3-way signal conditioner with plug-in connection technology for the electrical isolation of analog signals. Input
signal: 4 ... 20 mA, output signal: 0 ... 10 V, screw connection technology
The figure shows the MINI MCR-2-UI0-PT version
Product description
Standard signal 3-way signal conditioner with plug-in connection technology for the electrical isolation, conversion, amplification, and filtering of standard
signals. The measuring transducer supports fault monitoring and NFC communication.
Key commercial data
Packing unit
1 pc
Weight per Piece (excluding packing)
103.4 GRM
Custom tariff number
85437090
Country of origin
Germany
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
6.2 mm
Height
110.5 mm
Depth
120.5 mm
Ambient conditions
Ambient temperature (operation)
-40 °C ... 70 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
07/07/2015 Page 1 / 6
https://www.phoenixcontact.com/us/products/2902002
Signal conditioner - MINI MCR-2-I4-U - 2902002
Technical data
Ambient conditions
Degree of protection
IP20
Input data
Number of inputs
1
Configurable/programmable
no
Current input signal
4 mA ... 20 mA
Input resistance current input
approx. 63 Ω
Output data
Number of inputs
1
Configurable/programmable
no
Voltage output signal
0 V ... 10 V
Max. output voltage
11 V
Short-circuit current
< 15 mA
Load/output load voltage output
≥ 10 kΩ
Power supply
Nominal supply voltage
24 V DC
Supply voltage range
9.6 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5ST-3,81 GN, Order No. 2869728) can be used to bridge the supply
voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
Typical current consumption
25 mA (24 V DC)
54 mA (12 V DC)
Power consumption
≤ 200 mW (at 9.6 V DC)
Connection data
Connection method
Screw connection
Single conductor/terminal point, solid, with ferrule, min.
0.2 mm²
Single conductor/terminal point, solid, with ferrule, max.
1.5 mm²
Single conductor/terminal point, solid, without ferrule, min.
0.2 mm²
Single conductor/terminal point, solid, without ferrule, max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
1.5 mm²
Min. AWG conductor cross section, flexible
24
Max. AWG conductor cross section, flexible
12
Stripping length
10 mm
Screw thread
M3
General
Maximum transmission error
0.1 % (of final value)
Maximum temperature coefficient
0.01 %/K
07/07/2015 Page 2 / 6
https://www.phoenixcontact.com/us/products/2902002
Signal conditioner - MINI MCR-2-I4-U - 2902002
Technical data
General
Limit frequency (3 dB)
approx. 30 Hz
Step response (10-90%)
approx. 10 ms
Protective circuit
Transient protection
Electrical isolation
Reinforced insulation in accordance with IEC 61010-1
Surge voltage category
II
Pollution degree
2
Rated insulation voltage
300 V
Test voltage, input/output/supply
3 kV (50 Hz, 1 min.)
Electromagnetic compatibility
Conformance with EMC Directive 2004/108/EC
Noise emission
EN 61000-6-4
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be minimal
deviations.
Color
gray
Housing material
PBT
Mounting position
any
Assembly instructions
The T connector can be used to bridge the supply voltage. It can be
snapped onto a 35 mm DIN rail according to EN 60715.
Conformance
CE-compliant
ATEX
II 3 G Ex nA IIC T4 Gc X
UL, USA / Canada
UL 508 Listed
Class I, Div. 2, Groups A, B, C, D T6
Class I, Zone 2, Group IIC T6
EMC data
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Designation
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Classifications
eCl@ss
eCl@ss 4.0
27040702
eCl@ss 4.1
27040702
eCl@ss 5.0
27242213
eCl@ss 5.1
27049002
07/07/2015 Page 3 / 6
https://www.phoenixcontact.com/us/products/2902002
Signal conditioner - MINI MCR-2-I4-U - 2902002
Classifications
eCl@ss
eCl@ss 6.0
27049002
eCl@ss 7.0
27049002
eCl@ss 8.0
27210120
ETIM
ETIM 3.0
EC001039
ETIM 4.0
EC002540
ETIM 5.0
EC002653
UNSPSC
UNSPSC 6.01
30211502
UNSPSC 7.0901
39121004
UNSPSC 11
39121004
UNSPSC 12.01
39121004
UNSPSC 13.2
39121004
Approvals
Approvals
Approvals
UL Listed / cUL Listed / EAC / GL / cULus Listed
Ex Approvals
ATEX / UL Listed / cUL Listed / cULus Listed
Approvals submitted
Approval details
UL Listed
07/07/2015 Page 4 / 6
https://www.phoenixcontact.com/us/products/2902002
Signal conditioner - MINI MCR-2-I4-U - 2902002
Approvals
cUL Listed
EAC
GL
cULus Listed
Drawings
Pictogram
Block diagram
Sensor / Field
OUT
IN
TI–
+ 1
OUT
1
I+
US
PLC / DCS
5 +
OUT U+
IN I+
5
4-wire
OUT
2
I-
– 2
+ 3
– 4
OUT U–
IN I–
PWR+
PWR+
PWR–
6 –
6
7 +
PWR–
8 –
PWR–
PWR+
FM
Zone 2
Pictogram
IN
I
U
FM
POWER
Pictogram
OUT
IN
U
I
OUT
FM
POWER
07/07/2015 Page 5 / 6
https://www.phoenixcontact.com/us/products/2902002
Phoenix Contact 2015 © - all rights reserved
http://www.phoenixcontact.com
07/07/2015 Page 6 / 6