
Connection of sensors in 2 and 3-wire technology
Maximum permissible load current per sensor: 125 mA
Maximum permissible load current from the sensor
supply: 2.0 A
Features of Combined Inputs or Outputs
–
–
–
–
–
–
–
–
–
Connections for 16 digital sensors/actuators
Each individual channel can be used as an input or an
output
Connection of sensors in 2 and 3-wire technology
Maximum permissible load current per sensor: 125 mA
Maximum permissible load current from the sensor
supply: 2.0 A
Connection of actuators in 2-wire technology
Nominal current per output: 0.5 A
Total current of all outputs: 8 A
Short-circuit and overload protected
outputs
Please refer to the "Assembly and Removal of Inline Block IO Modules" application note (see "Documentation"
on page 2).
Make sure you always use the latest documentation.
It can be downloaded at www.download.phoenixcontact.com.
A conversion table is available on the Internet at
www.download.phoenixcontact.com/general/7000_en_00.pdf.
ILB S3 24 DI16 DIO16-2TX
Ordering Data
Product
Description
Type
Order No.
Pcs./Pck.
ILB S3 24 DI16 DIO16-2TX
2897570
1
Accessories: Ethernet
Description
Type
Order No.
Pcs./Pck.
Gray RJ45 connector set for linear cable
FL PLUG RJ45 GR/2
2744856
2
Green RJ45 connector set for crossed cable
FL PLUG RJ45 GN/2
2744571
2
Inline Block IO module for SERCOS III with 16 digital inputs and
16 digital inputs/outputs
Double sheathed Ethernet cable
FL CAT5 HEAVY
2744814
1
Stranded Ethernet cable
FL CAT5 FLEX
2744830
1
Assembly tool for RJ45 connector
FL CRIMPTOOL
2744869
1
Matching dust protection covers and safety systems for RJ45 connections can be found in the product range from
Reichle & De-Massari AG/Switzerland.
Accessories: Other
Description
Type
Order No.
Pcs./Pck.
End clamp for securing the module on the DIN rail for a horizontal mounting
position; to the right and left of the module
CLIPFIX 35
3022218
50
End clamp for securing the module on the DIN rail for a vertical mounting
position; above and below the module
E/AL-NS 35
1201662
10
Documentation
Description
Type
Order No.
Pcs./Pck.
"Assembly and Removal of Inline Block IO Modules" application note
AH ILB INSTALLATION
9014931
1
Technical Data
General Data
Housing dimensions with connectors (width x height x depth)
156 mm x 55 mm x 141 mm
Weight
500 g (with connectors)
Operating mode
Process data mode with 2 words
Transmission speed
100 Mbps with auto negotiation and auto crossing
Connection method for sensors and actuators
2 and 3-wire technology
Regulations
Developed according to VDE 0160/EN 50178/IEC 62103
Ambient temperature (operation)
-25°C to +60°C
Ambient temperature (storage/transport)
-25°C to +85°C
Permissible humidity (operation/storage/transport)
10% to 95%, according to EN 61131-2
Permissible air pressure (operation/storage/transport)
70 kPa to 108 kPa (up to 3000 m above sea level)
Degree of protection according to IEC 60529
IP20
Protection class
Class 3 according to EN 61113-2, IEC 61113-2
Connection data for Inline connectors
Connection method
Spring-cage terminals
Conductor cross-section
0.2 mm2 to 1.5 mm2 (solid or stranded), 24 - 16 AWG
Air and creepage distances
According to DIN VDE 0110/IEC 60664, IEC 60664A,
DIN VDE 0160/EN 50178/IEC 62103
Housing material
Plastic, PVC-free, PBT, self-extinguishing (V0)
Pollution degree according to
EN 60664-1/IEC 60664-1, EN 61131-2/IEC 61131-2
2; condensation not permitted during operation
Surge voltage category
II
7606_en_00
PHOENIX CONTACT
2
ILB S3 24 DI16 DIO16-2TX
Housing Dimensions
55
141
120
156
7151B005
Figure 1
Module housing dimensions (in mm)
