Single-channel input loop-powered 2-way isolator with plug-in connection technology for the electrical isolation
of analog signals. Input signal = output signal: 0(4) mA ... 20 mA. Push-in connection technology.
Product Description
Single-channel input-loop-powered 2-way isolator with plug-in connection technology for the electrical isolation and filtering of analog signals. The
input-loop-powered isolator allows operation with active sensor technology with a supply voltage of 9.6 V DC ... 30 V DC. The device is powered via
the current loop of the sensor. Input signal = output signal: 0(4) mA ... 20 mA. The measuring transducer supports NFC communication.
Key Commercial Data
Packing unit
1 STK
GTIN
GTIN
4046356649261
Weight per Piece (excluding packing)
52.200 g
Custom tariff number
85437090
Country of origin
Germany
Technical data
Dimensions
Width
6.2 mm
Height
110.5 mm
Depth
120.5 mm
Ambient conditions
Ambient temperature (operation)
-40 °C ... 70 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Maximum altitude
< 2000 m
Input data
Description of the input
Current input
04/16/2018 Page 1 / 9
https://www.phoenixcontact.com/gb/products/2901995
Loop-powered isolators - MINI MCR-2-I-I-ILP-PT - 2901995
Technical data
Input data
Number of inputs
1
Configurable/programmable
no
Current input signal
0 mA ... 20 mA
4 mA ... 20 mA
Response current
approx. 200 µA
Input voltage limitation
30 V
Voltage dissipation
3.1 V (I = 20 mA)
Output data
Output name
Current output
Number of outputs
1
Configurable/programmable
no
Current output signal
0 mA ... 20 mA
4 mA ... 20 mA
Load/output load current output
< 600 Ω (at I = 20 mA output signal)
Transmission Behavior
1:1 to input signal
Power supply
Supply voltage range
9.6 V DC ... 30 V DC (no separate supply voltage necessary)
Power consumption
600 mW
Connection data
Connection method
Push-in connection
Single conductor/terminal point, solid, with ferrule, min.
0.14 mm²
Single conductor/terminal point, solid, with ferrule, max.
2.5 mm²
Single conductor/terminal point, solid, without ferrule, min.
0.14 mm²
Single conductor/terminal point, solid, without ferrule, max.
2.5 mm²
Conductor cross section flexible min.
0.14 mm²
Conductor cross section flexible max.
2.5 mm²
Min. AWG conductor cross section, flexible
24
Max. AWG conductor cross section, flexible
12
Stripping length
10 mm
General
No. of channels
1
Maximum transmission error
≤ 0.1 % (of final value)
Maximum temperature coefficient
≤ 0.002 %/K (of measured value / 100 Ω load)
Additional error, load-dependent
< 0.075 % (of measured value / 100 Ω load)
Limit frequency (3 dB)
100 Hz
Electrical isolation
Reinforced insulation in accordance with IEC 61010-1
Overvoltage category
II
Degree of pollution
2
Rated insulation voltage
300 V (effective)
04/16/2018 Page 2 / 9
https://www.phoenixcontact.com/gb/products/2901995
Loop-powered isolators - MINI MCR-2-I-I-ILP-PT - 2901995
Technical data
General
Test voltage, input/output/supply
3 kV (50 Hz, 1 min.)
Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be
minimal deviations.
