Hybrid motor starter for starting 3~ AC motors up to 500 V AC and 9 A output current, with 24 V DC control
voltage, adjustable overload shutdown and emergency stop function to SIL3 /PL e, and screw connection.
Why buy this product
22.5 mm wide
Reduction in wiring
Long service life
Space saving
3-phase loop bridges
Adjustable current for bimetal function
Low-wear switching
Key Commercial Data
Packing unit
1 STK
GTIN
GTIN
4046356526159
Weight per Piece (excluding packing)
217.180 g
Custom tariff number
85371098
Country of origin
Germany
Technical data
Device supply
Rated control circuit supply voltage US
24 V DC
Control supply voltage range
19.2 V DC ... 30 V DC
Rated control supply current IS
40 mA
Type of protection
Surge protection
Reverse polarity protection
Input data
04/16/2018 Page 1 / 13
https://www.phoenixcontact.com/gb/products/2900569
Hybrid motor starter - ELR H3-IES-SC- 24DC/500AC-9 - 2900569
Technical data
Input data
Input name
Control input
Rated actuating voltage UC
24 V DC
Triggering voltage range
19.2 V DC ... 30 V DC
Rated actuating current IC
5 mA (Input type 1)
Switching threshold
9.6 V (“0” signal)
19.2 V (“1” signal)
Switching level
< 5 V DC (For EMERGENCY STOP)
Typical turn-off time
< 30 ms
Type of protection
Reverse polarity protection
Output data load output
Output name
AC output
Rated operating voltage Ue
500 V AC
Operating voltage range
42 V AC ... 550 V AC
Rated operating current Ie
9 A (AC-51)
6.5 A (AC-53a)
Mains frequency
50/60 Hz
Load current range
1.5 A ... 9 A (see to derating)
Trigger characteristic in acc. with IEC 60947-4-2
Class 10A
Cooling time
20 min. (for auto reset)
Leakage current
0 mA
Type of protection
Surge protection
Output data reply output
Output name
Acknowledge output
Note
Confirmation: floating change-over contact, signal contact
Contact type
1 PDT
Switching capacity according to IEC 60947-5-1
3 A (230 V, AC15)
2 A (24 V, DC13)
Overspeed tripping
Operate threshold
> 45 A
Response time