Electrical Isolation/Isolation of the Voltage Areas
Test Distance
Test Voltage
I/O/logic
500 V AC, 50 Hz, 1 min.
I/O/functional earth ground
500 V AC, 50 Hz, 1 min.
Logic/functional earth ground
500 V AC, 50 Hz, 1 min.
Ethernet interface signals/logic
1500 V rms, 50 Hz to 60 Hz, 1 min.
Mechanical Requirements
Vibration test sinusoidal vibrations according to
EN 60068-2-6/IEC 60068-2-6
5g load, 2.5 hours in each space direction
Shock test according to EN 60068-2-27/IEC 60068-2-27
25g load for 11 ms, half sinusoidal wave,
3 shocks in each space direction and orientation
Broadband noise according to EN 60068-2-64/IEC 60068-2-64
0.78g load, 2.5 hours in each space direction
7606_en_00
PHOENIX CONTACT
3
ILB S3 24 DI16 DIO16-2TX
Conformance With EMC Directive 89/336/EEC and 2004/108/EC
Noise Immunity Test According to EN 61000-6-2
Electrostatic discharge (ESD)
EN 61000-4-2
IEC 61000-4-2
Criterion B
Electromagnetic fields
EN 61000-4-3
IEC 61000-4-3
Criterion A
Fast transients (burst)
EN 61000-4-4
IEC 61000-4-4
Criterion B
Remote bus: 2 kV
Power supply: 2 kV
I/O cables: 2 kV
4 kV contact discharge
8 kV air discharge
Field strength: 10 V/m
Criterion A
All interfaces: 1 kV
Surge voltage
EN 61000-4-5
IEC 61000-4-5
Criterion B
DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical)
Signal lines: ±1 kV/±1 kV (symmetrical/asymmetrical)
Conducted interference
EN 61000-4-6
IEC 61000-4-6
Criterion A
Test voltage 10 V
Noise Emission Test According to EN 61000-6-4
Noise emission of housing
EN 55011
Class A
Interface
SERCOS III interface
2 x SERCOS III via RJ45 connectors;
Shielding via parallel connection of R, C, and VDR
24 V Module Supply (Logic, Sensor, and Actuator Supply)
Nominal value
24 V DC
Tolerance
-15%/+20% according to EN 61131-2
Ripple
±5% according to EN 61131-2
Permissible range
19.2 V to 30 V
Current consumption at UL
90 mA
Safety equipment
Surge protection and protection against polarity reversal
Connection
Via power connectors
Digital Outputs
Number
16 (can be freely selected)
Connection method for actuators
2-wire technology
Nominal output voltage UOUT
24 V DC
Differential voltage for Inom
≤1V
Nominal current Inom per channel
0.5 A
Total current
8A
Protection
Short circuit; overload
Delay time
tON
Approximately 40 μs, typical; 200 µs, maximum
tOFF
Approximately 150 μs, typical; 400 µs, maximum
Nominal load
Ohmic
48 Ω/12 W
Lamp
12 W
Inductive
12 VA (1.2 H, 50 Ω)
Switching frequency with nominal inductive load
0.5 Hz (1.2 H, 50 Ω), maximum
Overload response
Auto restart
Response with inductive overload
Output may be damaged
Reverse voltage protection against short pulses
Protected against reverse voltages
Resistance to permanently applied reverse voltages
Protected against reverse voltages, permissible current 2 A, maximum
Response upon power down
The output follows the supply voltage without delay
7606_en_00
PHOENIX CONTACT
4
ILB S3 24 DI16 DIO16-2TX
Digital Outputs (Continued)
Limitation of the voltage induced on circuit interruption
-41.0 V
Single maximum energy in free running
1 J, maximum
Protective circuit type
Integrated free running circuit in the output chip
Overcurrent shutdown
0.7 A, minimum
Maximum output current when switched off
10 µA
When not loaded, a voltage can be measured even at an output that is not set.
