https://www.phoenixcontact.com/us/products/2900543
Hybrid motor starter - ELR H3-I-SC- 24DC/500AC-2 - 2900543
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Hybrid motor starter for starting 3~ AC motors up to 500 V AC and 2.4 A output current, with 24 V DC control
voltage, adjustable overload shutdown, and screw connection.
The figure shows the 9 A version
Product Features
■
■
■
■
■
■
■
22.5 mm wide
Low-wear switching
Space saving
Reduction in wiring
Long service life
3-phase loop bridges
Bimetal function can be set up to 9 A
Key Commercial Data
Packing unit
1 pc
Weight per Piece (excluding packing)
260.0 g
Custom tariff number
85371099
Country of origin
Germany
Technical data
Dimensions
Width
22.5 mm
Height
99 mm
Depth
114.5 mm
Ambient conditions
Ambient temperature (operation)
-25 °C ... 70 °C (observe derating)
Ambient temperature (storage/transport)
-40 °C ... 80 °C
03/14/2016 Page 1 / 8
https://www.phoenixcontact.com/us/products/2900543
Hybrid motor starter - ELR H3-I-SC- 24DC/500AC-2 - 2900543
Technical data
Ambient conditions
Degree of protection
IP20
Device supply
Rated control circuit supply voltage US
24 V DC
Control supply voltage range
19.2 V DC ... 30 V DC
Rated control supply current IS
40 mA
Protective circuit
Protection against polarity reversal Parallel polarity protection diode
Surge protection
Input data
Input name
Control input right/left
Rated actuating voltage UC
24 V DC
Voltage range
19.2 V DC ... 30 V DC
Rated actuating current IC
5 mA
Switching threshold
9.6 V (“0” signal)
19.2 V (“1” signal)
Protective circuit
Protection against polarity reversal
Typical turn-off time
< 30 ms
Output data load output
Output name
AC output
Rated operating voltage Ue
500 V AC
Operating voltage range
42 V AC ... 550 V AC
Load current range
180 mA ... 2.4 A (see to derating)
Trigger characteristic in acc. with IEC 60947
Class 10A
Cooling time
20 min. (for auto reset)
Rated operating current at AC-51
2.4 A
Rated operating current at AC-53a
2.4 A
Leakage current
0 mA
Protective circuit
Surge protection Varistor
Output data reply output
Output name
Acknowledge output
Note
Confirmation: floating change-over contact, signal contact
Contact type
1 PDT
Switching capacity according to IEC 60947-5-1
3 A (230 V, AC15)
2 A (24 V, DC13)
General
Switching frequency
≤ 2 Hz (Load-dependent)
03/14/2016 Page 2 / 8
https://www.phoenixcontact.com/us/products/2900543
Hybrid motor starter - ELR H3-I-SC- 24DC/500AC-2 - 2900543
Technical data
General
Mounting position
vertical (horizontal DIN rail, motor output below)
Assembly instructions
alignable, for spacing see derating
Operating mode
100% operating factor
Maximum power dissipation
4.1 W
Minimum power dissipation
0.88 W
Operating voltage display
Green LED
Status display
Yellow LED
Indication
Red LED
Connection data, input side
Connection name
Control circuits
Connection method
Screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section solid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 14
Torque
0.5 Nm ... 0.6 Nm
Connection data, output side
Connection name
Load circuit
Connection method
Screw connection
Stripping length
8 mm
Screw thread
M3
Conductor cross section solid
0.2 mm² ... 2.5 mm²
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 14
Torque
0.5 Nm ... 0.6 Nm
Standards/regulations
Designation
Standards/regulations
Standards/regulations
IEC 60947-1
EN 60947-4-2
IEC 61508
ISO 13849
Insulation characteristics
Rated insulation voltage
500 V
Rated surge voltage
6 kV
03/14/2016 Page 3 / 8