Color
gray
Housing material
PBT
Mounting position
any
Conformance
CE-compliant
ATEX
II 3 G Ex nA IIC T4 Gc X
UL, USA/Canada
UL 508 Listed
Class I, Div. 2, Groups A, B, C, D T6
Class I, Zone 2, Group IIC T6
GL
GL applied for
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 2
Standards and Regulations
Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Electrical isolation
Reinforced insulation in accordance with IEC 61010-1
Conformance
CE-compliant
ATEX
II 3 G Ex nA IIC T4 Gc X
UL, USA/Canada
UL 508 Listed
Class I, Div. 2, Groups A, B, C, D T6
Class I, Zone 2, Group IIC T6
GL
GL applied for
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 2 HL 1 - HL 2 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 2 HL 1 - HL 2 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 2 HL 1 - HL 2 HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R26
HL 1 - HL 2 HL 1 - HL 2 HL 1 - HL 2
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”,
Category “Manufacturer's declaration”
Drawings
04/16/2018 Page 3 / 9
https://www.phoenixcontact.com/gb/products/2901995
Loop-powered isolators - MINI MCR-2-I-I-ILP-PT - 2901995
Application drawing
UV = 3,1 V
I
US
4-wire
Pictogram
UE
I
RB
I
US = ! 30 V DC
MINI MCR-2-I-I-ILP
Us " UE = 3,1 V + 20 mA x RB
IN
POWER
I
I
OUT
Block diagram
Sensor / Field
OUT
IN
TI–
+ 1
OUT I+
US
4-wire
1
PWR
max
30VDC
2
OUT I-
IN I+
TI+
5 +
OUT I+
active
– 2
5
passive
6 –
IN I–
3
PLC / DCS
6
OUT I–
7
8
4
Zone 2
Classifications
eCl@ss
eCl@ss 4.0
27210120
eCl@ss 4.1
27210120
eCl@ss 5.0
27210120
eCl@ss 5.1
27210120
eCl@ss 6.0
27210120
eCl@ss 7.0
27210120
eCl@ss 8.0
27210120
eCl@ss 9.0
27210120
ETIM
ETIM 4.0
EC002653
ETIM 5.0
EC002653
ETIM 6.0
EC002653
04/16/2018 Page 4 / 9
https://www.phoenixcontact.com/gb/products/2901995
Loop-powered isolators - MINI MCR-2-I-I-ILP-PT - 2901995
Classifications
UNSPSC
UNSPSC 6.01
30211506
UNSPSC 7.0901
39121008
UNSPSC 11
39121008
UNSPSC 12.01
39121008
UNSPSC 13.2
39121008
Approvals
Approvals
Approvals
UL Listed / cUL Listed / cULus Listed
Ex Approvals
UL Listed / cUL Listed / ATEX / cULus Listed
Approval details
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 238705
cUL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm
FILE E 238705
cULus Listed
Accessories
Accessories
Communication module
Communication module - MINI MCR-2-V8-MOD-RTU - 2905634
Eight MINI Analog Pro signal conditioners and measuring transducers can be quickly and easily integrated into a
Modbus/RTU network via a communication adapter.
04/16/2018 Page 5 / 9
https://www.phoenixcontact.com/gb/products/2901995
Loop-powered isolators - MINI MCR-2-I-I-ILP-PT - 2901995
Accessories
Communication module - MINI MCR-2-V8-MOD-TCP - 2905635
Eight MINI Analog Pro signal conditioners and measuring transducers can be quickly and easily integrated into a
Modbus/TCP network via a communication adapter.
Communication module - MINI MCR-2-V8-PB-DP - 2905636
Eight MINI Analog Pro signal conditioners and measuring transducers can be quickly and easily integrated into a
PROFIBUS DP network via a communication adapter.
Device marking
Marker for end clamp - UCT-EM (30X5) - 0801505
Marker for end clamp, Sheet, white, unlabeled, can be labeled with: THERMOMARK PRIME, THERMOMARK CARD,
BLUEMARK CLED, BLUEMARK LED, TOPMARK LASER, mounting type: snapped into marker carrier, lettering field
size: 30 x 5 mm
Marker for end clamp - UCT-EM (30X5) YE - 0830340
Marker for end clamp, Sheet, yellow, unlabeled, can be labeled with: THERMOMARK PRIME, THERMOMARK
CARD, BLUEMARK CLED, BLUEMARK LED, TOPMARK LASER, mounting type: snapped into marker carrier,
lettering field size: 30 x 5 mm
Plastic label - UC-EMLP (15X5) - 0819301
Plastic label, Sheet, white, unlabeled, can be labeled with: BLUEMARK CLED, BLUEMARK LED, CMS-P1PLOTTER, PLOTMARK, mounting type: adhesive, lettering field size: 15 x 5 mm
