https://www.phoenixcontact.com/us/products/2900570
Hybrid motor starter - ELR H3-IES-SC-230AC/500AC-9 - 2900570
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Hybrid motor starter for starting 3~ AC motors up to 550 V AC, with 230 V AC input, 9 A output current,
emergency stop function, and adjustable overload shutdown.
Illustration shows the 24 V design
Product Features
■
■
■
■
■
■
■
22.5 mm wide
Safety level according to IEC 61508-1: SIL 3, ISO 13849: PL e
Long service life
Reduction in wiring
Space saving
3-phase loop bridges
Bimetal function can be set up to 9 A
Key Commercial Data
Packing unit
1 pc
Weight per Piece (excluding packing)
260.0 g
Custom tariff number
85371099
Country of origin
Germany
Technical data
Dimensions
Width
22.5 mm
Height
99 mm
Depth
114.5 mm
Ambient conditions
Ambient temperature (operation)
-25 °C ... 70 °C (observe derating)
Ambient temperature (storage/transport)
-40 °C ... 80 °C
04/05/2016 Page 1 / 8
https://www.phoenixcontact.com/us/products/2900570
Hybrid motor starter - ELR H3-IES-SC-230AC/500AC-9 - 2900570
Technical data
Ambient conditions
Degree of protection
IP20
Device supply
Rated control circuit supply voltage US
230 V AC (50/60 Hz)
Control supply voltage range
85 V AC ... 253 V AC
Rated control supply current IS
4 mA
Protective circuit
Surge protection
Input data
Input name
Control input right/left
Rated actuating voltage UC
230 V AC
Voltage range
85 V AC ... 253 V AC
Rated actuating current IC
7 mA
Switching threshold
44 V AC (“0” signal)
85 V AC (“1” signal)
Switching level
< 5 V AC (For EMERGENCY STOP)
Typical turn-off time
< 70 ms
Output data load output
Output name
AC output
Rated operating voltage Ue
500 V AC
Operating voltage range
42 V AC ... 550 V AC
Mains frequency
50 Hz
60 Hz
Load current range
1.5 A ... 9 A (see to derating)
Trigger characteristic in acc. with IEC 60947
Class 10A
Cooling time
20 min. (for auto reset)
Rated operating current at AC-51
9A
Rated operating current at AC-53a
6.5 A
Leakage current
0 mA
Protective circuit
Surge protection
Output data reply output
Output name
Acknowledge output
Note
Confirmation: floating change-over contact, signal contact
Contact type
1 PDT
Switching capacity according to IEC 60947-5-1
3 A (230 V, AC15)
2 A (24 V, DC13)
Overspeed tripping
04/05/2016 Page 2 / 8
https://www.phoenixcontact.com/us/products/2900570
Hybrid motor starter - ELR H3-IES-SC-230AC/500AC-9 - 2900570
Technical data
Overspeed tripping
Operate threshold
> 45 A
Response time