EMD-SL-LL-110
Electronic monitoring relay for level monitoring of
conductive liquids
INTERFACE
Data sheet
104375_en_00
1
© PHOENIX CONTACT 2010-07-13
Description
Increasingly higher demands are being placed on safety and
system availability – across all sectors. Processes are
becoming more and more complex, not only in mechanical
engineering and the chemical industry, but also in plant and
automation technology. Demands on power engineering are
also increasing constantly.
Features
–
–
–
–
–
–
Error-free and therefore cost-effective operation can only be
achieved through continuous monitoring of important network –
and system parameters. Electronic monitoring relays in the
EMD series are available for a wide range of monitoring tasks
to avoid the consequences of errors or to keep them within
limits.
Filling level monitoring
Pump up (minimum monitoring)
Pump down (maximum monitoring)
Adjustable switch-on delay
Adjustable release delay
Supply voltage 110 V AC
Two PDTs
The operating states are indicated using colored LEDs, errors
that may occur can be sent to a control system via a floating
contact or can shut down a part of the system. Some device
versions are equipped with startup and response delays in
order to briefly tolerate measured values outside the set
monitoring range.
WARNING: Risk of electric shock
Never carry out work when voltage is present.
Make sure you always use the latest documentation.
It can be downloaded at www.phoenixcontact.net/catalog.
EMD-SL-LL-110
2
Ordering data
Description
Type
Order No.
Pcs. / Pkt.
Electronic monitoring relay for level monitoring of conductive liquids
EMD-SL-LL-110
2901137
1
3
Technical data
Input data
Input name
Measuring input
Description of the input
Conductive probe, type: SK1, SK2, SK3
Function
Pumping up (minimum monitoring), pumping down (maximum monitoring)
Recovery time
500 ms
Max. probe voltage
16 V AC
Max. probe current
7 mA
Length of probe cable
< 1000 m Set value < 50% (Capacity 100 nF/km)
< 100 m Set value 100% (Capacity 100 nF/km)
Switching Threshold
0.25 kΩ ... 100 kΩ (4 mS ... 1 μS)
Output data
Contact type
2 floating PDT contacts
Only apply the supply voltage for PDT 2.
Nominal insulation voltage
250 V AC (in acc. with IEC 60664-1)
Interrupting rating (ohmic load) max.
750 VA (3 A/250 V AC, module aligned, ≤ 5 mm spacing)
1250 VA (5 A/250 V AC, module not aligned, ≥ 5 mm spacing)
Output fuse
5 A (fast-blow)
Supply
Supply voltage
110 V AC -10 % ... +15% AC
Frequency range
48 Hz ... 63 kHz
Nominal power consumption
2 VA (1.5 W)
General data
Mains type
1-phase
Service life mechanical
Approx. 2 x 107 cycles
Service life, electrical
2 x 105 cycles at ohmic load, 1000 VA
Switching frequency
max. 60 (per minute at 100 VA ohmic load)
max. 6 (per minute at 1000 VA ohmic load)
Operating mode
100% operating factor
Degree of protection
IP40 (housing) / IP20 (connection terminal blocks)
Pollution degree
2 (according to EN 50178)
Surge voltage category
III, basic insulation (as per EN 50178)
Rated insulation voltage
300 V (According to EN 50178)
Assembly
on TS 35 profile rail acc. to EN 60715
Mounting position
Any
Width
22.5 mm
Height
113 mm
Length
90 mm
104375_en_00
PHOENIX CONTACT
2
EMD-SL-LL-110
General data
Type of housing
Polyamide PA, self-extinguishing
Color
green
Weight
160 g
Connection data
Conductor cross section, solid
0.5 mm² ... 2.5 mm²
Conductor cross section, stranded
0.25 mm² ... 2.5 mm²
Stripping length
8 mm
Type of connection
Screw connection
Tightening torque
1 Nm
Ambient conditions
Ambient temperature (operation)
-25 °C ... 55 °C
-25 °C ... 40 °C (corresponds to UL 508)
Ambient temperature (storage/transport)
-25 °C ... 70 °C
Permissible humidity (operation)
15 % ... 85 %
Climatic class
3K3 (in acc. with EN 60721)
Conformance / approvals
Conformity
CE compliant
UL, USA / Canada
UL/C-UL listed UL 508
Conformance with EMC directive 2004/108/EC
Immunity to interference according to
EN 61000-6-2
Emitted interference according to
EN 61000-6-3
Conformance with LV directive 2006/95/EC
Electronic equipm. for electrical power installations according to
4
EN 50178
Block diagram
16 18 26 28
E1
E2
E3
15
25
A1 A2
U = 110 V AC
5
Safety notes
WARNING: Risk of electric shock
Never carry out work when voltage is present.
104375_en_00
PHOENIX CONTACT
3
EMD-SL-LL-110
6
Structure
1
2
3
4
5
6
7
A1
E1
15
E2
25
E3
U
1
"U" LED: Supply voltage
"REL" LED: Output relay
"FUNCTION" rotary switch: Function selection
"SENSITIVITY" potentiometer: Sensitivity control
"DELAY OFF" potentiometer: Release delay
"DELAY ON" potentiometer: Switch-on delay
Universal snap-on foot for EN DIN rails
Level monitor
0,5
De 1
onlay 0s
0,5
De
10
offlay s
ns
10
itiv
REL
y
2
7
5
Se
0k
Ω
up
do
wn
PU
MP
26
16
18 28
A2
EMD-SL-LL-110
0,2
4
5
6
3
7
Installation
WARNING: Risk of electric shock
Never carry out work when voltage is present.
The module can be snapped onto all 35 mm DIN rails according to EN 60715.
8
Diagnostics
The LEDs indicate the following error states:
"U" LED (Green)
–
LED ON: Supply voltage present
"REL" LED (Yellow)
–
–
LED ON: Output relay has picked up
LED OFF: Output relay has dropped out
104375_en_00
PHOENIX CONTACT
4
EMD-SL-LL-110
9
Connection example
L1
N
A1
E1
15
E2
15
25
E3
E1
25
E2
16 18
16
10
26 28
26
28
18
A2
E3
Function
The "FUNCTION" rotary switch is used to set the desired
function:
– PUMP UP = Pump up or minimum monitoring
– PUMP DOWN = Pump down or maximum monitoring
Setting the Monitoring Relay Prior to Startup
EMD-SL-LL-110
–
–
–
–
–
104375_en_00
Set the time delays ("DELAY ON" and "DELAY OFF"
potentiometers) to 0.5 s, minimum.
Set the rotary switch to the "PUMP DOWN" function.
With probes submersed slowly turn the "SENSITIVITY"
potentiometer clockwise from 0.25 kΩ towards 100 kΩ
until the relay switches.
Remove the probes from the liquid and check whether
output relay "R" drops out. If the relay does not drop out
when the probes are removed, slowly turn the
"SENSITIVITY" potentiometer back counter-clockwise.
Set the desired function ("PUMP UP" or "PUMP DOWN")
and set the time delays to the desired values.
PHOENIX CONTACT
5
EMD-SL-LL-110
Pump Up (PUMP UP)
U
LED REL,R
E1
E2
E3
DELAY
ON
DELAY
OFF
很抱歉,暂时无法提供与“2901137”相匹配的价格&库存,您可以联系我们找货