https://www.phoenixcontact.com/us/products/2900543
Hybrid motor starter - ELR H3-I-SC- 24DC/500AC-2 - 2900543
Technical data
Insulation characteristics
Overvoltage category
III
Degree of pollution
2
Designation
Insulation characteristics between the control input and control supply
voltage, and auxiliary circuit to the main circuit
Insulation
Safe isolation (IEC 60947-1) at operating voltage ≤ 300 V AC (e.g.,
230/400 V AC, 277/480 V AC)
Safe isolation (EN 50178) at operating voltage ≤ 300 V A (e.g., 230/400 V
AC, 277/480 V AC)
Basic isolation (IEC 60947-1) at operating voltage 300 ... 500 V AC
Safe isolation (EN 50178) at operating voltage 300 ... 500 V AC
Designation
Isolation characteristics between the control input and control supply
voltage to auxiliary circuit
Insulation
Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC
Safe isolation (EN 50178) in the auxiliary circuit ≤ 300 V AC
UL data
SCCR
100 kA (480 V AC (fuse: 30 A class CC/30 A class J (high fault)))
5 kA (480 V AC (fuse: 20 A RK5 (standard fault)))
FLA
2.4 A (480 V AC)
Group installation
20 A (class RK5, SCCR 5kA, #24 - 14 AWG max. solid and stranded)
30 A (class CC or J, SCCR 100kA, #24 - 14 AWG max, solid and stranded)
Category code
NLDX / NRNT
Standards and Regulations
Designation
Standards/regulations
Standards/regulations
IEC 60947-1
EN 60947-4-2
IEC 61508
ISO 13849
Classifications
eCl@ss
eCl@ss 4.0
27371102
eCl@ss 4.1
27371102
eCl@ss 5.0
27371601
eCl@ss 5.1
27371601
eCl@ss 6.0
27371601
eCl@ss 7.0
27371601
eCl@ss 8.0
27370905
03/14/2016 Page 4 / 8
https://www.phoenixcontact.com/us/products/2900543
Hybrid motor starter - ELR H3-I-SC- 24DC/500AC-2 - 2900543
Classifications
ETIM
ETIM 2.0
EC000066
ETIM 3.0
EC000066
ETIM 4.0
EC000066
ETIM 5.0
EC002055
UNSPSC
UNSPSC 6.01
30211915
UNSPSC 7.0901
39121514
UNSPSC 11
39121514
UNSPSC 12.01
39121514
UNSPSC 13.2
39121514
Approvals
Approvals
Approvals
UL Listed / cUL Listed / IECEE CB Scheme / UL Listed / cUL Listed / EAC / EAC / cULus Listed
Ex Approvals
Approvals submitted
Approval details
UL Listed
cUL Listed
IECEE CB Scheme
03/14/2016 Page 5 / 8
https://www.phoenixcontact.com/us/products/2900543
Hybrid motor starter - ELR H3-I-SC- 24DC/500AC-2 - 2900543
Approvals
UL Listed
cUL Listed
EAC
EAC
cULus Listed
Drawings
Load current [A]
Diagram
Block diagram
MAN
RES
AUTO
9
8
7
6
5
4
3
2
1
0,18
RES
1/L1 3/L2 5/L3
Logic
µP
Us
T
0
50
60
70
Ambient temperature [°C]
= aligned with > 20 mm spacing
= aligned without spacing
10
20
30
40
ON
& Error
97 96 95
2/T1 4/T2 6/T3
Derating diagram
03/14/2016 Page 6 / 8
https://www.phoenixcontact.com/us/products/2900543
Hybrid motor starter - ELR H3-I-SC- 24DC/500AC-2 - 2900543
Circuit diagram
L1
L2
L3
Circuit diagram
+24V DC
F1
F2
F3
F5
F4
T1
K1
F4
M
3~
M1
K1
GND
PE
Conventional structure
Main current path reversing contactor
K1 = Right contactor
F4 = Motor protection relay
Conventional structure
Control current path contactor
K1 = Right contactor
T1 = Right
F4 = Motor protection relay
Circuit diagram
F1
L1 F2
L2 F3
L3
+24V DC
L1 L2 L3
K1
T1
T1 T2 T3
M
3~
M1
K1 +US
ON
PE
GND
Structure with CONTACTRON
,
,
Main and control current path for 2 in 1 hybrid motor starter
,
,
K1 = 2 in 1 hybrid motor starter
03/14/2016 Page 7 / 8
https://www.phoenixcontact.com/us/products/2900543
Hybrid motor starter - ELR H3-I-SC- 24DC/500AC-2 - 2900543
T1 = Right
Phoenix Contact 2016 © - all rights reserved
http://www.phoenixcontact.com
03/14/2016 Page 8 / 8
很抱歉,暂时无法提供与“2900543”相匹配的价格&库存,您可以联系我们找货
免费人工找货- 国内价格 香港价格
- 1+1698.190501+211.32196