Error message sent to the higher-level control system
Short circuit/overload of outputs
Digital Inputs
Number
32 (16 fixed, 16 can be freely selected)
Connection method for sensors
2 and 3-wire technology
Input design
According to EN 61131-2 Type 1
Definition of switching thresholds
Maximum low-level voltage
ULmax < 5 V
Minimum high-level voltage
UHmin > 15 V
Common potentials
Sensor supply US, ground
Nominal input voltage UIN
24 V DC
Permissible range
-30 V < UIN < +30 V DC
Nominal input current for UIN
5 mA, typical
Current flow
Linear in the range 1 V < UIN < 30 V
Delay time
tON
Approximately 50 μs, typical; 100 µs, maximum
tOFF
Approximately 145 μs, typical; 400 µs, maximum
Permissible cable length to the sensor
100 m
Use of AC sensors
AC sensors in the voltage range < UIN are limited in application
Error message sent to the higher-level control system
Sensor supply not present
Sensor supply short circuit/overload
Power Dissipation
Formula to Calculate the Power Dissipation of the Electronics
2
2
16
2
32
PTOT = 1.68 W + (IS36 + IS710 ) x 0.06 W + S (0.129 W + ILn x 0.28 W + ILn x 0.35 V) + S 0.125 W
n=1
Where
PTOT
n
ILn
m
IS36
IS710
m=1
Total power dissipation of the module
Index of the number of set outputs (n = 1 to 16)
Load current of output n
Index of the number of set inputs (m = 1 to 32)
Current from the sensor supply at slots 3 to 6
Current from the sensor supply at slots 7 to 10
Limitation of Simultaneity
No limitation of simultaneity, derating
7606_en_00
PHOENIX CONTACT
5
ILB S3 24 DI16 DIO16-2TX
Derating
Ambient Temperature (TA)
Outputs, Connectors 3 to 6
Total Current (ITOT)
-25°C to +30°C
8A
A
+30°C to +60°C
8 A - ((TA - 30°C) x 0.2 A/°C)
8
ITOT
2
0
-25
0
30
60
°C
60
°C
TA
6992B012
Sensor Supply, Connectors 3 to 6
-25°C to +30°C
2A
+30°C to +60°C
2 A - ((TA - 30°C) x 0.05 A/°C)
A
Sensor Supply, Connectors 7 to 10
2
-25°C to +30°C
2A
+30°C to +60°C
2 A - ((TA - 30°C) x 0.05 A/°C)
1.5
1
ITOT
0.5
0
-25
6992B013
0
30
TA
Approvals
For the latest approvals, please visit www.download.phoenixcontact.com or eshop.phoenixcontact.com.
7606_en_00
PHOENIX CONTACT
6
ILB S3 24 DI16 DIO16-2TX
Internal Circuit Diagram
LNK1/2 ACT1/2
S3
8x
8x
8x
8x
mP
3.3 V
24 V
UA1
UA2
DIO1...8
DIO9..16
DI1...8
DI9..16
US2
UL
US1
16x
IN/
OUT
16x
IN
SERCOS III
7488B004
Figure 2
Internal wiring of the terminal points
Key:
Shielding
Microprocessor
The shielding ground of the connected twisted
pair cables is electrically connected to FE.
When connecting network segments, avoid
ground loops, potential transfers, and voltage
equalization currents via the braided shield.
Switch
Electrostatic discharge
LED
µ P
Relevant Notes
Transmitter
Electrical isolation
Optocoupler
The module contains components that can be
damaged or destroyed by electrostatic
discharge. When handling this module,
observe the necessary safety precautions
against electrostatic discharge (ESD)
according to EN 61340-5-1 and EN 61340-5-2,
as well as IEC 61340-5-1 and IEC 61340-5-2..
Housing
Short-circuit-proof sensor supply
7606_en_00
Only personnel authorized by Phoenix Contact
are permitted to open the housing.