04/16/2018 Page 6 / 9
https://www.phoenixcontact.com/gb/products/2901995
Loop-powered isolators - MINI MCR-2-I-I-ILP-PT - 2901995
Accessories
Plastic label - UC-EMLP (15X5) YE - 0822615
Plastic label, Sheet, yellow, unlabeled, can be labeled with: BLUEMARK CLED, BLUEMARK LED, CMS-P1PLOTTER, PLOTMARK, mounting type: adhesive, lettering field size: 15 x 5 mm
Plastic label - UC-EMLP (15X5) SR - 0828095
Plastic label, Sheet, silver, unlabeled, can be labeled with: BLUEMARK CLED, BLUEMARK LED, CMS-P1PLOTTER, PLOTMARK, mounting type: adhesive, lettering field size: 15 x 5 mm
Plastic label - US-EMLP (15X5) - 0828790
Plastic label, Card, white, unlabeled, can be labeled with: THERMOMARK PRIME, THERMOMARK CARD, mounting
type: adhesive, lettering field size: 15 x 5 mm
Plastic label - US-EMLP (15X5) YE - 0828873
Plastic label, Card, yellow, unlabeled, can be labeled with: THERMOMARK PRIME, THERMOMARK CARD,
mounting type: adhesive, lettering field size: 15 x 5 mm
Plastic label - US-EMLP (15X5) SR - 0828874
Plastic label, Card, silver, unlabeled, can be labeled with: THERMOMARK PRIME, THERMOMARK CARD, mounting
type: adhesive, lettering field size: 15 x 5 mm
Labeled device marker
04/16/2018 Page 7 / 9
https://www.phoenixcontact.com/gb/products/2901995
Loop-powered isolators - MINI MCR-2-I-I-ILP-PT - 2901995
Accessories
Marker for end clamp - UCT-EM (30X5) CUS - 0801589
Marker for end clamp, can be ordered: by sheet, white, labeled according to customer specifications, mounting type:
snapped into marker carrier, lettering field size: 30 x 5 mm
Marker for end clamp - UCT-EM (30X5) YE CUS - 0830348
Marker for end clamp, can be ordered: by sheet, yellow, labeled according to customer specifications, mounting type:
snapped into marker carrier, lettering field size: 30 x 5 mm
Plastic label - UC-EMLP (15X5) CUS - 0824550
Plastic label, can be ordered: by sheet, white, labeled according to customer specifications, mounting type: adhesive,
lettering field size: 15 x 5 mm
Plastic label - UC-EMLP (15X5) YE CUS - 0824551
Plastic label, can be ordered: by sheet, yellow, labeled according to customer specifications, mounting type:
adhesive, lettering field size: 15 x 5 mm
Plastic label - UC-EMLP (15X5) SR CUS - 0828099
Plastic label, can be ordered: by sheet, silver, labeled according to customer specifications, mounting type: adhesive,
lettering field size: 15 x 5 mm
04/16/2018 Page 8 / 9
https://www.phoenixcontact.com/gb/products/2901995
Loop-powered isolators - MINI MCR-2-I-I-ILP-PT - 2901995
Accessories
Plastic label - US-EMLP (15X5) CUS - 0830076
Plastic label, can be ordered: By card, white, labeled according to customer specifications, mounting type: adhesive,
lettering field size: 15 x 5 mm
Plastic label - US-EMLP (15X5) YE CUS - 0830077
Plastic label, can be ordered: By card, yellow, labeled according to customer specifications, mounting type: adhesive,
lettering field size: 15 x 5 mm
Plastic label - US-EMLP (15X5) SR CUS - 0830078
Plastic label, can be ordered: By card, silver, labeled according to customer specifications, mounting type: adhesive,
lettering field size: 15 x 5 mm
System adapter
System adapter - MINI MCR-2-V8-FLK 16 - 2901993
Eight MINI Analog Pro signal conditioners and measuring transducers can be connected to a controller with minimal
cabling effort and without any errors using system adapters and system cabling.
Terminal marking
Marker strip - SK 5,0 WH:REEL - 0805221
Marker strip, Roll, white, unlabeled, can be labeled with: THERMOMARK ROLL, THERMOMARK ROLL X1,
THERMOMARK ROLLMASTER 300/600, THERMOMARK X1.2, THERMOMARK S1.1, mounting type: adhesive, for
terminal block width: 5 mm, lettering field size: continuous x 5 mm
Phoenix Contact 2018 © - all rights reserved
http://www.phoenixcontact.com
04/16/2018 Page 9 / 9