https://www.phoenixcontact.com/us/products/2902033
Limit value switches - MINI MCR-2-UI-REL - 2902033
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Universally configurable limit value switch with PDT relay output and plug-in connection technology for switching
analog limit values. Configurable via DIP switch or software, screw connection technology.
The figure shows the MINI MCR-2UI-REL-PT version
Product Description
Universally configurable limit value switch with PDT relay output and plug-in connection technology for switching analog limit values. Current signals
between 0 mA ... 24 mA and voltage signals between 0 V ... 12 V can be processed on the input side. A relay with PDT contact is available on the output
side. It is then possible to switch loads up to 250 V AC/DC and max. 6 A. You can configure the device using one of the free software solutions. Default
settings can also be made directly on the device by simply using the DIP switches (see configuration table). The measuring transducer supports fault
monitoring and NFC communication.
Key Commercial Data
Packing unit
1 pc
Weight per Piece (excluding packing)
120.0 g
Custom tariff number
85437090
Country of origin
Germany
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width
6.2 mm
Height
110.5 mm
Depth
120.5 mm
Ambient conditions
10/29/2015 Page 1 / 4
https://www.phoenixcontact.com/us/products/2902033
Limit value switches - MINI MCR-2-UI-REL - 2902033
Technical data
Ambient conditions
Ambient temperature (operation)
-40 °C ... 70 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Degree of protection
IP20
Input data
Configurable/programmable
Yes
Voltage input signal
0 V ... 10 V (via DIP switch)
0 V ... 12 V (via DIP switch)
Current input signal
0 mA ... 20 mA (via DIP switch)
0 mA ... 24 mA (Can be set via software)
Max. input voltage
12 V
Max. input current
24 mA
Input resistance of voltage input
> 120 kΩ
Input resistance current input
approx. 50 Ω
Switching output
Output name
Relay output
Contact type
1 PDT
Contact material
AgSnO2, hard gold-plated
Maximum switching voltage
250 V AC
240 V AC (UL)
Limiting continuous current
6A
Min. switching current
100 mA (12 V DC)
Mechanical service life
2 x 10 cycles
Setting range of the response delay
0 s ... 10 s (can be set freely via software)
Internal hysteresis
can be set freely via software
Max. switching current
6 A (for 250 V AC)
7
Power supply
Nominal supply voltage
24 V DC
Supply voltage range
9.6 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5ST-3,81 GN, Order No. 2869728) can be used to bridge the supply
voltage. It can be snapped onto a 35 mm DIN rail according to EN 60715))
Typical current consumption
40 mA (12 V DC)
20 mA (24 V DC)
Power consumption
≤ 0.5 W
Connection data
Connection method
Screw connection
Single conductor/terminal point, solid, with ferrule, min.
0.2 mm²
10/29/2015 Page 2 / 4
https://www.phoenixcontact.com/us/products/2902033
Limit value switches - MINI MCR-2-UI-REL - 2902033
Technical data
Connection data
Single conductor/terminal point, solid, with ferrule, max.
1.5 mm²
Single conductor/terminal point, solid, without ferrule, min.
0.2 mm²
Single conductor/terminal point, solid, without ferrule, max.
2.5 mm²
Conductor cross section flexible min.
0.2 mm²
Conductor cross section flexible max.
1.5 mm²
Min. AWG conductor cross section, flexible
24
Max. AWG conductor cross section, flexible
12
Stripping length
10 mm
Screw thread
M3
General
No. of channels
1
Maximum transmission error
0.1 % (of final value)
Maximum temperature coefficient
0.01 %/K
Switching point accuracy
< 0.1 %
Status display
Yellow LED (switching output)
Electrical isolation
Reinforced insulation in accordance with IEC 61010-1
Overvoltage category
II
Pollution degree
2
Rated insulation voltage
300 V (effective)
Test voltage, input/output/supply
3 kV (50 Hz, 1 min.)
Electromagnetic compatibility
Conformance with EMC Directive 2004/108/EC
Noise emission
EN 61000-6-4
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be minimal
deviations.
Color
gray
Housing material
PBT
Mounting position
any
Assembly instructions
The T connector can be used to bridge the supply voltage. It can be
snapped onto a 35 mm DIN rail according to EN 60715.
Conformance
CE-compliant
ATEX
II 3 G Ex nA nC IIC T4 Gc X
UL, USA / Canada
UL 508 Listed
Class I, Div. 2, Groups A, B, C, D T4A
GL
GL applied for
10/29/2015 Page 3 / 4
https://www.phoenixcontact.com/us/products/2902033
Limit value switches - MINI MCR-2-UI-REL - 2902033
Classifications
eCl@ss
eCl@ss 4.0
27210120
eCl@ss 4.1
27210120
eCl@ss 5.0
27210120
eCl@ss 5.1
27210120
eCl@ss 6.0
27210120
eCl@ss 7.0
27210120
eCl@ss 8.0
27210122
ETIM
ETIM 3.0
EC001485
ETIM 4.0
EC001446
ETIM 5.0
EC002654
UNSPSC
UNSPSC 6.01
30211506
UNSPSC 7.0901
39121008
UNSPSC 11
39121008
UNSPSC 12.01
39121008
UNSPSC 13.2
39121008
Drawings
Block diagram
IN
OUT
PLC / DCS
Pictogram
Sensor / Field
S-Port
14
1
11
2
2
11
3
3
12
4
TI5 +
IN U, I+
1
4
OUT
U,I +
6
OUT
U,I -
4-wire
6 –
IN U, I–
PWR+
5
US
7 +
PWR–
8 –
IN
U,I
OUT
FM
PWR–
PWR+
FM
POWER
II 3 G
Ex nA IIC T4 Gc X
Phoenix Contact 2015 © - all rights reserved