PHOENIX CONTACT
7
ILB S3 24 DI16 DIO16-2TX
Local Diagnostic and Status Indicators
A
S3
1 E
2
3
4
LNK1
ACT1
LNK2
ACT2
I1
E
1 2
E
1 2
1
UA A2
U
1
US US2
K1
LN
T1
AC
K2
LN
T
AC
2
UL
3 4
1 2
3 4
3 4
1 2
3 4
3 4
1 2
3 4
4
I2
I3
2
3
4
I4
4
1 2
3 4
3 4
I4
D
I2
I1
4
IO
3
IO
2
IO
1 E
2
3
4
1
IO
R2
PW
R1
PW
US1
US2
1
2
3
IO2
4
1 E
2
1
3
3
IO3
4
PWR1
2
IO4
4
C
UA1
UA2
UL
PWR2
B
7488B002
Local diagnostic and status indicators
Designation
Color
A: SERCOS III
S3
Green
ON
Flashing, 4 Hz
Red
ON
Flashing, 4 Hz
Orange
ON
Flashing, 4 Hz
OFF
Green
ON
ACT1/2
Yellow
ON
B: PWR 1/PWR 2
US1/2
Green
ON
OFF
UA1/2
Green
ON
OFF
7606_en_00
1
2
3
I3
IO1
LNK1/2
1
2
1 2
E
1 2
Figure 3
1
3
Meaning
CP4 no error
Loop back activated
SIII C1D (Class 1 diagnostics)
Communication error (S-0-1003)
CP0 ... CP3
Identification (bit 15 in interface control)
Used for address assignment and configuration errors.
24 V communications power not present or no SERCOS III communication
Link1/2
Connection via Ethernet to a module via port 1/2 established
Activity1/2
If the yellow LED is on, this indicates transmission or reception of a telegram at port 1/2
Sensor supply 1/2
Sensor supply 1/2 present
Sensor supply 1/2 not present
Actuator supply 1/2
Actuator supply 1/2 present
Actuator supply 1/2 not present
PHOENIX CONTACT
8
ILB S3 24 DI16 DIO16-2TX
Designation
UL
C: IO1 ... IO4
E
1 ... 4
D: I1 ... I4
E
1 ... 4
Color
Green
ON
OFF
Meaning
24 V communications power
24 V communications power present
24 V communications power not present
Red
ON
OFF
Yellow
ON
OFF
Output error message (see note below)
Short circuit or overload of outputs
No output error
Status of the inputs/outputs
Input/output active
Input/output not active
Red
ON
OFF
Yellow
ON
OFF
Sensor supply error
Short circuit or overload of one of the sensor supplies
No sensor supply error
Status indicators of the inputs
Input active
Input not active
If the error LED (E) of a group of eight outputs lights up (connector 3/4 or connector 5/6), this indicates that a
short circuit or overload is present at one or more of the outputs in this group.
7606_en_00
PHOENIX CONTACT
9
ILB S3 24 DI16 DIO16-2TX
Connection of SERCOS III, Supply,
Inputs, and Outputs
Connection of SERCOS III
By default upon delivery, the Ethernet connections have
been set to auto negotiation with auto crossing.
The module can be connected using, e.g., a 1:1 cable or a
crossover cable.
1 2
1 2
E
1 2
E
1 2
E
1 2
1
UA A2
U
For additional information about Ethernet
cabling, please refer to www.iaona-eu.com.
1
US US2
K1
LN
S3
T1
AC
K2
LN
T2
AC
UL
3 4
1 2
3 4
3 4
1 2
3 4
3 4
1 2
3 4
3 4
3 4
I4
I3
I2
I1
4
IO
3
IO
2
IO
1
IO
R2
PW
RECONF
R1
PW
X7E1
Connect SERCOS III to the module via an 8-pos.
RJ45 connector. For the pin assignment of the female
connector, please refer to the following table:
Pin
1
2
3
4
5
6
7
8
Assignment
TD+ (transmit data +)
TD- (transmit data -)
RD+ (receive data +)
Reserved
Reserved
RD- (receive data -)
Reserved
Reserved
X7E2
7487B006
Figure 5
8-pos. RJ45 female connectors
Reconfiguration Button
The reconfiguration button is currently not supported.
