MINI MCR-2-UI-UI(-PT)(-C)
3-way signal conditioner
Data sheet
106006_en_02
1
© PHOENIX CONTACT 2016-02-10
Description
The 3-way signal conditioner with pluggable connection
technology and calibrated measuring range changeover
can be configured using DIP switches and is used for the
electrical isolation, conditioning, amplification, and filtering
of unipolar and bipolar standard and normalized signals.
On the input side, the standard analog signals 0 - 20 mA,
4 - 20 mA, 0 - 10 V, 0 - 5 V, 1 - 5 V, or -10 - 10 V and the
signals 2 - 10 V, 0 - 20 V, 4 - 20 V, 0 - 24 V, 4.8 - 24 V,
6 - 30 V, 0 - 30 V, -5 - 5 V, -20 - 20 V, -24 - 24 V, -30 - 30 V,
and -20 - 20 mA are available.
On the output side, 0 - 20 mA, 4 - 20 mA, 0 - 10 V, 2...10 V,
0 - 5 V, 1 - 5 V, -10 - 10 V, and -5 - 5 V are available.
Features
–
–
–
–
–
–
–
–
Configurable 3-way signal conditioner with plug-in
connection technology
Input and output signal range and cut-off frequencies
configurable via DIP switches
Calibrated measuring range switch-over
Approval for Ex-zone 2 (nA)
Screw or push-in connection available
Can be supplied configured or unconfigured
Reinforced insulation according to IEC 61010-1
Supply voltage range 9.6 ... 30 V DC
There is no need for adjustment following a measuring
range changeover.
WARNING: Correct usage in potentially explosive areas
The module is a category 3 item of electrical equipment. It is absolutely vital to follow the instructions provided
here during installation and observe the information in the "Safety regulations and installation notes".
This device offers the option of NFC communication.
You can use the MINI Analog Pro Smartphone app to call-up DIP switch setting help and comprehensive
module information via the NFC interface of your Smartphone.
The MINI Analog Pro Smartphone app is available to you free.
Make sure you always use the latest documentation.
It can be downloaded from the product at phoenixcontact.net/products.
This document is valid for the products listed in the “Ordering data”.
MINI MCR-2-UI-UI(-PT)(-C)
2
Table of contents
1
Description .............................................................................................................................. 1
2
Table of contents ..................................................................................................................... 2
3
Ordering data .......................................................................................................................... 3
4
Technical data ......................................................................................................................... 5
5
Safety regulations and installation notes.................................................................................. 7
5.1
Installation notes ................................................................................................................. 7
5.2
Installation in Zone 2............................................................................................................. 7
5.3
UL Notes ........................................................................................................................... 7
6
Installation ............................................................................................................................... 8
6.1
Connection notes ................................................................................................................ 8
6.2
Structure ........................................................................................................................... 8
6.3
Block diagram ..................................................................................................................... 8
6.4
Power supply ...................................................................................................................... 8
6.5
Assembly........................................................................................................................... 9
6.6
FASTCON Pro plugs ............................................................................................................ 9
6.7
Fault monitoring FM ............................................................................................................. 9
6.8
Current measurement ......................................................................................................... 10
6.9
Marking ........................................................................................................................... 10
7
Configuration ......................................................................................................................... 11
7.1
Configuration table ............................................................................................................. 12
8
Status indicator...................................................................................................................... 12
106006_en_02
PHOENIX CONTACT 2 / 12
MINI MCR-2-UI-UI(-PT)(-C)
3
Ordering data
Description
Type
Order No.
Pcs./Pkt.
3-way signal conditioner with plug-in connection technology and calibrated
measuring range changeover for the electrical isolation of unipolar and
bipolar analog signals. Input/output configurable via DIP switch. Screw
connection technology, standard configuration.
MINI MCR-2-UI-UI
2902037
1
3-way signal conditioner with plug-in connection technology and calibrated
measuring range changeover, for the electrical isolation of unipolar and
bipolar analog signals. Input/output configurable via DIP switch. push-in
connection technology, standard configuration.
