PSR-...-42-48UC/ESAM4/3X1/1X2/B
Safety relay for emergency stop and safety door
monitoring
Data sheet
105315_en_02
1
© PHOENIX CONTACT 2014-06-13
Description
The safety relay can be used in safety circuits according to
EN 60240-1 and IEC 61508.
With this switching device, circuits are interrupted in a
safety-oriented manner.
Control is via a single channel or two channels, either with
automatic or manual start circuit.
Depending on the external wiring, up to category 4, PL e according to EN ISO 13849-1 or SILCL 3 according to
EN 62061 can be achieved.
Features
–
–
–
–
–
–
Emergency stop and safety door monitoring
Suitable up to category 4, PL e (EN ISO 13849-1),
SILCL 3 (EN 62061)
Optional plug-in screw or spring-cage terminal blocks
Single-channel or two-channel wiring with cross-circuit
detection
3 enable current paths
1 signaling current path
The safety relay is equipped with three enabling current
paths that drop out without delay corresponding to stop category 0 according to EN 60204-1.
WARNING: Risk of electric shock
Observe the safety instructions in the corresponding section!
Make sure you always use the latest documentation.
It can be downloaded from the product at phoenixcontact.net/products.
This data sheet is valid for all products listed on the following pages.
PSR-...-42-48UC/ESAM4/3X1/1X2/B
2
Table of contents
1
Description .............................................................................................................................. 1
2
Table of contents ..................................................................................................................... 2
3
Ordering data .......................................................................................................................... 3
4
Technical data ......................................................................................................................... 3
5
Basic circuit diagram ............................................................................................................... 5
6
Derating................................................................................................................................... 5
7
Safety notes............................................................................................................................. 6
8
Operating and indication elements .......................................................................................... 7
9
Diagnostics.............................................................................................................................. 7
10
Application examples .............................................................................................................. 8
10.1 Two-channel emergency stop circuit with cross-circuit detection ..................................................... 8
10.2 Single-channel emergency stop circuit ...................................................................................... 8
105315_en_02
PHOENIX CONTACT
2
PSR-...-42-48UC/ESAM4/3X1/1X2/B
3
Ordering data
Description
Order No.
Pcs. / Pkt.
Safety relay for emergency stop and safety door monitoring up to SIL 3 or PSR-SCP-42-48UC/ESAM4/3X1/
Cat. 4, PL e according to EN ISO 13849, single or two-channel operation, 1X2B
3 enabling current paths, nominal input voltage of 42 ... 48 V AC/DC, plugin screw terminal blocks.
2901416
1
Safety relay for emergency stop and safety door monitoring up to SIL 3 or PSR-SPP-42-48UC/ESAM4/3X1/
Cat. 4, PL e according to EN ISO 13849, single or two-channel operation, 1X2B
3 enabling current paths, nominal input voltage of 42 ... 48 V AC/DC, plugin spring-cage terminal blocks.
2901417
1
Documentation
Type
Order No.
Pcs. / Pkt.
User manual, English, for applications for PSR safety relay
UM EN SAFETY RELAY APPLICATION
2888712
1
4
Type
Technical data
Input data
Input voltage range
42 V AC/DC ... 48 V AC/DC
Input voltage range (factor)
0.85 ... 1.1
Typical input current
95 mA
Voltage at input/start and feedback circuit
~ 24 V DC
Max. permissible overall conductor resistance
(Input and reset circuit at UN)
50 Ω
Typical response time
40 ms (man. start)
Typical release time
90 ms (when controlled via A1)
Recovery time
1s
Operating voltage display
Green LED
Status display
Green LED
Protective circuit
Surge protection Suppressor diode
Output data
Contact type
3 enabling current paths
1 signaling current path
Contact material
AgSnO2, + 0.2 µm Au
Minimum switching voltage
10 V AC/DC
Maximum switching voltage
250 V AC/DC
Limiting continuous current
6 A (N/O contact)
Maximum inrush current
6A
Inrush current, minimum
10 mA
Sq. Total current
72 A2 (ITH2 = I12 + I22 + I32)
(see derating curve)
Interrupting rating (ohmic load) max.