Pin 4
Pin 3
Pin 2
Pin 1
Pin 8
Pin 7
Pin 6
Pin 5
RJ45
Figure 4
7606_en_00
Pin assignment of the RJ45 female connector
PHOENIX CONTACT
10
ILB S3 24 DI16 DIO16-2TX
Connection of Supply, Actuators, and Sensors
1
1
1.1
1
1
2.1
1.2
2
2
2.2
1.4
3
4
3
4
E
1 2
2.3
E
1 2
E
1 2
2.4
1
UA A2
U
1
US US2
LN
S3
1.5
1.6
5
5
6
6
1-2
2.5
2.6
1.1
1
1
2.1
1.2
2
2
2.2
3
3
2.3
4
4
5
5
6
6
1 2
1 2
1.3
2
2
LN
K1
AC
T1
K2
AC
T2
UL
3 4
1 2
3 4
3 4
1 2
3 4
4
IO
3 4
1 2
3 4
3 4
3 4
I4
1.3
I3
I2
I1
1.4
3
IO
2.4
2
IO
1
IO
R2
PW
R1
PW
1.5
1.6
2.5
2.6
3-10
7487B003
Figure 6
Terminal point assignment of the Inline
connectors
Terminal Point Assignment of the Power Connectors (Connectors 1 and 2 in Figure 6)
Terminal Point
Assignment
Connector 1 (PWR 1)
1.1
24 V sensor supply US1
(Supply for the sensors at
connectors 3 to 6)
1.2
24 V communications power UL
1.3
GND
1.4
FE
1.5
24 V communications power UL
1.6
GND
Connector 2 (PWR 2)
1.1
Actuator supply UA1
(Supply for the sensors at
connectors 3 to 4)
1.2
24 V communications power UL
1.3
GND
1.4
FE
1.5
24 V communications power UL
1.6
GND
Terminal Point
Assignment
2.1
24 V sensor supply US2
(Supply for the sensors at
connectors 7 to 10)
24 V communications power UL
GND
FE
24 V communications power UL
GND
2.2
2.3
2.4
2.5
2.6
2.1
2.2
2.3
2.4
2.5
2.6
Actuator supply UA2
(Supply for the sensors at
connectors 5 to 6)
24 V communications power UL
GND
FE
24 V communications power UL
GND
The terminal points can have a total current of 8 A per terminal point. The maximum current carrying capacity
of 8 A must not be exceeded. If the total output current in your application is > 8 A, supply the module via a
minimum of two terminal points connected in parallel.
7606_en_00
PHOENIX CONTACT
11
ILB S3 24 DI16 DIO16-2TX
The supply points have the same ground potential.
Terminal points 1.2, 1.5, 2.2, 2.5 of the PWR1 and PWR2 connectors (24 V communications power UL) are
electrically connected with one another. This means that power can be supplied via one power supply with
forwarding to 1.1, 2.1 of the PWR1 connector (US1 and US2) and to 1.1, 2.1 of the PWR2 connector
(UA1 and UA2). In addition, terminal points 1.3, 1.6, 2.3, 2.6 of the PWR1 and PWR2 connectors (GND) are
electrically connected with one another. See connection example on page 13.
This means that power can be supplied via one power supply.
Terminal Point Assignment of the Input and Output Connectors (Connectors 3 to 6 in Figure 6 on page 11)
Terminal Point
Connector 3 Connector 4
(IO1)
(IO2)
1.1, 2.1
1.1, 2.1
1.2, 2.2
1.2, 2.2
1.3, 2.3
1.3, 2.3
1.4, 2.4
1.4, 2.4
1.5, 2.5
1.5, 2.5
1.6, 2.6
1.6, 2.6
Assignment
Connector 5
(IO3)
1.1, 2.1
1.2, 2.2
1.3, 2.3
1.4, 2.4
1.5, 2.5
1.6, 2.6
Connector 6
(IO4)
1.1, 2.1
1.2, 2.2
1.3, 2.3
1.4, 2.4
1.5, 2.5
1.6, 2.6
Signal input (IN) or output (OUT)
Sensor voltage UI1 for 2 and 3-wire termination
Ground contact (GND) for 3-wire termination
Signal input (IN) or output (OUT)
Initiator supply UI1 for 2 and 3-wire termination
Ground contact (GND) for 3-wire termination
The channels on connectors 3 to 6 can be used as inputs or outputs. Configuration is not required.
If a channel is used as an input, this input must not be set as an output.