MINI MCR-2-UI-UI-PT
2902040
1
3-way signal conditioner with plug-in connection technology and calibrated
measuring range changeover for the electrical isolation of unipolar and
bipolar analog signals. Input/output configurable via DIP switch. Screw
connection technology, order configuration.
MINI MCR-2-UI-UI-C
2902036
1
3-way signal conditioner with plug-in connection technology and calibrated
measuring range changeover for the electrical isolation of unipolar and
bipolar analog signals. Input/output configurable via DIP switch. push-in
connection technology, order configuration.
MINI MCR-2-UI-UI-PT-C
2902039
1
Accessories
Type
Order No.
Pcs./Pkt.
DIN rail connector for DIN rail mounting. Universal for TBUS housing. Gold- ME 6,2 TBUS-2 1,5/5-ST-3,81 GN
plated contacts, 5-pos. Plug component, Number of positions: 5, Pitch:
3.81 mm
2869728
10
Power terminal with plug-in connection technology for delivering the supply
voltage to the DIN rail connector. Monitoring of the supply voltages in
combination with the fault monitoring module. Screw connection
technology
MINI MCR-2-PTB
2902066
1
Power terminal with plug-in connection technology for delivering the supply
voltage to the DIN rail connector. Monitoring of the supply voltages in
combination with the fault monitoring module. Push-in connection
technology
MINI MCR-2-PTB-PT
2902067
1
Fault monitoring module with plug-in connection technology for evaluating
and reporting group errors from the FM system and for monitoring the
supply voltages. Error reporting via N/O contact. Screw connection
technology, standard configuration
MINI MCR-2-FM-RC
2904504
1
Fault monitoring module with plug-in connection technology for evaluating
and reporting group errors from the FM system and for monitoring the
supply voltages. Error reporting via N/O contact. Push-in connection
technology, standard configuration
MINI MCR-2-FM-RC-PT
2904508
1
Primary-switched MINI POWER supply for DIN rail mounting, input: 1phase, output: 24 V DC/1.5 A
MINI-SYS-PS-100-240AC/24DC/1.5
2866983
1
Marker for end clamp, Sheet, white, unlabeled, can be labeled with:
THERMOMARK CARD, BLUEMARK CLED, BLUEMARK LED,
TOPMARK LASER, Mounting type: snapped into marker carrier, Lettering
field: 30 x 5 mm
UCT-EM (30X5)
0801505
10
Marker for end clamp, can be ordered: by sheet, white, labeled according
to customer specifications, Mounting type: snapped into marker carrier,
Lettering field: 30 x 5 mm
UCT-EM (30X5) CUS
0801589
1
Marker for end clamp, Sheet, yellow, unlabeled, can be labeled with:
THERMOMARK CARD, BLUEMARK CLED, BLUEMARK LED,
TOPMARK LASER, Mounting type: snapped into marker carrier, Lettering
field: 30 x 5 mm
UCT-EM (30X5) YE
0830340
10
Marker for end clamp, can be ordered: by sheet, yellow, labeled according
to customer specifications, Mounting type: snapped into marker carrier,
Lettering field: 30 x 5 mm
UCT-EM (30X5) YE CUS
0830348
1
Plastic label, Sheet, white, unlabeled, can be labeled with: BLUEMARK
CLED, BLUEMARK LED, Plotter, Mounting type: Adhesive, Lettering
field: 15 x 5 mm
UC-EMLP (15X5)
0819301
10
Plastic label, Sheet, white, unlabeled, can be labeled with: BLUEMARK
CLED, BLUEMARK LED, Plotter, Mounting type: Adhesive, Lettering
field: 15 x 5 mm
UC-EMLP (15X5)L
0820138
5
106006_en_02
PHOENIX CONTACT 3 / 12
MINI MCR-2-UI-UI(-PT)(-C)
Accessories
Type
Order No.
Pcs./Pkt.