144 W (24 V DC, τ = 0 ms)
230 W (48 V DC, τ = 0 ms)
68 W (110 V DC, τ = 0 ms)
88 W (220 V DC, τ = 0 ms)
2000 VA (250 V AC, τ = 0 ms)
Maximum interrupting rating (inductive load)
48 W (24 V DC, τ = 40 ms)
40 W (48 V DC, τ = 40 ms)
35 W (110 V DC, τ = 40 ms)
33 W (220 V DC, τ = 40 ms)
Switching capacity min.
100 mW
Mechanical service life
Approx. 107 cycles
105315_en_02
PHOENIX CONTACT
3
PSR-...-42-48UC/ESAM4/3X1/1X2/B
Output data
Switching capacity (360/h cycles)
6 A (24 V DC)
5 A (230 V AC)
Switching capacity (3600/h cycles)
3 A (24 V (DC13))
3 A (230 V (AC 15))
Output fuse
10 A gL/gG NEOZED (N/O contact)
6 A gL/gG NEOZED (N/C contact)
General data
Relay type
Electromechanically forcibly guided, dust-proof relay.
Nominal operating mode
100% operating factor
Degree of protection
IP20
Min. degree of protection of inst. location
IP54
Mounting position
any
Air and creepage distances between the power circuits
DIN EN 50178/VDE 0160
Rated surge voltage / insulation
4 kV / basic insulation (safe isolation, reinforced insulation, and 6 kV between A1A2/logic/enabling and signaling current paths)
Dimensions
Screw connection
Spring-cage connection
WxHxD
22.5 x 99 x 114.5 mm
22.5 x 112 x 114.5 mm
Connection data
Screw connection
Spring-cage connection
Conductor cross section, solid
0.2 mm² ... 2.5 mm²
0.2 mm² ... 1.5 mm²
Conductor cross section, stranded
0.2 mm² ... 2.5 mm²
0.2 mm² ... 1.5 mm²
Conductor cross section AWG/kcmil
24 ... 12
24 ... 16
Ambient conditions
Ambient temperature (operation)
-25 °C ... 55 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Max. permissible relative humidity (operation)
75 %
Max. permissible humidity (storage/transport)
75 %
Certification / Approvals
Approvals
Safety data
Stop category according to IEC 60204
0
Safety parameters for IEC 61508 - High demand
SIL
3
Demand rate
< 12 Months
Proof test interval
240 Months
Safety parameters for IEC 61508 - Low demand
SIL
3
Proof test interval
78 Months
Duration of use
240 Months
Safety characteristic data according to EN ISO 13849
Category
4
Performance level
e
105315_en_02
PHOENIX CONTACT
4
PSR-...-42-48UC/ESAM4/3X1/1X2/B
Basic circuit diagram
S11 S12
A1
S34
U Logic
13
6
23
33
41
K1
IN 1/2
Logic
K2
Power
AC/DC
I [A2]
5
Derating
100
90
80
72 70
60
50
40
30
20
10
0
0
S21
A2
Figure 1
S22
14
24
34
10
20
42
Block diagram
Figure 2
30
40 45 50 55 60
TA [°C]
Derating curve
Key:
Designation
A1/A2
S11/S12
S21/S22
S34
13/14
23/24
33/34
41/42
105315_en_02
Explanation
Safety relay input voltage
Safety sensor/switch 1 input circuit
Safety sensor/switch 2 input circuit
Start circuit
Undelayed enabling current path 1
Undelayed enabling current path 2
Undelayed enabling current path 3
Signaling current path
PHOENIX CONTACT
5
PSR-...-42-48UC/ESAM4/3X1/1X2/B
7
Safety notes
WARNING: Risk of electric shock
During operation, parts of electrical switching
devices carry hazardous voltages.
Before working on the switching device, disconnect the power.
Please observe the safety regulations of electrical engineering and industrial safety and liability associations!
Disregarding these safety regulations may result in death, serious personal injury or damage to equipment.
Startup, mounting, modifications, and upgrades should only be carried out by a skilled
electrical engineer!
NOTE: Risk of damage to equipment due
to incorrect installation
For reliable operation, the safety relay must
be installed in housing protected from dust
and humidity (IP54).
Carry out wiring according to the application.
Refer to the “Application examples” section
for this.
NOTE: Risk of damage to equipment due
to noise emissions
When operating relay modules the operator
must meet the requirements for noise emission for electrical and electronic equipment
(EN 61000-6-4) on the contact side and, if required, take appropriate measures.
WARNING: Risk of automatic machine restart!
For emergency stop applications, the machine must be prevented from restarting automatically by a higher-level control system.