Terminal Point Assignment of the Input Connectors (Connectors 7 to 10 in Figure 6 on page 11)
Terminal Point
Connector 7 Connector 8
(I1)
(I2)
1.1, 2.1
1.1, 2.1
1.2, 2.2
1.2, 2.2
1.3, 2.3
1.3, 2.3
1.4, 2.4
1.4, 2.4
1.5, 2.5
1.5, 2.5
1.6, 2.6
1.6, 2.6
7606_en_00
Assignment
Connector 9
(I3)
1.1, 2.1
1.2, 2.2
1.3, 2.3
1.4, 2.4
1.5, 2.5
1.6, 2.6
Connector 10
(I4)
1.1, 2.1
1.2, 2.2
1.3, 2.3
1.4, 2.4
1.5, 2.5
1.6, 2.6
Signal input (IN)
Sensor voltage UI2 for 2 and 3-wire termination
Ground contact (GND) for 3-wire termination
Signal input (IN)
Initiator supply UI2 for 2 and 3-wire termination
Ground contact (GND) for 3-wire termination
PHOENIX CONTACT
12
ILB S3 24 DI16 DIO16-2TX
Connection Examples
Module With Three Supplies UL
(US1 and US2 Jumpered), UA1, UA2
3
2
2
1
2
1
2
1
2
1
2
1
5
4
2
1
2
1
6
2
1
8
7
2
1
2
1
9 10
2
1
2
1
11
11
11
11
11
11
1
1
11
11
11
11
11
11
11
1
2
22
22
22
22
22
22
22
2
2
22
22
22
22
22
22
22
2
3
33
33
33
33
33
33
33
3
3
33
33
33
33
33
33
33
3
4
44
44
44
44
44
44
44
4
4
44
44
44
44
44
44
44
4
5
55
55
55
55
55
55
55
5
5
55
55
55
55
55
55
55
5
6
66
66
66
66
66
66
66
6
6
66
66
66
66
66
66
66
6
+
-
UA1 UA2
B
A
+
-
UL
B
C
A
B
A
B
C
7488A007
Connection example with three supplies
+24 V
IN 30
11
+24 V
IN 15
1
A
Figure 7
2
IN 31
+24 V
1
3
2
OUT 14
2
US1 US2 UA1 UA2 1
10
OUT 6
UL
-
1
9
SERCOS III
+
2
8
+24 V
IN 30
-
1
7
IN 31
+24 V
+
2
6
OUT 14
SERCOS III
1
5
4
+24 V
IN 15
1
OUT 6
US1 US2
Module With One Supply UL
(US1, US2, UA1 and UA2 Jumpered)
7488A008
Figure 8
Connection example with one supply
A 2-wire termination for actuator
B 2-wire termination for sensor
C 3-wire termination for sensor
The numbers above the module illustration indicate the connector slots.
The module has an FE spring (metal clip) on the bottom of the electronics base. This spring establishes an
electrical connection to the DIN rail. Use grounding terminals to connect the DIN rail to protective earth ground.
The modules are grounded when snapped onto the DIN rail.
To ensure reliable functional earth grounding of the modules even when the DIN rail is dirty or the metal clip
is damaged, Phoenix Contact also recommends grounding the modules via one of the FE terminal points.
7606_en_00
PHOENIX CONTACT
13
ILB S3 24 DI16 DIO16-2TX
Mapping of Inputs and Outputs to SERCOS III
Data Length
2 words IN/1 word OUT
Assignment of Terminal Points to the OUT Process Data Word (Slot 3 to 6)
(Word.bit) view
Bit
Word 2
15
14
13
Bit
12
11
10
9
8
7
6
5
Byte 0
(Byte.bit) view
7
Slot
6
5
4
3
4 (IO2)
4
3
2
1
0
2
1
0
Byte 1
2
1
0
7
3 (IO1)
6
5
4
3
6 (IO4)
5 (IO3)
Terminal point
Signal output (OUT)
2.4
1.4
2.1
1.1
2.4
1.4
2.1
1.1
2.4
1.4
2.1
1.1
2.4
1.4
2.1
1.1
Terminal point (GND)
2.6
1.6
2.3
1.3
2.6
1.6
2.3
1.3
2.6
1.6
2.3
1.3
2.6
1.6
2.3
1.3
Status indicator, LED
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
6
5
4
3
2
1
0
1
0
Assignment of Terminal Points to the IN Process Data Word (Slot 3 to 6)
Word 0
(Word.bit) view
Bit
15
14
13
11
10
9
8
7
Byte 0
(Byte.bit) view
Bit
12
7
6
4
3
2
Terminal point
Signal input (IN)
2.4
1.4
2.1