Plastic label, Sheet, yellow, unlabeled, can be labeled with: BLUEMARK
CLED, BLUEMARK LED, Plotter, Mounting type: Adhesive, Lettering
field: 15 x 5 mm
UC-EMLP (15X5) YE
0822615
10
Plastic label, can be ordered: by sheet, white, labeled according to
customer specifications, Mounting type: Adhesive, Lettering field: 15 x 5
mm
UC-EMLP (15X5) CUS
0824550
1
Plastic label, can be ordered: by sheet, yellow, labeled according to
customer specifications, Mounting type: Adhesive, Lettering field: 15 x 5
mm
UC-EMLP (15X5) YE CUS
0824551
1
Plastic label, can be ordered: by sheet, white, labeled according to
customer specifications, Mounting type: Adhesive, Lettering field: 15 x 5
mm
UC-EMLP (15X5)L CUS
0824552
1
Plastic label, Sheet, yellow, unlabeled, can be labeled with: BLUEMARK
CLED, BLUEMARK LED, Plotter, Mounting type: Adhesive, Lettering
field: 15 x 5 mm
UC-EMLP (15X5)L YE
0825325
5
Plastic label, can be ordered: by sheet, yellow, labeled according to
customer specifications, Mounting type: Adhesive, Lettering field: 15 x 5
mm
UC-EMLP (15X5)L YE CUS
0826680
1
Plastic label, Sheet, silver, unlabeled, can be labeled with: BLUEMARK
CLED, BLUEMARK LED, Plotter, Mounting type: Adhesive, Lettering
field: 15 x 5 mm
UC-EMLP (15X5) SR
0828095
10
Plastic label, can be ordered: by sheet, silver, labeled according to
customer specifications, Mounting type: Adhesive, Lettering field: 15 x 5
mm
UC-EMLP (15X5) SR CUS
0828099
1
Plastic label, Sheet, silver, unlabeled, can be labeled with: BLUEMARK
CLED, BLUEMARK LED, Plotter, Mounting type: Adhesive, Lettering
field: 15 x 5 mm
UC-EMLP (15X5)L SR
0828103
5
Marker strip, Roll, white, unlabeled, can be labeled with: THERMOMARK
ROLL, THERMOMARK X, THERMOMARK S1.1, THERMOMARK ROLL
X1, Mounting type: Adhesive, Lettering field: continuous x 5 mm
SK 5,0 WH:REEL
0805221
1
Electronics housing
ME 6,2 TBUS-2 1,5/5-ST-3,81 GY
2695439
10
106006_en_02
PHOENIX CONTACT 4 / 12
MINI MCR-2-UI-UI(-PT)(-C)
4
Technical data
Input
Number of inputs
1
Configurable/programmable
Yes
Voltage input signal
0 V ... 5 V (via DIP switch)
1 V ... 5 V (via DIP switch)
-5 V ... 5 V (via DIP switch)
0 V ... 10 V (via DIP switch)
2 V ... 10 V (via DIP switch)
-10 V ... 10 V (via DIP switch)
0 V ... 20 V (via DIP switch)
4 V ... 20 V (via DIP switch)
-20 V ... 20 V (via DIP switch)
0 V ... 24 V (via DIP switch)
4.8 V ... 24 V (via DIP switch)
-24 V ... 24 V (via DIP switch)
0 V ... 30 V (via DIP switch)
6 V ... 30 V (via DIP switch)
-30 V ... 30 V (via DIP switch)
Max. voltage input signal
33 V
Current input signal
0 mA ... 20 mA (via DIP switch)
4 mA ... 20 mA (via DIP switch)
-20 mA ... 20 mA (via DIP switch)
Max. current input signal
24 mA
Input resistance of voltage input
> 1000 kΩ
Input resistance current input
approx. 63 Ω
Output
Number of outputs
1
Voltage output signal
0 V ... 5 V (via DIP switch)
1 V ... 5 V (via DIP switch)
-5 V ... 5 V (via DIP switch)
0 V ... 10 V (via DIP switch)
2 V ... 10 V (via DIP switch)
-10 V ... 10 V (via DIP switch)
Short-circuit current
< 32 mA
Current output signal
0 mA ... 20 mA (via DIP switch)
4 mA ... 20 mA (via DIP switch)
Max. current output signal
22 mA
Non-load voltage
< 17 V
Configurable/programmable
Yes
Load/output load voltage output
≥ 10 kΩ
Ripple
< 20 mVPP (at 600 Ω)
Load/output load current output
≤ 600 Ω (at 20 mA)
Supply
Nominal supply voltage
24 V DC
Supply voltage range
9.6 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81
GN, Order No. 2869728) can be used to bridge the supply voltage. It can be
snapped onto a 35 mm DIN rail according to EN 60715))