Protective covers must not be removed when
operating electrical switching devices.
WARNING: Risk of automatic machine restart!
When using the manual reset function with
monitored start, the “cross-circuit between
S21/S22 and the cable from the reset button
to S34” error must be prevented by design-related measures, especially for safety functions with increased risk potential (see
EN ISO 13849-2).
WARNING: Danger due to faulty devices!
The devices may be damaged following an error and correct operation can no longer be ensured.
In the event of an error, replace the device immediately.
Repairs to the device, especially if the housing must be opened, may only be carried out
by the manufacturer or authorized persons.
Otherwise the warranty is invalidated.
105315_en_02
PHOENIX CONTACT
6
PSR-...-42-48UC/ESAM4/3X1/1X2/B
Operating and indication elements
8
S
12
21
S
22
S
48
V
U
C
34
21
22
22
w
S
w
33
IN
2
K
2
K
1
K
2
1/
2
1/
er
er
o
P
o
P
5
S
S
S
48
S
12
34
21
S
S
V
U
C
11
2
S
12
11
A
S
2
S
1
K
P
S
R
-E
S
A
M
4
S
1
6
A
11
IN
5
2
A
1
S
6
7
10 12 11 13
9
8
2
A
7
10 12 11 13
9
P
S
R
-E
S
A
M
4
8
41
41
24
APPROVALS
14
41
33
13
14
INPUT
R
34
23
24
Functional Safety
Type Approved
TÜVRheinland
42
: 24 Vdc
24
4
2
: 24 V ac / dc (24UC)
24 V dc (24DC)
23
13
Max Ambient Rating
40℃
55℃
T0/T1 (per channel) :100mA
100mA
M0...M3 (per channel) :100mA
100mA
O0...O3 (per channel) :0,5A
140mA
O0...O3 (single channel) :2A
0,5A
34
Functional Safety
Type Approved
R
TÜVRheinland
42
OUTPUT
14
APPROVALS
IND.CONT. EQ.
32FB
24
13
23
14
23
33
13
34
13
34
41
2
33
42
33
42
4
13
23
23
33
14
33
14
24
41
24
34
41
34
42
42
1
Figure 3
1
PSR-SCP-42-48UC/ESAM4/3X1/1X2/B and PSR-SPP-42-48UC/ESAM4/3X1/1X2/B
Key:
Designation
1
2
3
4
5
6
7
8
9
10
11
12
13
9
Explanation
Metal lock for mounting on the DIN rail
COMBICON plug-in screw terminal blocks
COMBICON plug-in spring-cage terminal blocks
13/14, 23/24, 33/34 - enabling current paths
41/42 signaling current path
LED status indicator, green - K1
LED status indicator, green - K2
LED status indicator, green - IN 1/2
LED status indicator, green - Power
S11/S12 - input circuit
S21/S22 - input circuit
Power supply
S34 - start circuit
Diagnostics
The diagnostic descriptions can be found in Section 7 of the
application manual for PSR safety relays.
105315_en_02
PHOENIX CONTACT
7
PSR-...-42-48UC/ESAM4/3X1/1X2/B
10.2
10
Application examples
10.1
Two-channel emergency stop circuit with
cross-circuit detection
Manual activation with connection at S12-S34
Suitable up to category 4, PL e (EN ISO 13849-1),
SILCL 3 (EN 62061)
42-48V
60V
120V
230V
AC/DC
Emergency stop
Emergency stop
42-48V
60V
120V
230V
AC/DC
Automatic activation with connection at S22-S34
Suitable up to category 1, PL c (EN ISO 13849-1),
SILCL 1 (EN 62061)
S1
K3
K3
A1
S11 S12 S21 S22
(+)
( )
(GND)
S11 S12 S21 S22
13
23 33
41
14
24
42
A2
S34
23 33
41
K3
14
24 34
42
K4
K3
S34
A2
K3
Reset
S2
M
K3
PSR-...-...UC/ESAM4/3x1/1x2/B
K4
13
( )
PSR-...-...UC/ESAM4/3x1/1x2/B
K4
A1
S1
( )
–
–
–
–
Single-channel emergency stop circuit
34
K4
K4
M
K4
M
(N)
Figure 5
Emergency stop with automatic start
M
(N)
Figure 4
105315_en_02
Emergency stop with cross-circuit detection
and manually monitored reset
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
phoenixcontact.com
8