1.2
2.4
1.4
Terminal point
Sensor voltage UI1
2.5
1.5
2.2
1.2
2.5
Terminal point (GND)
2.6
1.6
2.3
1.3
Status indicator, LED
4
3
2
1
Slot
5
Byte 1
0
7
6
2.1
1.1
2.4
1.4
1.5
2.2
1.2
2.5
2.6
1.6
2.3
1.3
4
3
2
1
4 (IO2)
1
4
3
2
2.1
1.1
2.4
1.4
2.1
1.1
1.5
2.2
1.2
2.5
1.5
2.2
1.2
2.6
1.6
2.3
1.3
2.6
1.6
2.3
1.3
4
3
2
1
4
3
2
1
6
5
4
3
2
1
0
2
1
0
3 (IO1)
5
6 (IO4)
5 (IO3)
Assignment of Terminal Points to the IN Process Data Word (Slot 7 to 10)
Word 1
(Word.bit) view
Bit
15
14
13
Bit
12
11
10
9
8
7
Byte 2
(Byte.bit) view
7
Slot
6
5
4
3
8 (I2)
Byte 3
2
1
0
7
7 (I1)
6
5
4
3
10 (I4)
9 (I3)
Terminal point
Signal input (IN)
2.4
1.4
2.1
1.2
2.4
1.4
2.1
1.1
2.4
1.4
2.1
1.1
2.4
1.4
2.1
1.1
Terminal point
Sensor voltage UI1
2.5
1.5
2.2
1.2
2.5
1.5
2.2
1.2
2.5
1.5
2.2
1.2
2.5
1.5
2.2
1.2
Terminal point (GND)
2.6
1.6
2.3
1.3
2.6
1.6
2.3
1.3
2.6
1.6
2.3
1.3
2.6
1.6
2.3
1.3
Status indicator, LED
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
7606_en_00
PHOENIX CONTACT
14
ILB S3 24 DI16 DIO16-2TX
SERCOS III
The module supports SERCOS III V1.1.
Module-specific data is described in the following section.
I/O Control Word (Part of the Realtime Data of the Master Data Telegram (MDT))
Bit 15 (OutEn)
=0
=1
The outputs are disabled
The outputs are enabled
This control bit can be used to disable and reenable the outputs. To activate the outputs, this bit must be set to 1.
I/O Status Word (Part of the Realtime Data of the Drive Telegram (AT))
Bit 15 (OutEn)
=0
=1
The outputs are disabled
The outputs are enabled
Bit 13 (C1D error)
=0
=1
No error has occurred
An error has occurred, error class 1
Class 1 diagnostics can be read with S-0-0390
Class 1 diagnostics are saved and can be deleted with S-0-0099
Not supported
Bit 12 (C2D warning)
S-0-1300
S-0-1300.x.1
S-0-1300.x.3
S-0-1300.x.4
S-0-1300.x.5
S-0-1300.x.7
S-0-1300.x.12
S-0-1300.x.20
Electronic Label
Component Name
Vendor Code
Device Name
Vendor Device ID
Revision
Serial Number
Operational Hours
S-0-0390
0F013410hex
0F012344hex
0F012345hex
Diagnostic Number
Sensor supply US1 or US2 not present/too low
One or more outputs short-circuited or overloaded
Sensor supply US1 or US2 short-circuited/overloaded
7606_en_00
Digital Block I/O
000000xxhex
ILB S3 24 DI16 DIO16-2TX
2897570
xxxxhex
10-digit, hexadecimal notation
Number of operating hours
PHOENIX CONTACT
15
ILB S3 24 DI16 DIO16-2TX
Startup
Default Upon Delivery
By default upon delivery, the following features are
available:
SERCOS address = 55
Reconfiguration Button
The reconfiguration button is currently not supported.
SERCOS Address Assignment
–
–
–
There is no switch for setting the SERCOS address
The module supports automatic address assignment
for the SERCOS address according to SERCOS III
The SERCOS address is saved retentively
For additional information about automatic
address assignment, please refer to the
SERCOS III master documentation.
© PHOENIX CONTACT 09/2007
7606_en_00
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
Phone: +49 - 52 35 - 30 0 • Fax: +49 - 52 35 - 34 12 00
www.phoenixcontact.com
16