Typical current consumption
25 mA (Current output, at 24 V DC incl. load)
54 mA (Current output, at 12 V DC incl. load)
Power consumption
≤ 800 mW (at IOUT = 20 mA, 9.6 V DC, 600 Ω load)
Diagnostic and status indicators
Operating voltage display
106006_en_02
Green LED
PHOENIX CONTACT 5 / 12
MINI MCR-2-UI-UI(-PT)(-C)
General data
Limit frequency (3 dB)
30 Hz (via DIP switch)
5 kHz (via DIP switch)
Maximum transmission error
≤ 0.1 % (of final value)
≤ 0.15 % (of final value, at IN: 4 ... 20 mA / OUT: -10 V ... 10 V)
Maximum temperature coefficient
0.01 %/K
Step response (10-90%)
< 8.5 ms (with 30 Hz filter)
Electrical isolation
Reinforced insulation in accordance with IEC 61010-1
Overvoltage category
II
Mounting position
any
Degree of protection
IP20
Degree of pollution
2
Rated insulation voltage
300 V (effective)
Test voltage, input/output/supply
3 kV (50 Hz, 1 min.)
Dimensions W/H/D
6.2 mm / 110.5 mm / 120.5 mm
Type of housing
PBT gray
Connection data
Screw connection
Solid conductor cross section with ferrule
0.2 mm² ... 1.5 mm²
0.14 mm² ... 2.5 mm²
Solid conductor cross section without ferrule
0.2 mm² ... 2.5 mm²
0.14 mm² ... 2.5 mm²
Conductor cross section, flexible
0.2 mm² ... 1.5 mm²
0.14 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 12
24 ... 12
Stripping length
10 mm
10 mm
Push-in connection
Ambient conditions
Ambient temperature (operation)
-40 °C ... 70 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Permissible humidity (operation)
5 % ... 95 % (non-condensing)
Conformance with EMC Directive 2004/108/EC (valid until 19.04.2016) / 2014/30/EU (valid from 20.04.2016)
Noise immunity according to EN 61000-6-2
When being exposed to interference, there may be minimal deviations.
Noise emission according to EN 61000-6-4
Conformance / approvals
Conformance
CE-compliant
ATEX
II 3 G Ex nA IIC T4 Gc X
UL, USA / Canada
UL 508 Listed
UL, USA / Canada
Class I, Div. 2, Groups A, B, C, D T6
UL, USA / Canada
Class I, Zone 2, Group IIC T6
Shipbuilding DNV GL 14445-15HH
C, EMC2
106006_en_02
PHOENIX CONTACT 6 / 12
MINI MCR-2-UI-UI(-PT)(-C)
5
Safety regulations and installation notes
5.1
Installation notes
•
•
•
•
•
•
•
•
•
•
•
The category 3 device is suitable for installation in
potentially explosive area zone 2. It fulfills the
requirements of EN 60079-0:2012 and EN 6007915:2010.
Installation, operation, and maintenance may only be
carried out by qualified electricians. Follow the
installation instructions as described. When installing
and operating the device, the applicable regulations
and safety directives (including national safety
directives), as well as generally approved technical
regulations, must be observed. The safety data is
provided in this package slip and on the certificates
(conformity assessment, additional approvals where
applicable).
While the devices are in operation, contact-dangerous
voltages may be present on the control elements. For
this reason parameterization, conductor connection,
and opening of the module lid are allowed only when
devices are in a de-energized state unless the
connected circuits are exclusively SELV or PELV
circuits.
The device must not be opened or modified. Do not
repair the device yourself, replace it with an equivalent
device. Repairs may only be carried out by the
manufacturer. The manufacturer is not liable for
damage resulting from violation.
The IP20 protection (IEC 60529/EN 60529) of the
device is intended for use in a clean and dry
environment. The device must not be subject to
mechanical strain and/or thermal loads, which exceed
the limits described.
The device is not designed for use in atmospheres with
a danger of dust explosions.
The device complies with the EMC regulations for
industrial areas (EMC class A). When using the device
in residential areas, it may cause radio interference.
If the device is not used as described in the
documentation, the intended protection can be
negatively affected.
To protect the device against mechanical or electrical
damage, install it in a suitable housing with appropriate
degree of protection as per IEC 60529.
Provide a switch/circuit breaker close to the device,
which is labeled as the disconnecting device for this
device.
Provide for a overcurrent protection device (I ≤ 4 A) in
the installation.
106006_en_02
•
•
•
•
5.2
•
•
•
•
5.3
Thanks to its housing, the device has basic insulation to
the neighboring devices, for 150 Veff. If several devices
are installed next to each other, this has to be taken into
account, and additional insulation has to be installed if
necessary!
The voltages present at the input, output and supply are
extra-low voltages (ELV). Depending on the
application, dangerous voltage (> 30 V) against ground
could occur. For this event, safe electrical isolation from
the other connections has been implemented.
The device must be stopped if it is damaged, has been
subjected to an impermissible load, stored incorrectly,
or if it malfunctions.
Only use copper connecting cables providing the
permitted temperature range (60°C/75°C).
Installation in Zone 2
Observe the specified conditions for use in potentially
explosive areas! Install the device in a suitable
approved housing (with a minimum of IP54 protection)
that meets the requirements of EN 60079-15. Observe
the requirements of EN 60079-14.
Only devices which are designed for operation in Ex
zone 2 and are suitable for the conditions at the
installation location may be connected to the circuits in
the Ex zone.
In potentially explosive areas, terminals may only be
snapped onto or off the DIN rail connector and wires
may only be connected or disconnected when the
power is switched off.
The device must be stopped and immediately removed
from the Ex area if it is damaged, was subject to an
impermissible load, stored incorrectly or if it
malfunctions.
UL Notes
INDUSTRIAL CONTROL EQUIPMENT FOR
HAZARDOUS LOCATIONS 45FP
1 Suitable for use in class 1, division 2, groups A, B, C and
D hazardous locations, or nonhazardous locations only.
2 WARNING - EXPLOSION HAZARD: Do not disconnect
equipment unless power has been removed or the area
is known to be non-hazardous.
3 WARNING - EXPLOSION HAZARD: Substitution of any
components may impair suitability for Class I, Division
2.
4 This device is open-type and is required to be installed
in an enclosure suitable for the environment and can
only be accessed with the use of a tool or key.
PHOENIX CONTACT 7 / 12
MINI MCR-2-UI-UI(-PT)(-C)
6
Installation
6.1
Connection notes
6.3
Block diagram
The device contains components that can be
damaged or destroyed by electrostatic
discharge. When handling the device,
observe the necessary safety precautions
against electrostatic discharge (ESD)
according to EN 61340-5-1 and IEC 61340-51.
US
OUT
IN
Sensor / Field
TI–
+ 1
OUT
1
U,I
IN U, I+
4-wire
GND
– 2
2
+ 3
– 4
PLC / DCS
TI+
5 +
OUT U, I+
active
5
passive
6 –
OUT U, I–
IN U, I–
PWR+
PWR+
PWR–
6
7 +
PWR–
8 –
FM
Structure
PWR–
PWR+
6.2
2
1
Zone 2
3
12
Figure 2
4
11
5
9
Supply via the module
6
7
8
Structure
Green “PWR” LED, power supply
Cover with labeling option
Voltage/current input
DIP switch S1
Supply voltage
NFC coil
Universal snap-on foot for EN DIN rails
Connection for DIN rail connector
Spindle screw
DIP switch S2
Voltage output / current output
Current measuring socket
106006_en_02
You must refer to the MACX and MINI Analog power manual
for the design of the power supply.
Never connect the supply voltage directly
to the DIN rail connector. Drawing power
from individual devices is not permitted!.
5
1
2
3
4
5
6
7
8
9
10
11
12
Power supply
NOTE
10
Figure 1
6.4
Block diagram
Where the total current consumption of the aligned modules
does not exceed 400 mA, the power can be supplied directly
at the connection terminal blocks of the module.
We recommend connecting a 630 mA fuse (normal-blow or
slow-blow) upstream.
Supply via a power terminal block
The MINI MCR-2-PTB power terminal block (Order No.
2902066) or the MINI MCR-2-PTB-PT power terminal block
(Order No. 2902067) of the same shape is used to supply
the supply voltage to the DIN rail connector.
We recommend connecting a 4 A fuse upstream.
PHOENIX CONTACT 8 / 12
MINI MCR-2-UI-UI(-PT)(-C)
Supply via a system power supply unit
Screw connection:
The system power supply unit with 1.5 A output current
connects the DIN rail connector to the supply voltage and
can thus be used to supply several modules from the mains.
– MINI-SYS-PS-100-240AC/24DC/1.5 (Order No.
2866983)
– Potentially explosive areas:
MINI-PS-100-240AC/24DC/1.5/EX (Order No.
2866653)
6.5
AWG 26-16
2
0,2-1,5 mm
MINI MCR-2-…
B
10 mm
Assembly
A
A
B
Figure 4
C
•
E
0,5-0,6 Nm
5-7 lb ln
Screw connection
Insert the wire into the corresponding connection
terminal block.
Use a screwdriver to tighten the screw in the opening
above the connection terminal block.
•
D
Push-in connection:
AWG 26-12
0,2-2,5 mm2
Figure 3
–
–
6.6
FASTCON Pro plugs
The device has pluggable connection terminals with an
integrated test disconnect terminal block, with either push-in
or screw-in connection technology.
You can plug or screw the FASTCON Pro plugs onto the
device directly without tools. You can use the integrated
spindle screw to easily remove the plugs from the module or
set the isolating position, even when the plugs are
connected. For this purpose, use a screwdriver of sufficient
width, e.g. SZF 1-0.6x3.5 (order number: 1204517).
4-way coding prevents incorrect insertion into the module.
106006_en_02
A
10 mm
Mounting and removing
Mount the module on a 35 mm DIN rail according to EN
60715.
When using the DIN rail connector, first place it into the
DIN rail (see A – C). It is used to bridge the power
supply. It is also absolutely vital that you snap the
module and the DIN rail connector into position in the
correct direction: the snap-on foot should be at the
bottom and the connector on the left.
MINI MCR-2-…-PT
A
B
Figure 5
•
6.7
Push-in connection
Insert the wire into the corresponding connection
terminal block.
Fault monitoring FM
A module or power supply failure is reported to the formmatched MINI MCR-2-FM-RC fault monitoring module
(order number 2904504) or MINI MCR-2-FM-RC-PT fault
monitoring module (order number 2904508) via the DIN rail
connector. The module reports the error centrally via an N/C
contact.
A fault monitoring module is only required once in a group.
There is no need for individual evaluation of up to 115
connected Mini Analog Pro signal conditioners.
PHOENIX CONTACT 9 / 12
MINI MCR-2-UI-UI(-PT)(-C)
6.8
Current measurement
The device allows current measurement without
disconnection of the conductors by means of integrated test
disconnect terminals.
Test sockets which support current measurement are
marked TI+ or TI-.
For the current measurement, use 2 mm probe tips of the
type Fluke TL75-1 or probe tips with a comparable tip shape.
Figure 6
Test disconnect terminal block
Furthermore, individual circuits can be specifically
disconnected, e.g. for commissioning.
You can set the isolating position by turning the integrated
spindle screw through 180°. The isolating position is
indicated by the marking on the plugs.
Figure 7
6.9
Disconnect position
Marking
Standard UCT-EM... or UC-EMLP tags are available for
marking the devices and can be printed as per customer
requirements. In addition, the covers provide enough space
for the use of freely chosen sticky labels such as SK 5.0
WH:REEL without concealing the LED diagnostic
indicators.
106006_en_02
PHOENIX CONTACT 10 / 12
MINI MCR-2-UI-UI(-PT)(-C)
7
Configuration
Standard configuration for devicesnot configured to order:
Input 0...10 V, output 0...20 mA (all DIP switches in the "off"
position; transmission error